ENGLISH Read carefully all warning and instructions contained in this manual at they give important safety instructions regarding installation and maintenance. Keep this manual for future reference. Installation must be carried out by qualifi ed personnel who will be responsible for respecting existing safety regulations.
1959 with a widespread network of agents and concessionary agents to constantly guarantee the presence of our product on the market. Alongside this is the support of a technical service, “LAMBORGHINI SERVICE”, which is entrusted with the qualifi ed servicing of the product.
AUTHORISED SKILLED TECHNICIANS. TO ENSURE THAT BOILER IS INSTALLED CORRECTLY AND THAT IT FUNCTIONS PROPERLY, WE RECOMMEND THAT ONLY LAMBORGHINI ACCESSORIES AND SPARE PARTS BE USED. ON NOTICING THE SMELL OF GAS DO NOT TOUCH ANY ELECTRIC SWITCH. OPEN DOORS AND WIN- DOWS.
fl ue gas exchanger; Hot water plate exchanger. XILO T 20 N MS W TOP Equipped with electronic control unit for automatic ignition and ionization electrode fl ame control. To ensure safe operation, the electric fan is controlled by a pressure switch.
MAIN COMPONENTS XILO T 20 N MS W TOP Fume analysis points 14 13 LEGEND 11 Circulator 20 Lock-out warning light Fumes pressure switch 12 Filling cock 21 Fixed knob Heating sensor 13 Gas valve 22 Function selector Total safety thermostat...
DIMENSIONS mm XILO T 20 N MS W TOP Max. 3000 Max. 3000 TECHNICAL FEATURES Operating Expan- Connections Weight Thermal capacity Min. thermal capacity sion pressure tank max. MODEL Cold water Main system Output Input Input Output inlet Return Supply...
GAS - NOZZLE CALIBRATION The boilers leave the factory calibrated and ready to operate with G20 (Natural gas) and G30/G31 (LPG). For proper calibration, see the table below: Jets pressure mbar Burner Gas type Delivery L.C.V. XILO T 20 N MS jets min.
The power lead must only be replaced by another with the following characteristics: “HAR H05 VV-F” 3 X 1.00 . (You are strongly advised to use original LAMBORGHINI accessories and spare parts only). Installation must be made in compliance with safety REGULATIONS IN FORCE.
Page 10
ASSEMBLY DIAGRAM XILO T 20 N MS W TOP - card code 4.56035.0 TL (BASSA TEMP.) JUMPER TO BE CUT IF LIMIT THERMOSTAT IS REQUIRED R max. PANEL CONNECTION Lock-out warning light ON/OFF warning light Malfunction warning light LEGEND Gas valve SIT 837...
Page 11
ASSEMBLY DIAGRAM XILO T 20 N MS W TOP - card code 4.55828.0 JUMPER TO BE CUT IF LIMIT THERMOSTAT IS REQUIRED JP5 (BASSA TEMP.) Rmax . PANEL CONNECTION Lock-out warning light ON/OFF warning light Malfunction warning light LEGEND Safety thermostat...
Page 12
ASSEMBLY DIAGRAM XILO T 20 N MS W TOP - card code 4.56040.0 JP6 JP7 JUMPER TO BE CUT IF LIMIT THERMOSTAT IS REQUIRED JP5 (BASSA TEMP.) Rmax . PANEL CONNECTION ON/OFF warning light Malfunction warning light Lock-out warning light...
MULFUNCTIONS AND ADJUSTMENTS Constant light: No water Constant light: Ignition shutdown Fast fl ashing light: Sensor fault Fast fl ashing light: Slowly fl ashing light: TST shutdown Air pressure switch (MS) Should the boiler shut down it must be reset by rotating functions selector switch to position A. B: see TEST functions at “Gas pressure adjustments with Honeywell VK 4105 valve”...
WATER CONNECTION Fit the supporting hooks and attach the assembly template, moving it up to the wall; fi t all the pipes, starting with the end pipe fi ttings already mounted on the template: system supply, system return, cold water, hot water, any gas pipes and electric mains leads with room thermostat.
WATER CIRCUIT XILO T 20 N MS W TOP Fume analysis points LEGEND System delivery No-water pressure switch Circulator Cold water inlet Burner System return Expansion tank Exchanger Fumes pressure switch Modulator coil Heating sensor Automatic air bleed valve Gas valve...
INSTALLATION To be carried out by qualifi ed personnel. The installation must be in compliance with the stipulations of the law regarding the evacuation of combustion materials according to the REGULATIONS IN FORCE. The gas fume evacuation must be effected with a pipe of a diameter not less than that required by the boiler and it must be connected to a fl...
FLUE EXHAUST CONNECTION CONNECTION TO THE CHIMNEY - VERSION XILO T 20 N MS W TOP The boiler is for combustion in a sealed chamber and does not require any special ventilation, it can also be located in small rooms, lumber-rooms, laboratories. In addition, there are various possibilities for combustion fume evacuation and external air intake;...
ELBOW FITTED ELBOW FITTED TYPE OF INSTALLATION AT 90° AT 45° 0,5 m CONCENTRIC FLUE PIPE 0,6 m 0,3 m SEPARATE INTAKE/EXHAUST ** Air intake Ø 80 ATTENTION: Use only air intake/ fume evacuation kits produced by Lamborghini Caloreclima.
