Belimo T24-V42 Operation And Setting

Belimo T24-V42 Operation And Setting

Room control module

Advertisement

Quick Links

Controller operation

The T24-V42(-V02)LON room control module offers the advantages of network control via the high performance LON transceiver.
This controller features screw terminal blocks, analogue input, digital input, analogue output, three 24Vac digital outputs, MP-Bus
interface for connection to the Belimo VAV Compact and optional T24-MP room unit or TG-R10000 room sensor. Suitable for new
or existing VAV system installations.

Functions of T24-V42(-V02)LON and wiring diagram

Analogue
AC 24V
External
output (AO)
Power
sensor (AI)
2-10Vdc
supply
NTC 10k
1
2
Digital input
Electrical heaters,
(DI)
parallel/series fan
(3 x DO)
System
reset
Input & output assignment
Inputs
- AI
External temp. sensor TG-R10000 *
- DI
Remote setpoint shift, e.g. Occupancy sensor *
Open - Normal mode, Close - Economy mode

Functions of T24-MP and wiring diagram

LCD display
C
ON
MODE

Functions of TG-R10000 and wiring diagram

Operation and setting
MP-Bus (MP1~3)
LonWorks
3
MP
®
BUS
LonWorks
service pin
*Power
supply
Modulating
M
reheat valve
T24-MP
External
1 2 5
sensor
NTC 10k
(TG-R10000)
AI
Com
AO
Com
DI
Com
Occupancy
sensor
3-point
reheat
valve
xxx
Not available for T24-V02LON
Outputs
-
AO
Modulating reheat control
-
DO1
Heating output I
-
DO2
Heating output II
- DO3
Parallel or series fan output 24Vac ON/OFF
* Optional
T24-V42(-V02)LON+T24-MP
24Vac
~
1A fuse
1 2 3 5
VAV Compact
24V
LON
Com
MP1
MP2
MP3
ac
A
T24-V42(-V02)LON
DO1
Com
DO2
Com
DO3
Com
24Vac
*Relay supplied
by others
Caution: live voltage
Heater
Heater
Parallel
1
2
or
series fan
System
reset
LonWorks
service pin
2...10Vdc
24Vac ON/OFF
24Vac ON/OFF
Please note: A standard RJ12 6/4 (1:1)
cable can be plugged onto the RJ12 and
connected to a Belimo MP-Bus level
converter (e.g. ZTH-USB-MP) for the
Belimo PC-Tool.
1 2 3 5
VAV Compact
LonWorks®
LON
B
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the T24-V42 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Belimo T24-V42

  • Page 1 This controller features screw terminal blocks, analogue input, digital input, analogue output, three 24Vac digital outputs, MP-Bus interface for connection to the Belimo VAV Compact and optional T24-MP room unit or TG-R10000 room sensor. Suitable for new or existing VAV system installations.
  • Page 2 “ ”+ “ MODE ” for 5 seconds Functional keys Mounting Notes The T24-V42(-V02)LON control module can be mounted as follows: Observe all local installation and mounting regulations. DIN rail (EN 50 022-35 x 7.5) at least 120 mm long...
  • Page 3 T24-V42(-V02)LON+T24-MP Operation and setting Controller operation menu Press “ MODE ” Temperature display Menu structure Standby Normal 2 sec. Temperature setpoint mode mode Press Time Press Press “ MODE ” “ MODE ” 5 sec. “ ” & “ MODE ”...
  • Page 4 T24-V42(-V02)LON+T24-MP Operation and setting MP-Bus - VAV Compact addresses The MP-Bus is the Belimo master/salve bus. Up to 8 salves can be conne- T24-V42(-V02)LON, MP-Bus requirement cted to an MP-master devices. Each MP salve must be assigned a unique MP address between MP1 to MP8 before it can be operated on the MP-Bus.

Table of Contents