Panasonic Electric Works Nordic AB
MEW01091
25.6
Action
"Access"
Scroll to menu H2:
"A"
Scroll to menu B6.
"A"
"A"
Rev: 3
Re-enable zone / address (H2/B6)
Disabled alarm points (zone – address) are listed in menu H4/U1.
Re-enabling via this menu has higher priority than automatic re-
enabling.
Alarm points disabled via the "Encapsulation function", see chapter
"Single encapsulated reset" page 50, have to be re-enabled via this
menu before they can activate a new alarm.
Alarm points (zone – address) disabled when the "New Zealand FB
Silence switch" (outside switch) is turned OFF, have to be re-enabled
via menu B5 or B6 before they can activate a new alarm.
See also chapter "Perform monthly test (H1)", page 79 and chapter
"Perform ZONE TEST (test mode) (H7)", page 116.
When all alarm points have been re-enabled, the LED "Disablements"
(L8) will be turned OFF, if there are no other disablements.
Text in display
Disable or re-enable
Disable zone
Re-enable zone / address
Re-enable zone: 00 Address: 00
Re-enable zone / address
EBL128 Operating Instructions V1.1.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B6
ACCEPT?
ACCEPT? B6
87
Comments
According to chapter
"Access", see page 78.
If there are no zone -
addresses to re-enable,
L
menu B6 will be shown
again. L=a list in which
you can scroll. If it's the
correct zone - address to
re-enable, press "A" to
accept. If not, scroll or
write the wanted zone -
address and press "A" to
accept.
If more re-enablements
shall be done, continue like
above. If not, scroll or
press "Return" to menu
H2. Scroll or press
"Return" to log off.