System Fault References - GE PACSystems RX7i Cpu Programmer's Reference Manual

Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

9.3.1

System Fault References

When a system fault reference is set, additional fault references are also set. These other types of
faults are listed in Fault References for Configurable Faults below and Fault References for Non-
Configurable Faults in the section which follows.
Fault References for Configurable Faults
Fault
(Default
Address
Action)
#SBUS_ER
%SA0032 System bus error. All system bus error faults
(diagnostic)
#SFT_IOC
13
%SA0029 Non-recoverable software error in an I/O
(diagnostic)
#LOS_RCK
14
%SA0012 Loss of rack (BRM failure, loss of power) or
(diagnostic)
#LOS_IOC
15
%SA0013 Loss of I/O Controller or missing a configured
(diagnostic)
#LOS_IOM
%SA0014 Loss of I/O module (does not respond), or
(diagnostic)
#LOS_SIO
%SA0015 Loss of intelligent module (does not respond),
(diagnostic)
#IOC_FLT
%SA0022 Non-fatal bus or I/O Controller error, more than
(diagnostic)
#CFG_MM
%SA0009 Configuration mismatch. Wrong module type
(fatal)
#OVR_TMP
%SA0008 CPU temperature has exceeded its normal
(diagnostic)
Note: If the fault action for a fault logged to the fault table is informational, the configured action is
not used. For example, if the logged fault action for an SBUS_ERR is informational, but you
configure it as fatal, the action is still informational.
The #SFT_IOC software fault will have the same action as what you set for #LOS_IOC.
13
14
When a Loss of Rack or Addition of Rack fault is logged, individual loss or add faults for each module in that rack are
usually not generated.
15
Even if the #LOS_IOC fault is configured as Fatal, the CPU will not go to STOP/FAULT unless both GBCs of an internal
redundant pair fail.
GFK-2950C
Description
are logged as informational.
Controller (IOC).
missing a configured rack.
Bus Controller.
missing a configured I/O module.
or missing a configured module.
10 bus errors in 10 seconds. (Error rate is
configurable.)
detected. The CPU does not check the
configuration parameter settings for individual
modules such as Genius I/O blocks.
operating temperature.
February 2018
Chapter 9. Diagnostics
May Also Be Set
#HRD_FLT, #SY_PRES,
#SY_FLT
#IO_FLT, #IO_PRES,
#SFT_FLT
#SY_FLT, #SY_PRES,
#IO_FLT, #IO_PRES
#IO_FLT, #IO_PRES
#IO_FLT, #IO_PRES
#SY_FLT, #SY_PRES
#IO_FLT, #IO_PRES
#SY_FLT, #SY_PRES
#SY_FLT, #SY_PRES
391