Installation, Operation, Maintenance and Owner's Manual
Standard Models 36, 42 & 46 - Magnum Models 28,36,42 & 48
A PRODUCT OF EARTHCORE INDUSTRIES, LLC.
Important: This manual contains assembly rules, installation steps, guidelines, use and maintenance in-
structions for the Fire-Lite application fireplace with the FTF-13 Chimney System. This manual must be-
come the property of and be reviewed by all current and future users of this product. It is the responsibility
of the general contractor and the installer of this product to ensure that the instructions in this manual are
followed exactly and, further that any allowed gas log appliance used in this product be installed in strict
accordance with NFPA 58, NFPA 54/ANSI Z223.1 and the gas log manufacturer's explicit installation, siz-
ing and operation instructions. It is the responsibility of the general contractor to provide adequate clear-
ances from all firebox surfaces as specified in this manual.
Be Sure to Read Entire Manual Before Beginning Construction.
Contents of this manual may change without prior notification.
THIS FIREPLACE IS DESIGNED for USE with
SOLID WOOD LOGS, PLUMBED PROPANE
WARNING: If the information in this manual is not followed exactly, a fire or explosion may
result causing property damage, personal injury or loss of life.
SBCCI NO. 9626
ICC Report NO. ESR-2316
IBC 2006, IRC 2006, IMC 2006
THIS MANUAL CAN ONLY BE REPRODUCED IN ITS ENTIRETY
Isokern® Fireplace
FIRE-LITE SERIES
INSTALLER: Leave this manual with the appliance
CONSUMER: Retain this manual for future reference
(LP) or NATURAL GAS (NG), ONLY
INTERTEK TESTING SERVICES REPORT NO. 3159656MID-008
NYC-MEA 241-90-E
LA RR NO. 25483
Issued: April, 2011
Revision: 001
© 2007 Earthcore Industries, L.L.C.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FIRE-LITE series and is the answer not in the manual?

Questions and answers

Summary of Contents for Isokern FIRE-LITE series

  • Page 1 Isokern® Fireplace FIRE-LITE SERIES Installation, Operation, Maintenance and Owner’s Manual Standard Models 36, 42 & 46 - Magnum Models 28,36,42 & 48 A PRODUCT OF EARTHCORE INDUSTRIES, LLC. Important: This manual contains assembly rules, installation steps, guidelines, use and maintenance in- structions for the Fire-Lite application fireplace with the FTF-13 Chimney System.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS General Information ............................Intended Use Statement ............................Safety Instructions .............................. Warnock-Hersey Listing Label ........................... Assembled Firebox & Smoke Dome Dimensions ....................Component List & Dimensions .......................... Required Clearance to Combustibles ......................... Rough Framing Dimensions & Corner Location Layout ................... Assembly Instructions ..........................
  • Page 3: General Information

    General Information The Fire-Lite fireplace is a prefabricated, refractory modular fireplace designed for field assembly on a combustible floor. The system consists of interlocking precast parts which are glued together with a masonry adhesive. The parts of the Fire-Lite fireplace are precast using a proprietary mixture of volcanic pumice aggregate and cement.
  • Page 4: Intended Use Statement

    2. All work performed on, near and adjoining the fireplace and chimney installation must meet or exceed the specifications and requirements in this manual and the prevailing local building code. Isokern is not responsible for other construction work around the unit. Recommended...
  • Page 5: Safety Instructions

    Isokern. Failure to heed this other material. No material is allowed in these spaces. warning may cause a fire hazard and will void the Isokern 18. Never leave children unattended when there is a fire warranty.
  • Page 6: Warnock-Hersey Listing Label

    FIGURE 1 Isokern Fireplace and Chimney Systems are tested and listed to UL Fire-Lites: UL 127, ULC S610, and UL 103HT. The listing label shown in Figure 1 above outlines the listed clearances to combustibles and indicates that the units are suitable for use with solid fuel or listed gas appliances.
  • Page 7: Assembled Firebox & Smoke Dome Dimensions

    Assembled Firebox & Smoke Dome Dimensions 36, 42 & 46...
  • Page 8: Component List & Dimensions

    Component List & Dimensions 36, 42 & 46 Isokern reserves the right to make changes at any time, without notice in design, materials and specifications and also to discon- tinue styles and products. Please call (800) 642-2920 for an Isokern dealer near you.
  • Page 9: Required Clearance To Combustibles

