Advertisement

5 SETTINGS
The Modbus User Map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
line (this value must be converted from hex to decimal format). The corresponding value is dis-
ADDRESS
played in the
line. A value of "0" in subsequent register
VALUE
lines incremented by "1". An address value of "0" in the initial register means "none" and values of "0" will be dis-
ADDRESS
played for all registers. Different
These settings can also be used with the DNP protocol. See the DNP Analog Input Points section in Appen-
dix E for details.
NOTE
!
PATH: SETTINGS
PRODUCT SETUP
# REAL TIME
# CLOCK
MESSAGE
If the L90 Channel Asymmetry function is enabled, the IRIG-B input must be connected to the GPS receiver
and the proper receiver signal type assigned.
NOTE
The date and time for the relay clock can be synchronized to other relays using an IRIG-B signal. It has the same accuracy
as an electronic watch, approximately ±1 minute per month. An IRIG-B signal may be connected to the relay to synchronize
the clock to a known time base and to other relays. If an IRIG-B signal is used, only the current year needs to be entered.
See also the
!"
COMMANDS
The
REAL TIME CLOCK EVENTS
!
PATH: SETTINGS
PRODUCT SETUP
# FAULT REPORT 1
#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The L90 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as
the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
Fault report number
GE Multilin
values can be entered as required in any of the register positions.
ADDRESS
!"

REAL TIME CLOCK

IRIG-B SIGNAL TYPE:
None
REAL TIME CLOCK
EVENTS: Disabled
menu for manually setting the relay clock.
SET DATE AND TIME
setting allows changes to the date and/or time to be captured in the event record.
!"
!

FAULT REPORTS

FAULT REPORT 1
FAULT REPORT 1
SOURCE: SRC 1
FAULT REPORT 1 TRIG:
Off
FAULT REPORT 1 Z1
MAG: 3.00 Ω
FAULT REPORT 1 Z1
ANGLE: 75°
FAULT REPORT 1 Z0
MAG: 9.00 Ω
FAULT REPORT 1 Z0
ANGLE: 75°
FAULT REPORT 1 LINE
LENGTH UNITS: km
FAULT REP 1 LENGTH
(km
): 100.0
L90 Line Differential Relay
lines automatically returns values for the previous
ADDRESS
Range: None, DC Shift, Amplitude Modulated
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: FlexLogic™ operand
Range: 0.01 to 250.00
Range: 25 to 90° in steps of 1
Range: 0.01 to 650.00
Range: 25 to 90° in steps of 1
Range: km, miles
Range: 0.0 to 2000.0 in steps of 0.1
5.2 PRODUCT SETUP
5.2.6 REAL TIME CLOCK
5.2.7 FAULT REPORTS
in steps of 0.01
in steps of 0.01
5-19
5