Min./Max. Combustion Air & Vent Piping Lengths; Vent And Air Piping; Removing From Existing Vent - Crest Audio FB(N,L)1500 Installation & Operation Manual

Table of Contents

Advertisement

2
General venting
Table 2B Direct Vent Minimum / Maximum Allowable Air / Vent Lengths
Model
Air Intake
Diameter
FB 1500
7"
FB 2000
8"
FB 2500
8"
FB 3000
10"
FB 3500
10"
FB 4000
12"
FB 5000
14"
Table 2C Room Air Minimum / Maximum Allowable Air / Vent Lengths
Model
FB 1500
FB 2000
FB 2500
FB 3000
FB 3500
FB 4000
FB 5000
When determining equivalent combustion air and vent
length, add 5 feet (1.5m) for each 90° elbow and 3 feet (.9 m)
for each 45° elbow.
EXAMPLE: 20 feet (6 m) of pipe + (4) 90° elbows + (3) 45°
elbows = 49 equivalent feet (15 m) of piping.

Removing from existing vent

Follow the instructions in Section 1, page 10 of this manual
when removing a boiler from an existing vent system.

Vent and air piping

Vent and air system:
Installation must comply with local
NOTICE
requirements and with the National Fuel
Gas Code, NFPA 54 / ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
You must also install air piping from outside to the boiler
air intake adapter. The resultant installation is direct vent
(sealed combustion).
You may use any of the vent/air piping methods covered in
this manual. Do not attempt to install the Crest using any
other means.
DO NOT mix components from different
WARNING
systems.
causing leakage of flue products into the
living space. Use only approved stainless
steel pipe and fittings.
(continued)
AIR INLET
Air Intake
Air Intake
Min. Length
Max. Length
12'
100'
12'
100'
12'
100'
12'
100'
12'
100'
12'
100'
12'
100'
Vent
Diameter
Min. Length
7"
8"
9"
10"
10"
12"
14"
The vent system could fail,
Installation & Operation Manual
VENT
Vent
Vent
Diameter
Min. Length
7"
12'
8"
12'
9"
12'
10"
12'
10"
12'
12"
12'
14"
12'
Vent
Vent
Max. Length
12'
100'
12'
100'
12'
100'
12'
100'
12'
100'
12'
100'
12'
100'
Vent, air piping and termination:
The Crest vent and air piping can be installed through the roof
or through a sidewall. Follow the procedures in this manual for
the method chosen. Refer to the information in this manual to
determine acceptable vent and air piping length.
Air contamination
Pool and laundry products and common household and hobby
products often contain fluorine or chlorine compounds. When
these chemicals pass through the boiler, they can form strong
acids. The acid can eat through the boiler wall, causing serious
damage and presenting a possible threat of flue gas spillage or
boiler water leakage into the building.
Please read the information given in Table 1A, page 9,
listing contaminants and areas likely to contain them.
contaminating chemicals will be present near the location of the
boiler combustion air inlet, have your installer pipe the boiler
combustion air and vent to another location, per this manual.
If the boiler combustion air inlet is located
WARNING
in a laundry room or pool facility, for
example, these areas will always contain
hazardous contaminants.
To prevent the potential of severe personal
WARNING
injury or death, check for areas and products
listed in Table 1A, page 9 before installing
the boiler or air inlet piping.
If contaminants are found, you MUST:
De-Rate per
Vent
25 feet of Vent
Max. Length
100'
100'
100'
100'
100'
100'
100'
Input De-Rate per
25 feet of Vent
1%
1%
1%
1%
1%
0%
0%
• Remove products permanently.
—OR—
• Relocate air inlet and vent
terminations to other areas.
Input
2%
2%
2%
2%
2%
0.5%
0%
If
17