Configuration - Liebert RCM8DO Installation & User Manual

Remote contact monitors
Table of Contents

Advertisement

Configuration

To access the RCM8 Main Menu VIA MODEM:
1. Make sure RCM8 and attached modem are turned on and
properly configured.
2. On the remote PC, set up terminal emulation session for
dial-out access – Connect Using an attached modem, rather
than direct connect to a com port.
3. Once a connection has been established with the RCM8,
press Space Bar to initiate the log-in process.
4. Type the RCM8 password, then press Enter to gain access to
the RCM8. The factory-default password for modem access
is also "RCM8".
5. From here, continue to Step 3 of the local login process.
The Configuration option from the Main Menu lets you view the
current RCM8 settings.
1. Press 1 to display the Configuration menu:
RCM8 V4.0 CONFIGURATION - MON 07-05-99
SITE ID = WEST WING COMPUTER ROOM
IN
DELAY
NO
DIAL
MM:SS
NC
A
-------------------------------------------
01
00:00
NO
1
02
00:00
NO
1
03
05:00
NC
2
04
00:00
NO
0
05
00:00
NO
0
06
00:00
NO
0
07
00:00
NO
0
08
00:00
NO
0
RCM8 Phone Number =
Phone Number 1
= 9,5551212,,,,,911##
Phone Number 2
= A9,18007596366
Dial Prefix
= ATE1X4DT
Redial Tries
= 2
Redial Interval
= 30
Modem
= CONNECTED
Modem Baud Rate
= 1200
EIA-485 Online Units =
This is a view-only screen. Use the remaining Main Menu
options to make changes or reset the values shown in this
screen.
2. Press Esc to return to the Main Menu.
Chapter 3: Main Menu and SubMenus
18:03:20
ALT
DIAL
MESSAGE
CODE
B
0
0
WATER UNDER FLOOR
0
0
HIGH TEMP
&
1
DOOR HELD OPEN
0
0
CLOGGED FILTER
0
0
HIGH HUMIDITY
0
0
CONTACT #6
0
0
CONTACT #7
0
0
CONTACT #8
PAGER ID - 5551149
Liebert RCM8 17