    1” thick ceramic fiber insulation board rated to 2100 degrees Fahrenheit (Figure 10). 2. All Fire-Lite Series result in the finished fire brick floor of the firebox being at least Eight and a half inches (8 1/2”) above the combustible floor system (Figure 1).
  • Page 10: Rough Framing Dimensions & Corner Location Layout

    Rough Framing Dimensions Rough Framing Dimensions Model Width Height Depth Standard Series: Model 36 46” 68 3/4” 26 3/4” Model 42 52” 68 3/4” 26 3/4” Model 46 56” 68 3/4” 26 3/4” Magnum Series: Model 28 38 1/2” 65 3/4” 29 1/2”...
  • Page 11: Assembly Instructions

    By adding the weight of the appropriate Fire-Lite Model listed in #1 above to the allowance given for each item in 2 through 4 above, the total weight of the Fire-Lite Series can be estimated. The floor area for each model is as follows: Model 36 Standard Series @ 43”...
  • Page 12 Assembly Instructions - (cont.) Installation: Earthcore Mortar (a thin-set type masonry adhesive) is used to glue all Isokern components together during field assembly of the unit. The mortar is supplied dry, in either 15 pound or 50 pound pails. Earthcore Mortar is mixed with clean water to a smooth, workable texture (without lumps or dry pockets) of a “toothpaste”...
  • Page 13 It may be convenient to dry set the first course of side wall and back wall into place on the Isokern base plate and then to trace their position on the base plate with a pencil.
  • Page 14 Assembly Instructions - (cont.) Step 4: Continue assembly of the second and third courses of the side wall and back wall. Apply mortar to the top of each layer of wall components, then set the next course above into place. Be sure to mortar all vertical joints of the side wall to back wall connection when setting each component to its mate.
  • Page 15: Access Modification

    CAUTION: When using the decorative appliance, the fireplace damper must be set in the fully open position. Gas line for gas log sets used in the Isokern firebox can be routed through the side wall, back wall or floor of the firebox by drilling an appropriately sized hole using a masonry drill bit (Figure 18).
  • Page 16: Firebrick Installation

    Isokern makes no claims as to the performance of fire brick or fire brick mortar(s). It is typical for heat stress cracks to appear in the fire bricks in wood burning fireplaces.
  • Page 17: Flush Wall Finish Detail

    FIGURE 24 Fire-Lite Series fireplaces are designed to be installed so that the rough front face of the firebox and smoke dome sit flush to the room face of the rough framing members that create the room wall finish. (Figure 24) CAUTION: Do not frame a wall in front of the Fire-Lite Series firebox / smoke dome assembly, as shown in figure 25 Wall framing must not be placed across the front face of the fi rebox and smoke dome assembly.
  • Page 18: Required Clearances (When Sheathing Protrudes Beyond Front Of Firebox)

    The manufacturer strongly recommends that wherever possible, all combustible framing materials be kept a minimum of 1-1/2” clearance from the Isokern fireplace unit at the side walls and back walls. It is the responsibility of the General Contractor to insure that listed clearances to combustible framing and to insulation are maintained throughout the construction of the project...
  • Page 19: Required Clearance To Combustible Framing

    Do not frame a wall in front of the Isokern fireplace unit. When sheathing is installed directly to the front face of the Isokern fireplace unit, be sure that when the required noncombustible finished facing materials are applied that no gaps or voids are left behind the finished facing materials.
  • Page 20: Required Clearances To Insulation And Vapor Barriers

    When Fire-Lite fireplace installations are surrounded by walls that are to be insulated, the walls must have enough clearance to the Isokern unit in order to maintain the three inch (3”) minimum clearance to insulation. (Figure 33) Never spray the Fire-Lite fireplace with any type of sealer, insulation or other material.
  • Page 21: Flush Wall Fire Brick Finish Detail

    Flush Wall Fire Brick Finish Detail FIGURE 34 Recommended Fire Brick Detail: When drywall is the wall finish at the Fire-Lite face and flush with the rough face of the Fire-Lite firebox and damper beam, it is recommended when installing the required fire brick lining to the interior of the firebox, that the leading edge of the fire brick - at the floor and at the side walls of the firebox - be set flush with the Fire-Lite’s rough firebox front.
  • Page 22: Flush Wall Brick Finish Detail

