Is something blocking the air
outlet or inlet of either the
indoor or outdoor units?
Are refrigerant piping length
and additional refrigerant
charge noted down?
Also review the "SAFETY PRECAUTIONS".
b. Items to be checked at time of delivery
Items to be checked
Did you explain about operations while showing the
operation manual to your customer?
Did you hand the operation manual and warranty over to
your customer?
Did you explain about the way of maintaining and cleaning
local procurements (air filter, grille (both air outlet and suc-
tion grille), etc.) to your customer?
Did you hand manuals of local procurements (in case
equipped) over to your customer?
c. Points for explanation about operations
The items with
WARNING and
the operation manual are the items pertaining to
possibilities for bodily injury and material damage in
addition to the general usage of the product. Accordingly, it
is necessary that you make a full explanation about the
described contents and also ask your customers to read the
operation manual.
3.

SELECTING INSTALLATION SITE

CAUTION
• When moving the unit during or after unpacking, make sure
to lift it by holding its lifting lugs. Do not exert any pressure on
other parts, especially the refrigerant piping, drain piping and
flange parts.
• If you think the humidity inside the ceiling might exceed
30°C and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that
it is no thicker than 10mm and fits inside the ceiling open-
ing.
(1) Select an installation site where the following conditions
are fulfilled and that meets with your customer's approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor unit
weight.
• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service
can be ensured. (Refer to Fig. 1)
• Where piping between indoor and outdoor units is possi-
ble within the allowable limit. (Refer to the installation
manual for the outdoor unit.)
• The equipment is not intended for use in a potentially
explosive atmosphere.
English
It may result in insufficient
cooling.
The refrigerant charge in the
system is not clear.
CAUTION marks in
*300
or
more
Maintenance
space
Check
• *H1 dimension means the minimum height of the unit.
• Select the *H1, *H2 dimension such that a downward
slope of at least 1/100 is ensured as indicated in
"7. DRAIN PIPING WORK".
• The maintenance space marked with "*" is required when
the installation box for adaptor PC board (KRP1BA101)
sold separately is used.
[ PRECAUTION ]
• Install the indoor and outdoor units, power supply wiring
and connecting wires at least 1 m away from televisions or
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 m may not
be sufficient enough to eliminate the noise.)
• If installing the wireless kit in a room with electronic fluo-
rescent lighting (inverter or rapid start type), the remote
controller's transmission distance may be shortened.
Indoor units should be installed as far away from fluores-
cent lighting as possible.
(2) Use suspension bolts for installation. Check whether
the ceiling is strong enough to support the weight of
the unit or not. If there is a risk, reinforce the ceiling
before installing the unit.
• To avoid contact with the fan, one of the following precaution
actions must be taken:
- Install the unit as high as possible at a minimum bottom
height of 2.7 m.
- Install the unit as high as possible at a minimum bottom
height of 2.5 m in case the fan is externally screened by
parts which can be removed without the aid of tools (e.g.
false sealing, grill ... ).
- Install the unit with ducting and grill which can only be
removed with the aid of tooling. It shall be installed so that
it gives adequate protection against touching the fan. If a
maintenance panel exists in the ducting, it shall only be
possible to remove the panel by the aid of tooling to avoid
contact with the fan. The protection shall be according to
relevant European and local legislation. There are no
restrictions concerning the installation height.
300 or
more
Control box
Maintenance
space
*H2=20 or more
Ceiling
Fig. 1
Floor surface
(length : mm)
3