Panasonic Aquarea WH-ADC0309J3E5 Planning And Installation Manual page 44

Air-to-water heat pumps
Hide thumbs Also See for Aquarea WH-ADC0309J3E5:
Table of Contents

Advertisement

Product Description
All in One systems | Aquarea T-CAP | H Generation | Single Phase / Three Phase | Heating and
Cooling | R410A
Kit
Heating capacity / COP (A +7 °C, W 35 °C)
Heating capacity / COP (A +7 °C, W 55 °C)
Heating capacity / COP (A +2 °C, W 35 °C)
Heating capacity / COP (A +2 °C, W 55 °C)
Heating capacity / COP (A -7 °C, W 35 °C)
Heating capacity / COP (A -7 °C, W 55 °C)
Cooling capacity / EER (A 35 °C, W 7 °C)
Cooling capacity / EER (A 35 °C, W 18 °C)
ErP data for Space Heating
Seasonal energy efficiency (ηs,h)
Average climate
SCOP
Energy class
Seasonal energy efficiency (ηs,h)
Warm climate
SCOP
Energy class
Seasonal energy efficiency (ηs,h)
Cold climate
SCOP
Energy class
Indoor unit
Sound pressure
Heat / Cool
Dimension
H x W x D
Net weight
Water pipe connector
Number of speeds
A class pump
Input power (Min / Max)
4
Heating water flow (∆T=5 K. 35 °C)
Capacity of integrated electric heater
Recommended fuse
Recommended cable size, supply 1 / 2
Water volume
Maximum water temperature
Material inside tank
Tapping profile according EN16147
ErP data for Water Heating
Seasonal energy efficiency (ηw,h)
Average climate
SCOP
Energy class
Seasonal energy efficiency (ηw,h)
Warm climate
SCOP
Energy class
Seasonal energy efficiency (ηw,h)
Cold climate
SCOP
Energy class
Outdoor unit
Sound power
Heat
3
Dimension / Net weight H x W x D
Refrigerant (R410A) / CO
Eq.
2
Pipe diameter
Liquid / Gas
Pipe length range / Elevation difference (in/out)
Pipe length for additional gas / Additional gas amount
Outdoor ambient
Operation range
Water outlet
1 Scale from A+++ to D.
2 Scale from A+ to F.
3 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Notes:
EER and COP calculation is based in accordance to EN14511.
This product is designed to comply with the European Water Quality Directive 98/83/EC amended by 2015/1787/EU. The lifespan of the product is not guaranteed in the case of the use of
groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to
these cases are the customer's responsibility.
44
kW / –
kW / –
kW / –
kW / –
kW / –
kW / –
kW / –
kW / –
W35 / W55
%
W35 / W55
W35 / W55
1
W35 / W55
%
W35 / W55
W35 / W55
1
W35 / W55
%
W35 / W55
W35 / W55
1
dB(A)
mm
kg
Inch
W
l/min
kW
A
mm²
l
°C
%
2
%
2
%
2
dB(A)
mm / kg
kg / t
Inch (mm)
m / m
m / g/m
Heat
°C
Cool
°C
Heat
°C
Cool
°C
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Single phase (Power to indoor)
KIT‑AXC09HE5
KIT‑AXC12HE5