    Finish Facing Detail FIGURE 35 Important: Since there is no fire brick set along the top of the Fire-Lite’s firebox opening, when setting the noncombustible finished facing material (code required and supplied by others) across the top of the firebox opening there may be a gap between the back of the noncombustible finish material and the rough front face of the Fire-Lite damper plate.
  • Page 23: Interior Masonry Veneer Fireplace Finishes & Clearances

    Interior Masonry Veneer Fireplace Finishes & Clearances FIGURE 37 FIGURE 36 FIGURE 38...
  • Page 24: Masonry Veneer Construction Details

    Masonry Veneer Construction Details Brick, stone or other masonry veneer finished fronts to Fire-Lite fireplaces are possible. Special attention is required with regards to: (1) the placement of the proposed masonry veneer facing and its interface with the Fire-Lite fire brick lining, and (2) Clearance to combustible framing and sheathing from any steel “L”...
  • Page 25: Non Combustible Finished Facing Requirements & Clearance To Combustible Trim

    Non-combustible Finished Facing requirements & Clearance to Combustible Trim Hearth Extensions: All Fire-Lite fireplaces shall have hearth extensions of brick, concrete, stone, tile or other code approved noncombustible material. Suitable hearth extension material for the Fire-Lite fireplace shall be placed on the hearth extension’s noncombustible substrate and must extend to at least twenty inches (20”) in front of the fireplace’s finished opening and must extend to at least twelve inches (12”) beyond the sides of the...
  • Page 26: Concrete Support

    1. Slab on grade: Fire-Lite residential, minimum four inch (4”) thick, 2500 psi concrete foundations on properly compacted fill. This type foundation can support Isokern installations up to thirty feet (30’) overall height (brickledge installations not included). (Figure 43) 2. Slab-on-grade foundations, thickened and reinforced: for additional load carrying.
  • Page 27: General Information

    DM 54 Chimney System: General Information The DM 54 chimney is a dual module, refractory masonry chimney system. It is composed of two precast, mating components, the outer casing block and an inner liner. General Information: This chimney system is designed for installation in accordance with the National Fire Protection Fire-Lite for Chimneys and Solid Fuel-Burning Appliances, NFPA 211 and in accordance with codes such as ICC, BOCA Basic/National Codes, theInternational...
  • Page 28: Component List & Dimensions

    DM 54 Chimney Component List & Dimensions...
  • Page 29: Component Weights

    DM 54 Chimney: Component Weights Isokern DM Chimney Weights: Total installed Isokern DM chimney weight will vary according to each specific installation. Total installed chimney weight will be based on the overall height and the configuration of the chimney system.
  • Page 30 DM 54 Chimney Alignment: Where the chimney run is to be a straight vertical run the DM 54 outer casing block sits directly onto the Isokern smoke dome lid. The DM 54 outer casing block, properly set is intended to be flush with the back face of the firebox smoke dome assembly (Figures 49 &...
  • Page 31: Lateral Support

    DM 54 Chimney System: Lateral Support Additionally, a two inch (2”) by four inch (4”) by CAUTION: six feet (6’) minimum pressure treated member (“rat run”) Maintain three inch (3”) minimum clearance to installed on each side of and butted up to the outer casing block insulation from all DM 54 chimney component surfaces.
  • Page 32 DM 54 Chimney System: Lateral Support (cont.) FIGURE 51 FIGURE 52...
  • Page 33: Offset Block

    DM 54 Offset Chimney Block: For vertical DM 54 chimney to bypass overhead obstructions, the Isokern offset chimney block is used. Offset blocks are six inch (6”) thick, single module chimney components, measuring twenty-one and one-half inch (21-1/2”) wide by twenty-five inches (25”) long. The fourteen inch hole passes through the block at thirty (30°) degrees.
  • Page 34 (Figure 57) Offset block Support Foundations: It is required that every third Isokern offset chimney block in the sequence be supported down to footings via concrete block or steel support columns. (Figure 58)
  • Page 35 The total chimney weight above the last offset block will be the total weight of the vertical chimney plus any additional al- lowable loads such as the Isokern brickledge, its related brick or stone veneers, and any crown caps, clay pots or other masonry chimney terminations.
  • Page 36 Temporarily leave out the inner liner that fits this outer casing block. Set the Isokern brickledge onto the flat top surface of the outer casing in a full bed of Earthcore Mortar. Be sure to align the four 2-1/2” holes in the brickledge with the matching holes in the outer casing block below it.
  • Page 37: Brick Ledge Installation

