489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
Table CG–8: Analog Inputs Point List (Sheet 3 of 5)
INDEX
FORMAT
Ground Current Scale Factor. Will always be a
60
F1
power of 10 (1, 10, 100, etc.). Changes only when
the configuration setpoints are changed.
Ground Current (scaled according to the previous
61
F3
point)
62
F1
Phase A-B Voltage
63
F1
Phase B-C Voltage
64
F1
Phase C-A Voltage
65
F1
Average Line Voltage
66
F1
Phase A-N Voltage
67
F1
Phase B-N Voltage
68
F1
Phase C-N Voltage
69
F1
Average Phase Voltage
70
F3
Per Unit Measurement Of V/Hz
71
F3
Frequency
72
F1
Fundamental Frequency Neutral Voltage (volts)
Fundamental Frequency Neutral Voltage (tenths of
73
F10
a volt)
74
F1
Third Harmonic Neutral Voltage (volts)
75
F10
Third Harmonic Neutral Voltage (tenths of a volt)
76
F1
Third Harmonic Terminal Voltage (volts)
77
F10
Third Harmonic Terminal Voltage (tenths of a volt)
78
F2
Vab/Iab (loss of excitation impedance)
79
F1
Vab/Iab Angle (loss of excitation impedance angle)
80
F6
Power Factor
81
F1
Real Power (MW)
82
F1
Real Power (kW)
83
F1
Reactive Power (Mar)
84
F1
Reactive Power (kvar)
85
F1
Apparent Power (MVA)
86
F1
Apparent Power (kVA)
87
F1
Hottest Stator RTD
88
F4
Hottest Stator RTD Temperature (°C)
89
F4
RTD #1 Temperature (°C)
90
F4
RTD #2 Temperature (°C)
91
F4
RTD #3 Temperature (°C)
DESCRIPTION
EVENT CLASS
NOTES
ASSIGNED TO
Class 1
Note 3
Class 2
Class 2
Class 2
Class 2
Class 2
Class 2
Class 2
Class 2
Class 2
Class 2
Class 2
Note 2
Class 2
Note 10
Class 2
Note 10
Class 2
Note 10
Class 2
Note 10
Class 2
Note 10
Class 2
Note 10
Class 2
Class 2
Class 2
Class 2
Note 8
Class 2
Note 8
Class 2
Note 8
Class 2
Note 8
Class 2
Note 8
Class 2
Note 8
Class 2
Note 3
Class 2
Class 2
Class 2
Class 2