SAFETY PRECAUTION Cautions for devices that use R407C refrigerant. · Do not use the existing refrigerant piping. -The old refrigerant and lubricating oil in the existing piping contains a large amount of chlorine which may cause the lubricating oil of the new unit to deteriorate. ·...
Page 4
[1] Service tools Use the below service tools as exclusive tools for R407C refrigerant. No. Tool name Specifications 1 Gauge manifold ·Only for R407C. ·Use the existing fitting SPECIFICATIONS. (UNF7/16) ·Use high-tension side pressure of 35kgf/cm or over. 2 Charge hose ·Only for R407C.
PART NAMES AND FUNCTIONS Indoor (Main) Unit Filter Removes dust and pollutants from intake air Horizontal Air Outlet Sets airflow to horizontal automatically during cooling or dehumidifying. Grille Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.
Display In this display example on the bot- CENTRALLY CLOCK display tom left, a condition where all dis- CONTROLLED display play lamps light is shown for expla- The current time , start time and stop time can be displayed in ten second nation purposes although this differs This indicates when the unit is con- intervals by pressing the time setting...
3-2. Electrical parts specifications Model Symbol PLFY-P80VAM.UK PLFY-P100VAM.UK PLFY-P125VAM.UK Parts name Room temperature TH21 Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k" thermistor Liquid pipe thermistor TH22 Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k" Gas pipe thermistor TH23 Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"...
Page 9
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set the switches (SWA, SWB) on the indoor board to the appropriate setting. Correspondence of ceiling heights to numbers of air outlets. PLFY-P80VAM.UK Standard High ceiling...
Page 10
4-4. Fixing of horizontal vane The horizontal vane of each air outlet can be fixed according to the environment, in which it is installed. Setting procedure 1) Turn off the main power supply (Turn off the breaker). 2) Disconnect the vane motor connector of the direction of the arrow by pressing the unlocking button as shown in the figure below.
Page 11
4-5. Fresh air intake amount & static pressure characteristics (1) PLFY-P80VAM.UK Multifunction casement + Standard filter Multifunction casement + High efficiency filter Static pressure [Pa] Static pressure [Pa] Air flow [m /min] Air flow [m /min] 2 intakes 2 intakes...
WIRING DIAGRAM PLFY-P80VAM.UK PLFY-P100VAM.UK PLFY-P125VAM.UK [LEGEND] SYMBOL NAME SYMBOL NAME SYMBOL NAME INDOOR POWER BOARD LINEAR EXPANSION VALVE CAPACITOR(FAN MOTOR) INDOOR CONTROLLER BOARD FAN MOTOR(WITH INNER THERMO) CIRCUIT BOARD CN25 CONNECTOR HUMIDIFIER VANE MOTOR SWITCH MODE SELECTION VOLTAGE SELECTION CN32...
TROUBLE SHOOTING 8-1. How to check the parts PLFY-P•VAM.UK Parts name Check points Room temperature Disconnect the connector then measure the resistance using a tester. thermistor (TH21) (Surrounding temperature 10:~30:) Liquid pipe thermistor (TH22) Normal Abnormal (Refer to the thermistor) Gas pipe thermistor 4.3k"~9.6k"...
<Thermistor Characteristic graph> < Thermistor for lower temperature > Room temperature thermistor(TH21) Thermistor for Liquid pipe thermistor(TH22) lower temperature Gas pipe temperature thermistor(TH23) Thermistor R =15k' ± 3% Fixed number of B=3480k' ± 2% Rt=15exp { 3480( 273+t 15k' 9.6k' 6.3k' -20 -10 0 10 20 30 40 50 5.2k'...
Page 17
<Output pulse signal and the valve operation> Output Output (Phase) Closing a valve : 1 Opening a valve : 4 The output pulse shifts in above order. 1. When linear expansion valve operation stops, all output phase become OFF. 2. At phase interruption or when phase does not shift in order, motor does not rotate smoothly and motor will lock and vibrate.
8-2. FUNCTION OF DIP SWITCH Operation by switch Switch Pole Function Remarks Thermistor <intake temperature Built-in remote controller Indoor unit Address board detection> position Filter clogging detection Provided Not provided <At delivery> Filter cleaning 2,500hr 100hr Fresh air intake Effective Not effective 1 2 3 4 5 6 7 8 9 10 Remote indication switching...
Page 19
Switch Pole Operation by switch Remarks Address board Ceiling height can be changed depends on SWB setting. (High ceiling2) <At delivery> Ceiling PLFY P80VAM.UK (High ceiling1) height selector (Standard) High High Standard ceiling1 ceiling2 4 direction 2.7m 3.0m 3.5m 3 direction 3.0m 3.3m 3.5m...
DISASSEMBLY PROCEDURE PLFY-P80VAM.UK Be careful on removing heavy parts. OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS 1. Removing the air intake grille Figure 1 (1) Slide the knob of air intake grille toward the arrow 1 to open the air intake grille.
Page 21
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS 5. Remove the fan motor Photo 4 Fan motor (1) Remove the fan guard.(See photo 1) (2) Remove the bell mouth.(See photo 2) (3) Remove the electrical box.(See photo 3) (4) Remove the turbo fan nut, washer and radiation cap(P100, P125). (5) Pull out the turbo fan.
Page 22
OPERATING PROCEDURE PHOTOS & ILLUSTRATIONS 9. Removing the drain pump and drain sensor Photo 8 (1) Remove the panel. (See photo 6) (2) Remove the fan guard. (See photo 1) (3) Remove the bell mouth. (See photo 2) (4) Remove the electrical box. (See photo 3) (5) Remove the drain pan.
PARTS LIST PANEL PARTS PLFY-P80VAM.UK PLFY-P100VAM.UK PLFY-P125VAM.UK Part numbers that is circled is not shown in the figure. Q'ty/set Price Wiring Recom- PLFY- Remarks Diagram mended Part No. Part Name Specification P80 / P100 / P125 (Drawing No.) Unit Amount...
Page 24
FUNCTIONAL PARTS PLFY-P80VAM.UK PLFY-P100VAM.UK PLFY-P125VAM.UK Q'ty/set Price Wiring Recom- Remarks Diagram mended Part No. Part Name Specification PLFY- · VAM.UK (Drawing No.) Unit Amount Symbol Q'ty P80 P100/P125 BASE DWG S70 003 687 DRUM 1 ASSY S70 005 688 DRUM 1ASSY...
Page 25
FUNCTIONAL PARTS PLFY-P80VAM.UK PLFY-P100VAM.UK PLFY-P125VAM.UK Q'ty/set Price Wiring Recom- Remarks Diagram mended Part No. Part Name Specification PLFY- · VAM.UK (Drawing No.) Unit Amount Symbol Q'ty P80 P100 P125 S70 E02 529 DRAIN PAN S70 E00 529 DRAIN PAN S70 A41 523 DRAIN SOCKET <PART OF DRAIN PAN ASSY>...
OPTIONAL PARTS 11-1. Multi function casement Part No. PAC-SG03TM-E 11-2. Air outlet shutter plate (20sets, 2pcs / 1set) Part No. PAC-SG06SP-E 11-3. High efficiency filter (PAC-SG03TM-E is required in using this optional part.) Part No. PAC-SG01KF...
Page 28
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO cCopyright 2000 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. New publication, effective Aug. 2000 Issued in Aug. 2000. No. OC213 225 Specifications subject to change without notice Printed in Japan...