Rtd S 7 To 10 - GE Multilin 489 Instruction Manual

Generator management relay
Hide thumbs Also See for Multilin 489:
Table of Contents

Advertisement

5.9.3
RTDs 7 to 10
1 RTD #7
5–66
Courtesy of NationalSwitchgear.com
PATH: SETPOINTS
S8 RTD TEMPERATURE
[ ]
RTD #7 APPLICATION:
Bearing
RTD #7 NAME:
MESSAGE
RTD #7 ALARM:
MESSAGE
Off
ASSIGN ALARM
MESSAGE
RELAYS (2-5): ---5
RTD #7 ALARM
MESSAGE
TEMPERATURE: 80°C
RTD #7 ALARM
MESSAGE
EVENTS: Off
RTD #7 TRIP:
MESSAGE
Off
RTD #7 TRIP VOTING:
MESSAGE
RTD #7
ASSIGN TRIP
MESSAGE
RELAYS (1-4): 1---
RTD #7 TRIP
MESSAGE
TEMPERATURE: 90°C
RTDs 7 through 10 default to Bearing RTD type. There are individual alarm and trip
configurations for each RTD. This allows one of the RTDs to be turned off if it malfunctions.
The alarm level and the trip level are normally set slightly above the normal running
temperature, but below the bearing temperature rating. Trip voting has been added for
extra reliability in the event of RTD malfunction. If enabled, a second RTD must also exceed
the trip temperature of the RTD being checked before a trip will be issued. If the RTD is
chosen to vote with itself, the voting feature is disabled. Each RTD name may be changed if
desired.
CHAPTER 5: SETPOINTS
RTD #7(10)
Range: Stator, Bearing, Ambient, Other,
None
Range: 8 alphanumeric characters
Range: Off, Latched, Unlatched
Range: Any combination of Relays 2 to
5.
Range: 1 to 250°C in steps of 1
Range: On, Off
Range: Off, Latched, Unlatched
Range: RTD #1 to RTD #12
Range: Any combination of Relays 1 to
4
Range: 1 to 250°C in steps of 1
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL