Atsumi Electric NR30TD Installation Instructions Manual

Beam detectors

Advertisement

Quick Links

BEAM DETECTORS
NR30TD (Outdoor 30m/ Indoor 60m)
NR60TD (Outdoor 60m/ Indoor 120m)
NR90TD (Outdoor 90m/ Indoor 180m)
INSTALLATION INSTRUCTIONS
In this manual, symbols and marks are used to call attention to instructions that should be observed when installing the detector
so as to prevent the user and others from being exposed to a danger and property from being damaged.
Have full understanding of these marks before reading this installation manual.
Symbol
Indicates that failure to observe this instruction may cause a possible danger resulting in death or
WARNING
serious injury to the user.
Indicates that failure to observe this instruction may possibly cause injury to the user or damage to the
CAUTION
property.
The contents of instructions are identified by following marks of two types.
Mark
1
FOR PROPER INSTALLATION
1. Observe following instructions for installation of the unit.
This detector is intended for detection of human intruder. When using it for any other purpose, be sure to study and
test carefully in advance.
Study carefully possible intrusion route and posture of an intruder to determine the installation position so that the
beam is interrupted without fail.
Where there is not enough strength, perform full reinforcement work before installing the detector. If installed where
not strong enough, the detector may drop, possibly resulting in its failure or damage and personal injury.
The beam spread angle of this detector is about 1° on each side. When using a multiple number of the same type
detectors or when using this detector with another type detector, position them so that no interference would occur.
Do not install the unit where the beam is interrupted by an obstacle, or malfunction may result.
Do not install the unit where intense source of light such as sunlight and automobile head light beam is reflected into
the receiver. A strong light incoming within ±3° angle of each receiver axis may cause malfunction.
Do not install the unit where the detector can move easily after being installed, or malfunction may result.
Do not install the unit where it is exposed to foul water or sea spray, or a failure or malfunction may result.
Do not install the unit where the distance between the transmitter and receiver exceeds the rated detectable dis-
tance, or malfunction may result.
Do not install the unit where electrical noise or electromagnetic wave exists, or a failure or malfunction may result.
Do not install the unit where the detector receives strong impact or vibration, or a failure or malfunction may result.
Indicates what MUST NOT be performed..
Indicates what MUST be performed.
We appreciate your purchase of ATSUMI INTRUDER
ALARM SYSTEM BEAM DETECTOR. Please read this
installation manual carefully for appropriate installation
of the product and keep it in a safe place for the future
use.
<NOTE>
This detector is intended for detection of an illegal in-
truder and NOT for theft prevention. Each user is re-
quested to use it effectively under his/her full control.
ATSUMI ELECTRIC Co., Ltd. shall not be liable for any
theft or damage.
Meaning
Meaning
CAUTION
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NR30TD and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Atsumi Electric NR30TD

  • Page 1 NOT for theft prevention. Each user is re- NR90TD (Outdoor 90m/ Indoor 180m) quested to use it effectively under his/her full control. ATSUMI ELECTRIC Co., Ltd. shall not be liable for any INSTALLATION INSTRUCTIONS theft or damage. In this manual, symbols and marks are used to call attention to instructions that should be observed when installing the detector so as to prevent the user and others from being exposed to a danger and property from being damaged.
  • Page 2: General Description

    GENERAL DESCRIPTION The NR30TD/NR60TD/NR90TD outputs an alarm when the infrared pulse beam (referred to as beam hereinafter) emitted from its transmitter is not received by the receiver for a certain period of time (beam interruption time). To reduce influences from various external factors, the unit is provided with following features.
  • Page 3: Part Names And Functions

    PART NAMES AND FUNCTIONS Cover Transmitter Receiver Chassis Mount bracket Operation section of transmitter Operation section of receiver 1 Cover 6 Horizontal adjustment screw Passes the near infrared ray and attenuates the visible Used to make fine adjustment of optical axis horizontally. 7 Twin lens ray.
  • Page 4 DC30V, 0.1A DC30V, 0.1A Receiver Transmitter 2. WIRING LENGTH Maximum wiring distance (m) CAUTION Wire gauge NR30TD NR-60TD NR90TD Do not use aerial wiring, or malfunction may re- DC12V DC24V DC12V DC24V DC12V DC24V sult. AWG22 or φ0.65 2000 1850...
  • Page 5: Installation

    INSTALLATION For pole mounting, pole-back mounting, and embedded mounting, optional parts are required. In any of these cases, purchase the required optional parts and install the unit according to the installation manual supplied with the optional parts. Described below is the installation procedure for wall mounting. For more information on optional parts, refer to OPTIONAL PARTS.
  • Page 6: Sensitivity Adjustment

    SENSITIVITY ADJUSTMENT It is possible to adjust the detection sensitivity by adjusting the interruption time adjustment volume. When the unit is mounted on a wall, the interruption time can be set longer because the intruder cannot move quickly. This way, it is possible to prevent an erroneous operation by a bird, small animal, paper and other object that flies in.
  • Page 7: 11 Troubleshooting

    OPERATION CHECK 1. Alarm Operation Transmitter Receiver To check the alarm operation, actually walk along as- sumed intrusion path near the transmitter and receiver, respectively and in-between as shown in the figure be- low. Check that the alarm LED lights up and the controller 2.
  • Page 8 SPECIFICATIONS Product Name Photoelectric Detector Model NR30TD NR60TD NR90TD Power DC 10.5V ~ 28V Current Draw Transmitter: 11mA / Transmitter: 15mA / Transmitter: 20mA / Receiver: 43mA Receiver: 43mA Receiver: 43mA Operating Temp./Humid. -25°C ~ +60°C, RH 95% or less Storage Temp./Humid.