SYSTEM SETUP
5.5.7.7 Modification of SYNC word in CFG-2 for TR 90-5 data sets
In the CFG-2 file, all relevant information about the data being streamed is included. However, this file does not include the
fact that it describes a 90-5 dataset or the number of Application Service Data Units (datasets).  In order to communicate
this information via the CFG-2 file for a given aggregator, when the aggregator is set to 90-5, the version number of the
CFG-2 file (found in bits 0-3 of the frame SYNC word, which is set presently to 2) is set as follows:
Value (decimal)
 11
12
 13
 14
5.5.7.8 Settings
The PMU settings are organized as follows.
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1(2)
 PHASOR MEASUREMENT
 UNIT 1
5
5.5.7.9 Basic configuration
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  BASIC CONFIGURATION  PMU 1(2)
 PMU 1 BASIC
 CONFIGURATION
5-140
Number of ASDUs
 1
2
3
 4
 PMU 1 BASIC
 CONFIGURATION
 PMU 1
 CALIBRATION
 PMU 1
 TRIGGERING
 PMU 1
 RECORDING
PMU 1
FUNCTION: Disabled
PMU 1 IDCODE:
1
PMU 1 STN:
GE-UR-PMU
PMU 1 SIGNAL SOURCE:
SRC 1
PMU 1 CLASS:
CLASS M
PMU 1 FORMAT:
Integer
PMU 1 STYLE:
Polar
PMU 1 RATE:
10
PMU 1 f & df/dt
FILTER: None
PMU 1 PHS-1:
Off
See below
See page 5-144
See page 5-145
See page 5-151
Range:
Enabled, Disabled
Range:
1 to 65534 in steps of 1
Range:
32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
Range:
available signal sources
Range:
None, CLASS M, CLASS P
Range:
Integer, Floating-point
Range:
Polar, Rectangular
Range: 1, 2, 4, 5, 10, 12, 15,20, 25, 30,50, 60, 100, 120
/sec
Range: None, 10Hz/s <10Hz, 10Hz/s <20Hz, 20Hz/s
<10Hz, 20Hz/s <20Hz
Range:
available synchrophasor values
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS