10. Install the H201Ti horizontally; not at an angle, vertically or horizontally using an
elbow (see Figure 6-6 below). Elbows may cause turbulence that can reduce the
accuracy of gas level readings. For details pertaining to the positioning of
H201Ti's, see Section 6.2.2.3.
11. Do not subject the H201Ti or its sensor to high-pressure water streams (see Figure
6-7 below). Used during the cleaning of transformers, they may cause serious
damage.
Page 84
Figure 6-6: Do Not Install the H201Ti on an Elbow
Figure 6-7: Avoid High Pressure Water Streams