Exhaust Air And Supply Air Ducting Cross-Sections; Exhaust Gas Values; Room Ventilation Opening For Air Intake From The Setup Room - Miele PRI318 G Installations Plan

Commercial ironer (gas heating)
Table of Contents

Advertisement

Installation notes

Exhaust air and supply air ducting cross-sections

Exhaust gas values

Exhaust gas emissions*
Temperature*
CO
content*
2
Fan power**
Maximum permitted counter pressure
* Example value
** At 0 mbar counter pressure

Room ventilation opening for air intake from the setup room

The minimum dimension of the ventilation opening depends on the cross-section of the
vent pipe.
100 mm
-
120 mm
-
150 mm
-
180 mm
-
200 mm
-
220 mm
-
250 mm
-
300 mm
-
12
Model
PRI 318/418/421 gas
PRI318
160 g/s
120 °C
0.6 %
530 m³/h
200 Pa
Vent pipe
A
-
79 cm²
100 mm
100 cm²
-
113 cm²
120 mm
144 cm²
-
177 cm²
150 mm
225 cm²
-
254 cm²
180 mm
324 cm²
-
314 cm²
200 mm
400 cm²
-
380 cm²
220 mm
484 cm²
-
491 cm²
250 mm
625 cm²
-
707 cm²
300 mm
900 cm²
Cross-sections of vent outlets
PRI418
101 g/s
130 °C
1.0 %
530 m³/h
200 Pa
Minimum dimension for ventilation opening
A
237 cm²
175 mm
300 cm²
200 mm
339 cm²
210 mm
432 cm²
235 mm
531 cm²
260 mm
675 cm²
295 mm
762 cm²
315 mm
972 cm²
355 mm
942 cm²
350 mm
1200 cm²
395 mm
1140 cm²
381 mm
1452 cm²
430 mm
1473 cm²
435 mm
1875 cm²
490 mm
2121 cm²
520 mm
2700 cm²
590 mm
113 cm²
PRI421
122 g/s
130 °C
1.0 %
530 m³/h
200 Pa
155 mm
175 mm
185 mm
210 mm
230 mm
260 mm
280 mm
315 mm
310 mm
350 mm
377 mm
382 mm
385 mm
435 mm
460 mm
520 mm