Filters; Duct System; Venting - Lennox G50DF(X)?24A?045 Installation Instructions Manual

G50df(x) series
Table of Contents

Advertisement

WARNING
Improper installation of the furnace can result in per-
sonal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or the living space. Use screws and joint tape to seal
the return air system to the furnace.
In platform installations with bottom return air, the
furnace should be sealed airtight to the return air ple-
num. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Al-
low absolutely no sagging, cracks, gaps, etc.
The return and supply air duct systems must never
be connected to or from other heating devices such
as a fireplace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or proper-
ty damage could result.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal inju-
ry or death.

Filters

This unit is not equipped with a filter or rack. A field−pro-
vided high−velocity filter is required for the unit to operate
properly. Table 3 lists the recommended minimum filter
sizes.
A filter must be in place any time the unit is operating.
TABLE 3
Furnace
Cabinet Size
14−1/2"
17−1/2"
21"
24−1/2"

Duct System

Use industry-approved standards to size and install the
supply and return air duct system. This will result in a quiet
and low-static system that has uniform air distribution.
Ensure that you have made a seal between the supply air
plenum and the furnace and between the furnace and the
return air plenum.
NOTE − Do not operate the furnace with an external static
pressure that exceeds 0.5 inches w.c. Higher external stat-
ic pressures may cause erratic limit operation.
Return Air Filter Size (inches)
14 X 25 X 1 (1)
16 X 25 X 1 (1)
20 X 25 X 1 (1)
24 X 25 X 1 (1)
Return Air Plenum
NOTE − Return air must not be drawn from a room
where this furnace, or any other gas−fueled ap-
pliance (i.e., water heater), or carbon monoxide−
producing device (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pres-
sure is created in the room. If a gas appliance is operating
in a room with negative pressure, the flue products can
be pulled back down the vent pipe and into the room. This
reverse flow of the flue gas may result in incomplete com-
bustion and the formation of carbon monoxide gas. This
toxic gas might then be distributed throughout the house
by the furnace duct system.

Venting

A 4−inch diameter flue transition is factory-installed on all
models. Modifying or removing the flue transition will
cause the unit to operate unsafely and will void the unit
certification. The vent connector does not require insula-
tion.
The G50DF(X) series units are classified as fan−assisted
Category I furnaces when vertically vented according to
the latest edition of National Fuel Gas Code (ANSI
Z223.1/NFPA 54) in the USA and the current standards of
CSA B149 Natural Gas and Propane Installation Codes in
Canada. A fan−assisted Category I furnace is an appliance
equipped with an integral mechanical means to either draw
or force combustion products through the combustion
chamber and/or heat exchanger.
NOTE − Use these instructions as a guide. They do not su-
persede local codes. This furnace must be vented accord-
ing to all local codes, these installation instructions, and the
provided venting tables (5 through 10) in these instructions.
The venting tables in this manual were extracted from the
National Fuel Gas Code (ANSI Z223.1/NFPA 54) and are
provided as a guide for proper vent installation. Proper ap-
plication, termination, construction and location of vents
must conform to local codes having jurisdiction. In the ab-
sence of local codes, the NFGC serves as the defining doc-
ument.
Refer to the tables and the venting information contained in
these instructions to properly size and install the venting
system.
IMPORTANT
Once the venting system is installed, attach the Dis-
connected Vent" warning sticker to a visible area of
the plenum near the vent pipe. The warning sticker
is provided in the bag assembly.