GE Multilin 489 Instruction Manual page 184

Generator management relay
Hide thumbs Also See for Multilin 489:
Table of Contents

Advertisement

Note
5–74
Courtesy of NationalSwitchgear.com
100000
10000
1000
100
10
1.00
0.10
1.00
FIGURE 5–15: 489 Standard Overload Curves
Above 8.0 × Pickup, the trip time for 8.0 is used. This prevents the overload curve from
acting as an instantaneous element.
The standard overload curves equation is:
Time to Trip
--------------------------------------------------------------------------------------------------------------------------------------------- -
=
0.02530337
x15
x1
10
MULTIPLE OF FULL LOAD AMPS
×
Curve Multiplier
2.2116623
2
(
Pickup 1
)
×
0.05054758
+
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
100
1000
806804A5.CDR
(EQ 5.31)
(
Pickup 1
)
×