GAS PRESSURE ADJUSTMENTS WITH HONEYWELL VK 4105 VALVE All boilers are tested and calibrated in the factory. At fi rst ignition it is necessary to check and set up the boiler to adapt it to the system characteristics. The gas pressure at the burner must be checked through the pressure plug placed on the pipe coming out from the gas valve and by using a water column pressure gauge or a micro-manometer.
Frequency of inspection depends on the specifi c conditions of installation and use but it is advisable to have the unit checked once a year by authorised Lamborghini Service personnel. Only properly qualifi ed personnel with specifi c knowledge in the fi eld of safety, effi ciency, environmental hygiene and combustion may carry out work on the unit.
Page 21
removal of any oxidation from burners removal of any encrustation from heat exchangers checking and general cleaning of fan (mod. MS) checking connections between the various air/fume pipes general pipe cleaning checking general external appearance of boiler checking for proper ignition, shutdown and operation of both hot water and heating functions checking for proper seal on gas/water fi...
OPERATION WITH DIFFERENT TYPES OF GAS CONVERSION FROM NATURAL GAS TO LIQUID GAS The boiler is factory-set for G20 (Natural Gas) or G30/G31(LPG) operation, as mentioned on the Technical Nameplate and on the apparatus packaging. In the event the heater shall be operated using a different gas from that conceived by factory setting, a special kit has to be installed, which is to be ordered separately.
FAULT-FINDING CHART FAULT CAUSE REMEDY 1 NO IGNITION A. Gas cock closed A. Open gas cock B. Boiler locked out B. Reset by pressing C. No fl ame detection C. Neutral and phase inverted D. No ignition spark D. Call technical service E.
Page 24
TRATTAMENTO ACQUA CONDIZIONAMENTO Le illustrazioni e i dati riportati sono indicativi e non impegnano. La LAMBORGHINI si riserva il diritto di apportare senza obbligo di preavviso tutte le modifiche che ritiene più opportuno per l'evoluzione del prodotto. The illustrations and data given are indicative and are not binding on the manufacturer. LAMBORGHINI reserves the right to make those changes, considered necessary, for the improvement of the product without forwaming the customer.
Page 25
AZIENDA CERTIFICATA ISO 9001 CALDAIA MURALE A GAS TERMO ALTO RENDIMENTO - MODULANTE MANUALE PER L‘UTENTE Alla cortese attenzione del sig. INSTALLATORE: Consegnare il presente manuale d’uso all’UTENTE WALL-HUNG GAS BOILER FOR HEATING FOR HIGH EFFICIENCY - MODULATING USER MANUAL For the attention of the INSTALLATION TECHNICIAN: make sure that this manual is handed over to the USER CALDERA MURAL A GAS PARA CALEFACCIÓN...
Page 26
Carefully read this manual to know all information about the appliance operation. “LAMBORGHINI AFTER-SALE SERVICE”, is at your disposal to grant you a QUALIFIED MAINTENANCE and a VERY PROMPT AFTER-SALE SERVICE...
AUTHORISED SKILLED TECHNICIANS. TO ENSURE THAT BOILER IS INSTALLED CORRECTLY AND THAT IT FUNCTIONS PROPERLY, WE RECOMMEND THAT ONLY LAMBORGHINI ACCESSORIES AND SPARE PARTS BE USED. ON NOTICING THE SMELL OF GAS DO NOT TOUCH ANY ELECTRIC SWITCH. OPEN DOORS AND WIN-...
Call exclusively professionally qualifi ed personnel. Any repair must be carried out by an after-sale service centre “LAMBORGHINI SERVICE” authorised by the manufacturing fi rm, and using original replacements exclusively. Non-observance of the above could compromise the guarantee and the safety of the appliance.
CHECKS AND MAINTENANCE ● Prima di avviare la caldaia far verifi care da Personale Qualifi cato “LAMBORGHINI SERVICE”: a) that the data on the information plate corresponds to that required by the gas, electrical and water supply networks; b) that the pipes which branch off from the boiler are lined with suitable thermally-insulated sheathing;...
DIMENSIONS mm XILO T 20 N MS W TOP Max. 3000 Max. 3000 CONTROL PANEL AND ADJUSTMENTS Constant light: No water Constant light: Ignition shutdown Fast fl ashing light: Sensor fault Slowly fl ashing light: Air pressure Fast fl ashing light: TST shutdown switch (MS) Should the boiler shut down it must be reset by rotating functions selector switch 6 to position A.
IGNITION - OPERATION - SHUTDOWN INSTRUCTIONS IGNITION Open the gas tap and tun the selector switch (6) to the desired position. The burner will ignite automatically. Should ignition fail to take place check the lock-out warning light (1) and fault warning light (3) to see if they have come on.
FAULT-FINDING CHART FAULT CAUSE REMEDY 1 NO IGNITION A. Gas cock closed A. Open gas cock B. “Lock-out” button locked B. Reset by pressing C. No fl ame detection C. Call technical service D. No ignition spark D. Call technical service E.
Page 33
TRATTAMENTO ACQUA CONDIZIONAMENTO Le illustrazioni e i dati riportati sono indicativi e non impegnano. La LAMBORGHINI si riserva il diritto di apportare senza obbligo di preavviso tutte le modifiche che ritiene più opportuno per l'evoluzione del prodotto. The illustrations and data given are indicative and are not binding on the manufacturer. LAMBORGHINI reserves the right to make those changes, considered necessary, for the improvement of the product without forwaming the customer.