Demand - GE Multilin 489 Instruction Manual

Generator management relay
Hide thumbs Also See for Multilin 489:
Table of Contents

Advertisement

CHAPTER 5: SETPOINTS

5.11.5 Demand

CURRENT
MW DEMAND
Mvar DEMAND
MVA DEMAND
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
PATH: SETPOINTS
S10 MONITORING
CURRENT DEMAND
[ ]
PERIOD: 15 min.
CURRENT DEMAND
MESSAGE
ALARM: Off
ASSIGN ALARM
MESSAGE
RELAYS (2-5): ---5
CURRENT DEMAND
MESSAGE
LIMIT: 1.25 x FLA
CURRENT DEMAND
MESSAGE
ALARM EVENTS: Off
[ ]
MW DEMAND
PERIOD: 15 min.
MW DEMAND
MESSAGE
ALARM: Off
ASSIGN ALARM
MESSAGE
RELAYS (2-5): ---5
MW DEMAND
MESSAGE
LIMIT: 1.25 x Rated
MW DEMAND
MESSAGE
ALARM EVENTS: Off
[ ]
Mvar DEMAND
PERIOD: 15 min.
Mvar DEMAND
MESSAGE
ALARM: Off
ASSIGN ALARM
MESSAGE
RELAYS (2-5): ---5
Mvar DEMAND
MESSAGE
LIMIT: 1.25 x Rated
Mvar DEMAND
MESSAGE
ALARM EVENTS: Off
[ ]
MVA DEMAND
PERIOD: 15 min.
MVA DEMAND
MESSAGE
ALARM: Off
ASSIGN ALARM
MESSAGE
RELAYS (2-5): ---5
MVA DEMAND
MESSAGE
LIMIT: 1.25 x Rated
CURRENT DEMAND...
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to
5
Range: 0.10 to 20.00 × FLA in steps of
0.01
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to
5
Range: 0.10 to 2.00 × Rated in steps of
0.01
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to
5
Range: 0.10 to 2.00 × Rated in steps of
0.01
Range: On, Off
Range: 5 to 90 min. in steps of 1
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to
5
Range: 0.10 to 2.00 × Rated in steps of
0.01
5–93