Digital Counters; Selector Switches; Flex States - GE L90 Instruction Manual

Line differential relay ur series
Hide thumbs Also See for L90:
Table of Contents

Advertisement

6 ACTUAL VALUES
the transmitting direction is more than the delay in the receiving direction. A displayed value of "0.0" indicates that
either asymmetry is not present or can not be estimated due to failure with local/remote GPS clock source.
VALIDITY OF CHANNEL CONFIGURATION: The current state of the communications channel identification check,
and hence validity, is displayed here. If a remote relay ID number does not match the programmed number at the local
relay, the "FAIL" value is displayed. The "n/a" value appears if the Local relay ID is set to a default value of "0" or if the
87L element is disabled. Refer to
PFLL STATUS: This value represents the status of the Phase & Frequency Locked Loop Filter which uses timing infor-
mation from local & remote terminals to synchronize the clocks of all terminals. If
terminals are synchronized and 87L protection is enabled. If it is "FAIL", the clocks of all terminals are not synchronized
and 87L protection is disabled. If "n/a", then PFLL is disabled.
At startup, the clocks of all terminals are not synchronized and the PFLL status displayed is FAIL. It takes
up to 8 seconds after startup for the value displayed to change from FAIL to OK.
NOTE
!
PATH: ACTUAL VALUES

DIGITAL COUNTERS

# DIGITAL COUNTERS
# Counter 1
MESSAGE
MESSAGE
MESSAGE
The present status of the 8 digital counters is shown here. The status of each counter, with the user-defined counter name,
includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date/time stamp
for the frozen count. The
Counter n MICROS
!
PATH: ACTUAL VALUES
STATUS

# SELECTOR SWITCHES

#
MESSAGE
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
!
PATH: ACTUAL VALUES
STATUS

# FLEX STATES

#
MESSAGE
There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit.
GE Multilin
!"
SETTINGS
SYSTEM SETUP
!"
DIGITAL COUNTERS
Counter 1
ACCUM:
0
Counter 1
FROZEN:
0
Counter 1
FROZEN:
YYYY/MM/DD HH:MM:SS
Counter 1
MICROS:
0
value refers to the microsecond portion of the time stamp.
!"
SELECTOR SWITCHES
SELECTOR SWITCH 1
POSITION: 0/7
SELECTOR SWITCH 2
POSITION: 0/7
!"
FLEX STATES
PARAM
1: Off
Off
PARAM 256: Off
Off
L90 Line Differential Relay
!"
section for more information
L90 POWER SYSTEM
PFLL STATUS
6.2.10 DIGITAL COUNTERS
!
DIGITAL COUNTERS Counter 1(8)
6.2.11 SELECTOR SWITCHES
Range: Current Position / 7
Range: Current Position / 7
Range: Off, On
Range: Off, On
6.2 STATUS
is "OK", the clocks of all
6
6.2.12 FLEX STATES
6-7

Advertisement

Table of Contents
loading

Table of Contents