CHAPTER 6: COMMUNICATIONS
Remote outputs: DNA bit pairs
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Name
Range: up to 12 alphanumeric characters
Default: RemDPS Ip 1
This setting specifies an exact identification (ID) for each remote double-point status
input.
Device
Range: Remote Device 1 through Remote Device 32
Default: Remote Device 1
This setting selects a remote device ID to indicate the origin of a GOOSE message.
Item
Range: None, Dataset Item 1 through Dataset Item 64
Default: None
This setting specifies the required bits of the GOOSE message.
Default State
Range: Intermediate, Off, On, Bad, Latest
Default: Latest
This setting selects the default value for the offline remote double-point status input.
Events
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the logging of remote double-point status input events
in the sequence of events recorder.
Remote outputs (1 to 32) are FlexLogic operands inserted into GSSE/GOOSE messages that
are transmitted to remote devices on a LAN. Each digital point in the message must be
programmed to carry the state of a specific FlexLogic operand. This operand setting
represents a specific DNA function (as shown in the following table) to be transmitted.
Table 7: IEC 61850 DNA Assignments
DNA
IEC 61850 definition
1
Test
2
ConfRev
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Inputs/Outputs > Remote Outputs DNA menu to open the remote inputs configuration
window.
IEC 61850 COMMUNICATIONS
FlexLogic operand
IEC 61850 TEST MODE
IEC 61850 CONF REV
125