USER MANUAL

Line Interactive UPS
1000VA/1500VA/2000VA/3000VA
Uninterruptible Power Supply System
Copyright © Digital Data Communications GmbH, Germany. All Rights Reserved.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1000VA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Equip 1000VA

  • Page 1: User Manual

    USER MANUAL Line Interactive UPS 1000VA/1500VA/2000VA/3000VA Uninterruptible Power Supply System Copyright © Digital Data Communications GmbH, Germany. All Rights Reserved.
  • Page 2: Save These Instructions

    1000VA/1500VA/2000VA/3000VA series that should be followed during installation and maintenance of the UPS and batteries. Please read all safety and operating instructions before operating the UPS. Adhere to all warnings on the unit and in this manual.
  • Page 3: Table Of Contents

    CONTENTS 1. Introduction ············································································· 1 2. Safety Warning ········································································· 2 2.1 Description of Commonly Used Symbols ···································· 3 3. Installation ··············································································· 4 3.1 Inspection of Unit ·································································· 4 3.2 Unpacking the Cabinet ··························································· 4 3.3 UPS Setup ··········································································· 4 3.4 EBM Installation (Optional) ······················································ 8 3.5 UPS Initial Startup ·······························································...
  • Page 4: Introduction

    AC fail alarm and initiate the UPS self test sequence as well. The UPS case for 1000VA ~ 3000VA is made of metal. This series is powered from the AC mains and supply AC outputs via receptacles on the rear panel.
  • Page 5: Safety Warning

    2. Safety Warning DANGER: This UPS contains high voltages. All repairs and service should be performed by authorized service personnel only. There are no user serviceable parts inside the UPS. WARNING: n This UPS contains its own energy source (batteries).The UPS output may carry live voltage even when the UPS is not connected to an AC supply.
  • Page 6: Description Of Commonly Used Symbols

    and required precautions. Keep unauthorized personnel away from batteries. n Proper disposal of batteries is required. Refer to your local codes for disposal requirements. n Never dispose of batteries in a fire. Batteries may explode when exposed to flame. Following figure shows the basic internal circuit configuration of the UPS 2.1 Description of Commonly Used Symbols Some or all of the following Notations may be used in this manual and may appear in your application process.
  • Page 7: Installation

    3. Installation 3.1 Inspection of Unit Inspect the UPS upon receiving. If the UPS is apparently damaged during the shipment, please keep the box and packing material in original form for the carrier and notify the carrier and dealer immediately. 3.2 Unpacking the Cabinet To unpack the system: 1.
  • Page 8 Use the following procedure to install UPS in UPS stands. 1. Slide down the UPS vertically and put two UPS stands at the end of the tower. 2. Place down the UPS into two stands carefully.
  • Page 9 3. Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel. l Rack-mount setup The series can be installed in 19 inches racks. Both the UPS and external battery enclosure need 2U of valuable rack space.
  • Page 10 2. Assemble the rack rails with the rack-mounting. 3. Slide in the UPS into the rack rail and lock it in the rack enclosure.
  • Page 11: Ebm Installation (Optional)

    4. Tighten the screw, and the load can then be connected 3.4 EBM Installation (Optional) l Connecting the EBM in Tower form: 1. Slide down the UPS and EBM vertically and place two UPS stands with the extend part at the end of the tower. 2.
  • Page 12 3. Connect the Earth line from UPS (port A ) to EBM (port B) 4. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below. Users need to remove the small gate(C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
  • Page 13 l Connecting the EBM in a rack form 1. Using the same method as assembling UPS in a rack form, assemble EBM into the rack-mounting on the top or bottom of the UPS. 2. Connect the earth line from UPS (port A ) to EBM (port B )
  • Page 14 3. Take off the LCD box, and unscrew the internal screws. Unscrew 4. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below. Users need to remove the small gate(C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
  • Page 15 Connecting the Multiple EBMs 1000VA/1500VA/2000VA and 3000VA UPS include external battery port that allows users to connect multiple EBM in order to provide additional backup time. Follow the procedure to install multiple EBM as below. Connecting multiple EBMs in Tower form 1.
  • Page 16 Connecting the Multiple EBMs in rack form 1. Connect Earth line between UPS and the first EBM, and then connect Earth Line between the first EBM and the second EBM. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below.
  • Page 17: Ups Initial Startup

    Note: Three or more EBMs can be connected to the UPS in the same way as shown above. 3.5 UPS Initial Startup To start up the UPS: 1. Verify that the internal batteries are connected. If optional EBMs are installed, verify that the EBMs are connected to the UPS. 2.
  • Page 18: Operation

    4. Operation 4.1 Display Panel The UPS has a four-button graphical LCD with dual color backlight. Standard back-light is used to light up the display with black text and a blue background. When the UPS has a critical alarm, the backlight changes the background to red.
  • Page 19 The following table describes the functions of the LCD control buttons. Table2. Description of control button Control Switch Function Button --To turn on/off the UPS Press and hold the button more than 3 seconds. --To release the UPS from faulty mode ON/OFF Cut off input power and then press and hold the button...
  • Page 20 l LCD display functions: The following table describes the functions of the LCD display. Table3. Description of LCD display function Description Function Input frequency and Indicate the value of input frequency and voltage voltage Light on when the input power is at no loss. Input plug indicator Output frequency and Indicate the value of output frequency and...
  • Page 21 l UPS Status Display String Description: The following table shows the description of the LCD display string: Table4. UPS Status Display String LCD Display String Description UPS work at Standby mode STbY Input voltage is too low IPVL Input voltage is too high IPVH Input frequency is too low IPFL...
  • Page 22: Operating Mode

