Gas Submenu - GE Hydran 201i Instruction Manual

Transformer gas monitoring system
Hide thumbs Also See for Hydran 201i:
Table of Contents

Advertisement

Hydran* 201i Instruction Manual
5.5.2

Gas Submenu

The Gas submenu allows the user to set the parameters of the conditions that trigger:
• The gas alarm: A High or High-High alarm is triggered if an alarm condition
(GasLevel, HourlyTrend or DailyTrend) exceeds the corresponding High or High-
High alarm set point for a period of time greater than the delay.
• The fail alarm: It is triggered if an alarm condition (GasLevel, HourlyTrend or
DailyTrend) is below the corresponding Low or Low-Low alarm set point for a
period of time greater than the delay.
The operation of the alarms is explained in detail in Chapter 11.
5.5.2.1
Gas Level
This function gives access to the gas level High and High-High alarm parameters:
• GasLevel: Current reading of gas level, in ppm. Same value as the one shown in
the Main Display mode.
• GasAlr H: Set point of gas level High alarm.
• GasAlr HH: Set point of gas level High-High alarm.
• GasAlr Delay: Alarm delay for all gas level alarms' set points.
• GasAlr L (Extended Menu only): Set point of gas level Low alarm.
• GasAlr LL (Extended Menu only): Set point of gas level Low-Low alarm.
5.5.2.2
Hourly Trend
This function gives access to the hourly trend High and High-High alarm parameters:
• HourlyTrend: Current reading of hourly trend, in ppm/x hours. Same value as the
one shown in the Main Display mode.
• HourTrAlr H: Set point of hourly trend High alarm.
• HourTrAlr HH: Set point of hourly trend High-High alarm.
• HourTrAlr Delay: Alarm delay for all hourly trend alarms' set points, in % of the
period.
• HourlyTr Period (Extended Menu only): Period of the hourly trend (number of
hours used to calculate the gas level variation).
• HourTrAlr L (Extended Menu only): Set point of hourly trend Low alarm.
• HourTrAlr LL (Extended Menu only): Set point of hourly trend Low-Low alarm.
5.5.2.3
Daily Trend
This function gives access to the daily trend High and High-High alarm parameters:
• DailyTrend: Current reading of daily trend, in ppm/x days. Same value as the one
shown in the Main Display mode.
• DayTrAlr H: Set point of daily trend High alarm.
• DayTrAlr HH: Set point of daily trend High-High alarm.
• DayTrAlr Delay: Alarm delay for all daily trend alarms' set points, in % of the
period.
MA-033
Rev. 14.0, 12-Nov-18
Page 69

Advertisement

Table of Contents
loading

Table of Contents