3.8.3

Fault References

The fault references are discussed in Chapter 9 of this manual but are also listed here for your
convenience.
System Fault References
System Fault
Description
Ref
#ANY_FLT
Any new fault in either table since the last power-up or clearing of the fault tables
#SY_FLT
Any new system fault in the CPU fault table since the last power-up or clearing of
the fault tables
#IO_FLT
Any new fault in the I/O Fault Table since the last power-up or clearing of fault
tables
#SY_PRES
Indicates that there is at least one entry in the CPU fault table
#IO_PRES
Indicates that there is at least one entry in the I/O Fault Table
#HRD_FLT
Any hardware fault
#SFT_FLT
Any software fault
Configurable Fault References
Configurable Faults
(Default Action)
#SBUS_ER (diagnostic) System bus error. (The BSERR signal was generated on the VME system bus.)
#SFT_IOC (diagnostic) Non-recoverable software error in a Genius Bus Controller.
#LOS_RCK (diagnostic) Loss of rack (BRM failure, loss of power) or missing a configured rack.
#LOS_IOC (diagnostic) Loss of Bus Controller missing a configured Bus Controller.
#LOS_IOM (diagnostic) Loss of I/O module (does not respond) or missing a configured I/O module.
#LOS_SIO (diagnostic) Loss of intelligent option module (does not respond) or missing a configured
#IOC_FLT (diagnostic)
#CFG_MM (fatal)
GFK-2950C
Description
module.
Non-fatal bus or Bus Controller error—more than 10 bus errors in 10 seconds (error
rate is configurable).
Wrong module type detected during power-up, store of configuration, or RUN Mode.
The CPU does not check the configuration parameters set up for individual modules
such as Genius I/O blocks.