Standby Battery Requirements And Calculations - Bosch Conettix B465 Installation And Operation Manual

Universal dual path communicator
Hide thumbs Also See for Conettix B465:
Table of Contents

Advertisement

98
en | Specifications and certifications
12.1.3

Standby battery requirements and calculations

Model Number
B465
B46
B440
B441
B442
B443
B444
Aux Power
(0 - 500 mA)
____
____
Table 12.19: Current rating chart for standby battery calculations
Notice!
Maximum power supply current for Total B in the table above is 705 mA, and the maximum
power supply current for Total C is 900 mA.
Total B
( _______
_
1
Refer to the Application environment table.
2
Value = Minutes of alarm operation/60 as per the Application environment table.
3
Total Ah requirements must not exceed the Ah capacity of batteries:
2017.11 | 05 | F.01U.311.207
Qty
Used
1
______
______
______
______
______
______
______
______
______
Hours
1
Total C
x
_______
+
( ________
)
One D126 Battery = 7 Ah
One D1218 Battery = 18 Ah
Installation and Operation Manual
B
Standby Power On Normal
Current (mA)
Each
Qty
Total
Unit
150
x 1
= 150
23
x 1
= ____
35
x 1
= ____
35
x 1
= ____
35
x 1
= ____
35
x 1
= ____
35
x 1
= ____
_____
x Qty
= ______
_____
x Qty
= ______
_____
x Qty
= ______
Total B = ____
Alarm
Operation
2
x
________________)
Conettix Universal Dual Path Communicator
C
Alarm Current (mA)
Each Unit Qty
Total
230
x 1
= 230
23
x 1
= ____
150
x 1
= ____
150
x 1
= ____
150
x 1
= ____
150
x 1
= ____
150
x 1
= ____
______
x Qty
= ______
______
x Qty
= ______
______
x Qty
= ______
Total C = ____
Contingency
+
20%
= _________
Bosch Security Systems, Inc.
Total Ah
3