GE D90 Plus Instruction Manual page 133

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 6: COMMUNICATIONS
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
defined by the user selection of the FlexLogic operand whose state is represented in the
GSSE/GOOSE message. A user must program a DNA point from the appropriate FlexLogic
operand.
Table 6: IEC 61850 DNA Assignments
DNA
IEC 61850 definition
1
Test
2
ConfRev
Remote input 1 must be programmed to replicate the logic state of a specific signal from a
specific remote device for local use. This programming is performed via the three settings
indicated outlined as follows.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Inputs/Outputs > Remote Inputs menu to open the remote inputs configuration window.
Figure 99: Remote inputs configuration settings
The following settings are available for each of the 32 remote inputs.
Name
Range: up to 12 alphanumeric characters
Default: Remo Ip 1
This setting allows the user to assign descriptive text to the remote input.
Device
Range: 1 to 32 inclusive
Default: Remote Device 1
This setting selects the number (1 to 32) of the remote device that originates the required
signal, as previously assigned to the remote device via the
Bit Pair
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32, Config Item 1 to Config Item 64
Default: None
This setting selects the specific bits of the GSSE/GOOSE message required.
Default State
Range: On, Off, Latest/On, Latest/Off
Default: Off
This setting selects the logic state for this point if the local relay has just completed
startup or the remote device sending the point is declared to be non-communicating.
The following choices are available:
On — Defaults the input to logic 1
IEC 61850 COMMUNICATIONS
FlexLogic operand
IEC 61850 TEST MODE
IEC 61850 CONF REV
Remote Device 1 ID
setting.
123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents