16.2.3
16.2.4
16.3
16.4
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
All outputs (for fire alarm) are reset, i.e. de-activated.
If a key cabinet is installed, the key (to the building) has to be put
back into the key cabinet within 5 minutes. If not, a fault will be
generated and a fault message will be shown in the display, see
chapter "Key cabinet alarm reset", page 51.

Single with automatic disablement

Like "Single reset" but incl. the so called encapsulation function:
Normally when an alarm point or zone having activated fire alarm is
reset when it still is in alarm status, it will activate a new fire alarm
within 20 seconds. (In accordance with the EN54-2 standard.)
When "Single with automatic disablement" reset is performed, an
alarm point or zone, still in alarm status, will not only be reset but also
disabled, i.e. it will not activate a new fire alarm within 20 seconds.
It has to be re-enabled via menu H2/B5 before it can activate a new
fire alarm. (This function, set via WinG3, is a violation to the EN54-2
standard.)
LED Fault / Disablements "General disablements" (L10) is
indicating one or more disablements in the system.

Acknowledged and Isolated alarm

Acknowledged alarm and Isolated alarm are fire alarm functions
only used in New Zealand.
Acknowledged alarm
Acknowledged alarms have to be reset like normal fire alarms.
Isolated alarm
Isolated alarms have to be reset like normal fire alarms.
Isolated alarms also have to be re-enabled via menu H2/B4 or B5
before they can activate a new fire alarm again.

Heavy smoke / heat alarm reset

If a heavy smoke / heat alarm has been activated, it will be reset at the
same time as the corresponding fire alarm is reset. Also the output(s)
will be reset, i.e. de-activated.

Alert Annunciation

Regarding the function, see chapter "Alert Annunciation alarm (AA
alarm)", page 44 and EBL512 G3 Planning Instructions, chapter
"Alert annunciation". Reset of the AA alarm(s) can be done via push
button "Reset" on an AA unit 1735 / 1736 or an AA controller 1740
(or in the c.i.e.).
NOTE! Reset via an AA unit is possible only during the investigation
time and of AA alarm(s) only (not normal fire alarms). If more than
one AA alarm is activated, they will be reset all at a time.