    [000]=Disable Green function [001]=Enable [000]=Disable Buzzer control [001]=Enable [000]=Turn off [001]=Turn Load segment 1 [000]=Turn off [001]=Turn Load segment 2 4.2 Operating Mode l Normal range mode: Under Input mode the UPS accepts AC input voltage range for +/-20%. l Generator mode: Under generator mode, the low frequency transfer point can go as low as 40Hz and as high as 80Hz before being transferred to battery mode.
  • Page 23: Configuring Ups For Ebm Numbers

    Note: This configuring can be operated when UPS is power on. 1K model has only one load segment, cannot configure. To configure the load segment through the display: 1. Enter settings mode: Press and hold the Enter button more than 3 seconds.
  • Page 24: Configuring Green Function

    6. Exit Settings mode: Press and hold the Enter button for 3 seconds or button for 0.5 second to exit setting mode. 4.5 Configuring Green Function Green Function is that when an insignificant amount of load is detected, the UPS will shut down output automatically on battery mode. The green function is disabled on default mode and user can configure Green Function through the display: 1.
  • Page 25: Communication Port

    5. Communication Port 5.1 RS-232 and USB Communication Ports To establish communication between the UPS and a computer, connect your computer to one of the UPS communication ports using an appropriate communication cable. When the communication cable is installed, power management software can exchange data with the UPS.
  • Page 26: Network Management Card (Optional)

    Warning: This circuit must be separated from hazardous voltage circuits by reinforced insulation. Caution: The EPO must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The EPO Switch must have a minimum rating of 24Vdc and 20mA and be a dedicated latching-type switch not tied into any other circuit.
  • Page 27: Ups Maintenance

    6. UPS Maintenance 6.1 UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For long battery life, keep the UPS at an ambient temperature of 25°C (77°F) 6.2 Storing the UPS and Batteries When the UPS is intended to store for a long period, recharge the battery...
  • Page 28: Replacing Ups Internal Batteries

    Do not dispose of battery in a fire. Batteries may explode when exposed to flame. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Do not open or mutilate the battery. Released toxic electrolyte is harmful to skin and eyes.
  • Page 29 4. Remove the right inner battery bracket. 5. Pull the battery pack out onto flat area. 6. Install new battery pack into UPS. 7. Screw up the battery bracket and reconnect the battery cable A and B 8. Re-install the front panel back to UPS.
  • Page 30: Testing New Batteries

    6.5 Testing New Batteries For a battery test, please check: The batteries must be fully charged. l The UPS must be in Normal mode with no active alarms. l Don’t take on/off the load. l To test batteries: 1. Connect the UPS to utility power for at least 48 hours to charge the batteries.
  • Page 31: Specification

    7. Specification 7.1 Specification Table7. Electrical Specification 1500 2000 3000 1000 Model 1500S 2000S 3000S Capacity Watt 900W 1350W 1800W 2700W Input voltage range 0-300VAC Input 50/60Hz ±5Hz for Normal Mode Frequency range 40-80Hz for Generator Mode Voltage 220/230/240VAC Voltage Regulation ±5% (Batt.
  • Page 32 Table8. Indicators and Audible alarm AC Mode NORM---normal mode Backup Mode Show “bATT” and sounding every 4 seconds Load/Battery Level LCD showing Indicator LCD show red screen and “ **** ” UPS Fault Overload LCD show red screen and “ OVLD ” LCD show red screen and “...
  • Page 33: Rear Panels

    SNMP Port AC Input RS232 / Dry-Contact Communication Port USB Port Earth Line Port R S232 1000VA Standard model rear panel 1500VA Standard /Super charger model rear panel 2K/3KVA Standard & Supper charger model) Function( AC Output Modem/Network Surge Protection...
  • Page 34 2000VA Standard model rear panel 2000VA Super charger model rear panel 3000VA Standard & Supper charger model rear panel...
  • Page 35 The EBM rear panel description table and picture are shown as below: 36V, 48V &72V EBM) Function( Earth Line Port 36V, 48V &72V EBM rear panel...
  • Page 36: Trouble Shooting

    8. Trouble Shooting 8.1 Audible Alarm Trouble Shooting Indication Cause Solution Sounding every 4 The UPS is on battery Check the input voltage seconds mode Sounding every Second The battery voltage is Save your work and turn off your and “bATL” on screen equipment Sounding every second Check load level indicator and...
  • Page 37: Software Installation

    9. Software Installation Winpower is UPS monitoring software, featuring user-friendly interface to monitor and control your UPS. This unique software provides complete power protection for computer system while power failure. With the software users can monitor any UPS status on the same LAN. Furthermore, a UPS can provide security protection for more than one computer on the same LAN at the same time, such as shutting down system in security, saving application data and shutting down the UPS when power fails.
  • Page 38 614-00766-01...