9.00 / 4.84
12.00 / 4.74
9.00 / 2.94
12.00 / 2.88
9.00 / 3.59
12.00 / 3.44
9.00 / 2.21
12.00 / 2.19
9.00 / 2.85
12.00 / 2.72
9.00 / 2.02
12.00 / 1.92
7.00 / 3.17
10.00 / 2.81
7.00 / 5.19
10.00 / 5.13
181 / 130
170 / 130
4.59 / 3.32
4.32 / 3.32
A+++ / A++
A++ / A++
235 / 158
231 / 158
5.95 / 4.02
5.86 / 4.02
A+++ / A+++
A+++ / A+++
160 / 125
160 / 125
4.08 / 3.20
4.08 / 3.20
A++ / A++
A++ / A++
WH‑ADC1216H6E5
WH‑ADC1216H6E5
33 / 33
33 / 33
1,800 x 598 x 717
1,800 x 598 x 717
124
124
R 1¼
R 1¼
Variable Speed
Variable Speed
36 / 152
36 / 152
25.8
34.4
6
6
30 / 30
30 / 30
3 x 4.0 / 3 x 4.0
3 x 4.0 / 3 x 4.0
185
185
65
65
Stainless steel
Stainless steel
L
L
95
95
2.37
2.37
A
A
110
110
2.75
2.75
A
A
75
75
1.87
1.87
A
A
WH‑UX09HE5
WH‑UX12HE5
66
66
1,340 x 900 x 320 / 101
1,340 x 900 x 320 / 101
2.85 / 5.951
2.85 / 5.951
3/8 (9.52) / 5/8 (15.88)
3/8 (9.52) / 5/8 (15.88)
3 ~ 30 / 20
3 ~ 30 / 20
10 / 50
10 / 50
-28 ~ +35
-28 ~ +35
+16 ~ +43
+16 ~ +43
20 ~ 60
20 ~ 60
5 ~ 20
5 ~ 20
Three phase (Power to indoor)
KIT‑AXC09HE8
KIT‑AXC12HE8
9.00 / 4.84
12.00 / 4.74
9.00 / 2.94
12.00 / 2.88
9.00 / 3.59
12.00 / 3.44
9.00 / 2.21
12.00 / 2.19
9.00 / 2.85
12.00 / 2.72
9.00 / 2.02
12.00 / 1.92
7.00 / 3.17
10.00 / 2.81
7.00 / 5.19
10.00 / 5.13
181 / 130
170 / 130
4.59 / 3.32
4.32 / 3.32
A+++ / A++
A++ / A++
235 / 158
231 / 158
5.95 / 4.02
5.86 / 4.02
A+++ / A+++
A+++ / A+++
160 / 125
160 / 125
4.08 / 3.20
4.08 / 3.20
A++ / A++
A++ / A++
WH‑ADC0916H9E8
WH‑ADC0916H9E8
33 / 33
33 / 33
1,800 x 598 x 717
1,800 x 598 x 717
126
126
R 1¼
R 1¼
Variable Speed
Variable Speed
36 / 152
36 / 152
25.8
34.4
9
9
16 / 16
16 / 16
5 x 1.5 / 5 x 1.5
5 x 1.5 / 5 x 1.5
185
185
65
65
Stainless steel
Stainless steel
L
L
95
95
2.37
2.37
A
A
110
110 /
2.75
2.75
A
A
75
75
1.87
1.87
A
A
WH‑UX09HE8
WH‑UX12HE8
65
65
1,340 x 900 x 320 / 108
1,340 x 900 x 320 / 108
2.85 / 5.951
2.85 / 5.951
3/8 (9.52) / 5/8 (15.88)
3/8 (9.52) / 5/8 (15.88)
3 ~ 30 / 20
3 ~ 30 / 20
10 / 50
10 / 50
-28 ~ +35
-28 ~ +35
+16 ~ +43
+16 ~ +43
20 ~ 60
20 ~ 60
5 ~ 20
5 ~ 20
KIT‑AXC16HE8
16.00 / 4.28
16.00 / 2.71
16.00 / 3.10
16.00 / 2.13
16.00 / 2.49
16.00 / 1.86
12.20 / 2.57
12.20 / 3.49
160 / 125
4.08 / 3.20
A++ / A++
231 / 159
5.86 / 4.05
A+++ / A+++
150 / 125
3.83 / 3.20
A++ / A++
WH‑ADC0916H9E8
33 / 33
1,800 x 598 x 717
126
R 1¼
Variable Speed
36 / 152
45.9
9
16 / 16
5 x 1.5 / 5 x 1.5
185
65
Stainless steel
L
91 /
2.27
A
107
2.67
A
72
1.80
B
WH‑UX16HE8
67
1,340 x 900 x 320 / 118
2.90 / 6.055
3/8 (9.52) / 5/8 (15.88)
3 ~ 30 / 20
10 / 50
-28 ~ +35
+16 ~ +43
20 ~ 60
5 ~ 20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents