VII. Gas Piping
Explosion Hazard. Failure to properly pipe gas
supply to boiler may result in improper operation
and damage to the boiler or structure. Always
assure gas piping is absolutely leak free and of
the proper size and type for the connected load.
An additional gas pressure regulator may be
needed. Consult gas supplier.
NOTICE
Size corrugated stainless steel tubing (CSST)
to ensure proper capacity and minimize flow
restrictions.
A. Size gas piping. Design system to provide
adequate gas supply to boiler. Consider
these factors:
Table 16A: Maximum Capacity of Schedule 40 Black Pipe in CFH* (Natural Gas) For Gas Pressures
of 1/2 psi (3.4 kPa) or Less
Inlet Pressure 13.8 in wc (3.4 kPa)or less; 0.3 in wc (0.07 kPa) Pressure Drop
Nominal Pipe
Inside
Size, In.
Diameter, In.
½
0.622
¾
0.824
1
1.049
1.380
1.610
2
2.067
2.469
3
3.068
Inlet Pressure 13.8 in wc (3.4 kPa) or less; 0.5 in wc (0.12 kPa) Pressure Drop
Nominal Pipe
Inside
Size, In.
Diameter, In.
½
0.622
¾
0.824
1
1.049
1.380
1.610
2
2.067
2.469
3
3.068
* 1 CFH of Natural Gas is approximately equal to 1 MBH; contact your gas supplier for the actual heating value of your
gas.
WARNING
10
20
131
90
273
188
514
353
1056
726
1582
1087
3046
2094
4856
3337
8584
5900
10
20
172
118
360
247
678
466
1392
957
2085
1433
4016
2760
6401
4400
11316
7778
1. Allowable pressure drop from point of
delivery to boiler.
pressure is ½ psig (3.4 kPa). Actual point of delivery
pressure may be less; contact gas supplier for
additional information. Minimum gas valve inlet
pressure is printed on the rating label located in the
boiler's vestibule compartment.
2. Maximum gas demand.
input as printed on its rating label. Also consider
existing and expected future gas utilization
equipment (i.e. water heater, cooking equipment).
3. Length of piping and number of fittings.
Refer to Tables 16A (natural gas) or 16B (LP gas)
for maximum capacity of Schedule 40 pipe. Table
17 lists equivalent pipe length for standard fittings.
4. Specific gravity of gas.
gas with a specific gravity of 0.60 can be sized
directly from Table 16A and gas with a specific
gravity of 1.5 can be sized from Table 16B, unless
authority having jurisdiction specifies a gravity
factor be applied. For other specific gravity, apply
gravity factor from Table 18. If exact specific
gravity is not shown choose next higher value.
Length of Pipe, Ft.
30
40
50
72
62
55
151
129
114
284
243
215
583
499
442
873
747
662
1681
1439
1275
2680
2294
2033
4738
4055
3594
Length of Pipe, Ft.
30
40
50
95
81
72
199
170
151
374
320
284
768
657
583
1151
985
873
2217
1897
1681
3533
3024
2680
6246
5345
4738
Maximum allowable system
Refer to the boiler's
Gas piping systems for
60
70
80
50
46
42
104
95
89
195
179
167
400
368
343
600
552
514
1156
1063
989
1842
1695
1576
3256
2996
2787
60
70
80
65
60
56
137
126
117
257
237
220
528
486
452
791
728
677
1523
1402
1304
2428
2234
2078
4293
3949
3674
90
100
40
38
83
79
157
148
322
304
482
455
928
877
1479
1397
2615
2470
90
100
52
50
110
104
207
195
424
400
635
600
1223
1156
1950
1842
3447
3256
51