Download Print this page

System Overview; Specification - AccessZone GC500 Series Installation Manual

Access control systems

Advertisement

AccessZone ® - GC500/GC600 Series – Installation Manual

2 System Overview

This section presents a system overview:
Input 1 (IN1)
Block Operation
(Prevents any door/
gate activation)
Input 2 (IN2)
REX Button and
Alarm arm/
Alarm reject
arming

3 Specification

Description:
Dimensions
Weight
IP
Operation temp.
Humidity
Electrical:
Supply
Power
Outputs
Inputs
1)
A 500mA low noise power supply of high quality should be used
2)
The active levels (high/low) of inputs and outputs can be configured. Please refer to the User
Manual for more information.
All information is subject to change without notice. All other products and brand names are registered trademarks of their respective companies
Copyright © 2005-2011 All rights reserved MVC-Data ApS Skalhuse 5 9240 Nibe Denmark Web www.mvc-data.com E-mail info@mvc-data.com Phone +45 25 12 84 02
127 x 47 x 8 mm (H x W x D)
100g
67
-30°C - +80°C
100%
1)
12V DC, max. 120mA
max. 1,5W
2 outputs (open collector type), 500mA
2 inputs
Output 1 (OC1)
(Level/Latched)
Alarm Arm and Disarm/
Light Control Switch
Output 2 (OC2)
(Pulse/Level/Latched)
Door lock/gate control
2)
2011-03-21 US 1.05
5/7

Advertisement

loading

This manual is also suitable for:

Gc600 series