GASSONIC GASSSONIC MM0100 Installation And User Manual

Ultrasonic gas leak detectors

Advertisement

InstallatIon and User GUIde for
GasssonIC MM0100 / eH6028
UltrasonIC Gas leak deteCtors

Advertisement

Table of Contents
loading

Summary of Contents for GASSONIC GASSSONIC MM0100

  • Page 1 InstallatIon and User GUIde for GasssonIC MM0100 / eH6028 UltrasonIC Gas leak deteCtors...
  • Page 3 InstallatIon and User GUIde for GasssonIC MM0100 / eH6028 UltrasonIC Gas leak deteCtors From serial number: 056-001 Gassonic MM0100 / EH6028...
  • Page 4: Table Of Contents

    1. Introduction ........................... 4 2. Description of Gassonic MM0100 / EH6028 ................4 3. Installing the Detector 3.1. Area Monitored by Gassonic MM0100 / EH6028 ............4 3.2. Environmental Conditions ................... 5 3.3. Mounting the Detector ....................5 3.4. Cable Connections ....................6-7 4.
  • Page 5 Only original Gassonic screws with isolators should be used to tighten the lid. aBoUt tHIs InstallatIon GUIde This installation guide describes how to install the Gassonic MM0100 / EH6028 Gas Leak Detector and tells you how to adjust it to the local conditions.
  • Page 6: Introduction

    The Gassonic MM0100 detector has an adjustable alarm trigger level setting (7 levels, from 44 to 104dB in 10dB steps) and an internal adjustable alarm delay from 0 – 480 seconds. If the internal alarm delay is set to zero, an alarm delay of at least 15 seconds should be introduced at the control system.
  • Page 7: Environmental Conditions

    3.3. MoUntInG tHe deteCtor Two M8 stainless steel bolts attached to the detector’s lid are used to fix the Gassonic MM0100 / EH6028 in its operating position. The detectors can be mounted to a free-standing pole or wall, using the mountain bracket UA1352.
  • Page 8: Cable Connections

    3.4. CaBle ConneCtIons MTL5011 MTL5025 Installation and User Guide for Ultrasonic Gas Leak Detectors Page 6...
  • Page 9 Blue: 13 – 28 VDC Black: GND Pair 2 Trip Outputs: Blue & Black: Alarm Relay Output. Collective screen and drain wire: Is Earth Armour: Earth The braided cable must be fastened at least every 0.5m. Gassonic MM0100 / EH6028 Page 7...
  • Page 10: Power Requirements

    Pi = 0.75 W 5. adjUstMents 5.1. Adjustable Alarm Level settings The Gassonic MM0100 / EH6028 is equipped with an adjustable Alarm Trigger Level. This should be adjusted to suit the local conditions. The alarm has ten level settings: GAssOnIC MM0100...
  • Page 11: Alarm Delay & Cut-On Frequency Settings

    Alarm Delay: 0 seconds Cut-on frequency: 25 kHz 5.2.2 GAssOnIC M0100 The Gassonic MM0100 is equipped with an adjustable Alarm Level, Alarm Delay and a Cut-on Frequency. These should be adjusted to suit the local conditions. 5.2.2.1. Alarm Delay The Gassonic MM0100 is fitted with an Alarm Delay function. This can prevent short duration ultrasound noise events, which exceed the alarm level, from triggering the alarm.
  • Page 12: Operating The Equipment

    Adjusting the DIP switches: 1. Unscrew the four screws in the top of the Gassonic MM0100, and remove the lid. 2. Unscrew the six screws on the metalplate located under the lid and remove the plate. The dipswitches, illustrated below, are now visible.
  • Page 13 GasssonIC MM0100 / eH60288 From serial number: 056-001 GAssOnIC A/s Energivej 42 A DK-2750 Ballerup Denmark Tel +45 44 700 910 Fax +45 44 700 911 mail@gassonic.com www.gassonic.com BB 6016-03 CAPITOL COPENHAGEN +45 4580 0831...