Battery Parameters - Liebert Battery Cabinet User Manual

Liebert user manual battery cabinet
Table of Contents

Advertisement

LRT
Model Number
Compatible With
UPStation GXT:
DIMENSIONS: in. (mm)
Unit W x D x H
WEIGHT: lbs (kg)
Unit
INPUT AC PARAMETERS
Voltage Range
Frequency
Input Power Factor
Current Reflected THD
Current Rating
Input Power Connection
Fuse Rating
OUTPUT DC PARAMETERS
Output Sockets
Interconnect Cable
Protection

BATTERY PARAMETERS

Type
Quantity x Voltage x
Rating
Approved Battery
Manufacturers:
Recharge Time
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Audible Noise
AGENCY
Safety
Surge
ESD
Susceptibility
Electrical Fast
Transient/Burst
Immunity
EMI/EMC
Additional information on this product can be located on our web site
(www.liebert.com) or FastBak server (614) 841-5471.
TM
Battery Cabinet Specifications
GXT96VLRT2UL
1800RT-208, 2000RT-120, 2000RT-230, 2700RT-208,
3000RT-120 and 3000RT-230 VA UPS'
15 x 27 x 29 (381 x 686 x 737)
600 lbs (272kg)
85 to 265VAC
>40 to <70 Hz; auto sensing
>0.95
30% THD maximum
< 4A at 120VAC, < 2A at 230VAC
IEC320-C14 recessed plug, with input cords:
(1) 6' cord with NEMA 5-15P
6.3 A
(2) per LRT cabinet
(1) 9.8' (3m) cable with appropriately keyed plugs
(1) resettable DC circuit breaker
Valve-regulated, nonspillable, lead acid
8 x 12V x 65.0Ah
CSB, Panasonic, and Yuasa
<20 Hours to 95% capacity after full discharge into 100% load
+32° F to + 104° F (0° C to +40° C) for altitudes
0 to 5,000 ft (1,500m);
+32° F to + 95° F (0° C to +35° C) for altitudes
5,000 ft (1,500m) to 10,000 ft (3,000m)
+5° F to + 122° F (-15° C to +50° C)
0% to 95%, non-condensing
< 45 dBA, at 1 meter
UL 1778; c-UL Listed; EN 50091-1; CE low voltage directive
IEEE 587 Category A; EN61000-4-5,
Level 3 (L-E), Level 2 (L-L)
EN6100-4-2, Level 3
EN6100-4-3, Level 2
EN6100-4-4, Level 3
EN50082-1
FCC Part15, Class A; EN50081-1; EN 55022, Class B;
CE EMC Directive
7

Advertisement

Table of Contents
loading

Table of Contents