5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
 ANALOG INPUT / MME
 POINTS
MESSAGE
MESSAGE
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the B30 is restarted.
NOTE
k) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 IEC 61850 PROTOCOL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The B30 Bus Differential System is provided with optional IEC 61850 communications capability. This fea-
ture is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for
additional details.
GE Multilin


COMMUNICATIONS
DNP / IEC104 POINT LISTS
Point:
0
Off
Point:
1
Off
Point:
255
Off


COMMUNICATIONS
IEC 61850 PROTOCOL
 GSSE / GOOSE
 CONFIGURATION
 SERVER
 CONFIGURATION
 IEC 61850 LOGICAL
 NODE NAME PREFIXES
 MMXU DEADBANDS
 GGIO1 STATUS
 CONFIGURATION
 GGIO2 CONTROL
 CONFIGURATION
 GGIO4 ANALOG
 CONFIGURATION
 GGIO5 UINTEGER
 CONFIGURATION
 REPORT CONTROL
 CONFIGURATION
 XCBR
 CONFIGURATION
 XSWI
 CONFIGURATION
B30 Bus Differential System
5.2 PRODUCT SETUP

ANALOG INPUT / MME POINTS
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
5
5-39