INSTALLATION
CONFIGURATION
SWITCHES
2–6
Table 2–5: D485 status indicators
Number
Description
1
Network status
2
Module status
3
Not used
4
Not used
5
Modbus
status *
6
Device status
*
This LED turns green when all transactions have been active at least once. This includes any
transactions using "change of state" or "change of state on trigger". If a timeout occurs on a
transaction, this LED will turn red.
The configuration switches are used to set the DeviceNet MAC ID and baud rate settings.
Normally, these switches are covered by a plastic hatch. Note that the node address can
not be changed during runtime, i.e. the D485 requires a reset for any changes to have
effect. Recycle the power supply to reset the module.
Figure 2-10: D485 configuration switches
State
Status
Off
Not powered / not online
Green
Link OK, online, connected
Green flashing
Online, not connected
Red
Critical link failure
Red flashing
Connection timeout
Off
No power to device
Green
Device operational
Green flashing
Data size larger than configured
Red
Unrecoverable fault
Red flashing
Minor fault
-
-
-
-
Off
Power off
Green, flashing
Initializing and not running
Green
Running
Red
Stopped or subnet error, or timeout
Off
Power off
Red/green
Invalid or missing configuration
alternating
Green
Initializing
Green flashing
Running
Red flashing
If the device status LED is flashing in a
sequence starting with one or more red
flashes, note the sequence pattern and
contact GE Multilin
8
7
6
5
4
3
2
1
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE