Advertisement

5 SETTINGS
The relay contains a real time clock (RTC) to create timestamps for communications protocols as well as for historical data,
such as event records and oscillography. When the relay restarts, the RTC initializes from an onboard battery-backed
clock, which has the same accuracy as an electronic watch, approximately ±1 minute per month (~23 ppm). Once the RTC
is synchronized with the Precision Time Protocol (PTP), IRIG-B, or SNTP, its accuracy approaches that of the synchroniz-
ing time delivered to the relay.
The
SYNCHRONIZING SOURCE
able external time sources synchronizes the RTC and the synchrophasor clock. A setting of None causes the RTC and the
synchrophasor clock to free-run. A setting of PP/IRIGB/PTP/SNTP, IRIGB/PP/PTP/SNTP, or PP/PTP/IRIGB/SNTP causes
the relay to track the first source named that is enabled and operational, or free-run if none of these are available. Here, PP
means a time source that is strictly compliant with PP, PTP means a time source that is not strictly compliant with PP. When
a time source fails or recovers, the relay automatically transfers synchronization as required by this setting.
See the
COMMANDS
SET DATE AND TIME
The
REAL TIME CLOCK EVENTS
records the RTC time before the adjustment.
To enable IRIG-B synchronization, the input
synchronization can be disabled by making this setting None.
To configure and enable PTP and/or SNTP, or to set local time parameters (for example time zone, daylight savings), use
the following sections.
b) PRECISION TIME PROTOCOL (1588)
PATH: SETTINGS
PRODUCT SETUP
 PRECISION TIME
 PROTOCOL (1588)
MESSAGE
MESSAGE
MESSAGE
PATH: SETTINGS
PRODUCT SETUP
MESSAGE
MESSAGE
MESSAGE
The UR supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified
in IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet net-
work that implements PP.
The relay can be configured to operate on some PTP networks that are not strictly PP. Time accuracy can be less than
specified for a PP network. Tolerated deviations from strict PP include 1) missing declaration of PP compliance in the mes-
sages, 2) connection to a network device that does not support the PTP peer delay mechanism, 3) jitter substantially
greater than 1 µs in received event messages, and 4) certain non-compliant announce and sync message update rates.
The relay implements PTP according to IEEE Std 1588 2008 and the equivalent IEC 61588:2009(E), sometimes
referred to as version 2 PTP. It does not support the previous version of the standard (version 1).
NOTE
GE Multilin
setting configures the priority sequence that the relay uses to determine which of the avail-
menu section of this manual to manually set the RTC.
setting allows changes to the date and/or time to be captured in the event record. The event
IRIG-B SIGNAL TYPE


REAL TIME CLOCK
STRICT POWER PROFILE:
Disabled
PTP DOMAIN NUMBER
0
PTP VLAN PRIORITY
4
PTP VLAN ID
0
 PTP PORT 1


REAL TIME CLOCK
PORT 1 PTP FUNCTION:
Disabled
PORT 1 PATH DELAY
ADDER:
00000 ns
PORT 1 PATH DELAY
ASYMMETRY:
0000 ns
B30 Bus Differential System
must be set to DC Shift or Amplitude Modulated. IRIG-B
PRECISION TIME PROTOCOL (1588)
Range: Enabled, Disabled
Range: 0 to 255
Range: 0 to 7
Range: 0 to 4095
PRECISION TIME PROTOCOL (1588)
Range: Enabled, Disabled
Range: 0 to 60 000 ns in steps of 1
Range: –1 000 to +1 000 ns in steps of 1
5.2 PRODUCT SETUP

PTP PORT 1(3)
5-59