    All DM 54 chimneys that include the DM 54 brickledge must be reinforced as described above. CAUTION: When using the Isokern brickledge it is required that the Fire-Lite firebox/smoke dome assembly include the placement of a 4” by 4” by 3/8” minimum steel angle across the firebox opening.
  • Page 38: Brick Ledge Load Capacity

    FIGURE 65 Brickledge Veneer Finish and Flashing Details: When applying brick, stone or other masonry veneer to the Isokern brickledge Fire-Lite good building practices for masonry veneer work should govern weather-proofing details and the placement of flashings. A typical flashing detail would be to field fabricate an aluminum or galvanized sheet metal flashing, approximately thirty-two inches (32”)square with a twenty inch (20”) square...
  • Page 39: Crown Caps

    The small crown cap is intended for use where DM 54 chimneys are to receive thin veneers and cultured stone that do not require the installation of the Isokern brickledge. The small crown cap is also suitable where DM 54 chimneys are to receive a stucco finish.
  • Page 40: Height Requirements

    Chase enclosures need to be built to local wind load require- ments and shall be structurally independent of the Isokern chimney. As with all chimney installations, avoid overhead obstructions such as trees, power lines, etc.
  • Page 41: Structural Information / Wind Loads

    Structural Support The Fire-Lite firebox/smoke dome assembly has a load capacity that allows for the fireplace system to carry a limited amount of straight, vertical DM 54 chimney sections. The load capacity for each model, stated as maximum DM 54 chimney heights, are as follows: Fire-Lite Model 36: Max.
  • Page 42: Common Chimney Terminations

    Common Chimney Terminations Two chimney terminations are offered by Isokern, the DM 54 large crown cap and the DM 54 small crown caps. These are cement crown caps designed to provide a weather cap to the DM 54 chimney system. Their design is typical of the cement caps found on traditional masonry chimneys.
  • Page 43: Class A Metal Flue

    Class “A” (solid fuel) chimneys as an option. Any Class “A” or UL 103 listed metal chimney system is acce- table for use on an Isokern system. (Figure 76) Class “A” Metal Flue Types: The selected factory-built metal chimney for use with...
  • Page 44: See-Thru

    Drafting formulas indicate that 14” diameter flue is large enough to support a two sided Fire-Lite Series 36” fire- place if the unit has at least 24’ of flue. This, however, is no guarantee of draft performance.
  • Page 45: Two Story Stacked Installations

    Specialty Applications - Two Story Stacked Installations General Information: To install one Fire-Lite fireplace and DM 54 chimney system above another, as in a two story stacked installation, both the upper and lower fireplace installations require a con- crete slab that is supported down to footings via concrete or steel support structure.
  • Page 46: Specialty Applications

    “D” is also the sum of “B” plus “C”. “E” is the height of the Fire-Lite fireplace chosen for the lower unit and includes the Isokern three inch thick base plate. “E” is seventy inches (69 ½” actual) for all of the Fire-Lite models.
  • Page 47: Fire-Lite Application General Information

    Also the Fire-Lite assembled unit must sit on a raised, noncombustible platform. The parts of the Fire-Lite fireplace are an applica- tion of the Fire-Lite Series Fireplace. The requirements for the Fire-Lite fire brick installation will apply. See page 19 of this manual for fire brick installation.
  • Page 48: Fire-Lite Application - Required Clearance To Combustibles

    1” thick ceramic fiber insulation board rated to 2100 degrees Fahrenheit (Figure 90). All Fire-Lite Series result in the finished fire brick floor of the firebox being at least eight inches (8 1/2”) FIGURE 87 above the combustible floor system (Figure 87).
  • Page 49: Fire-Lite Application - Combustible Floor System

    5. Weight of metal flue: negligible By adding the weight of the appropriate Fire-Lite Model listed in #1 above to the allowance given for each item in 2 through 5, above, the total weight of the Fire-Lite Series can be estimated. FIGURE 89...
  • Page 50: Fire-Lite Application - Raised Metal Platform

    Fire-Lite Application - Raised Metal Platform The noncombustible raised platform must be set with a minimum one and one half inch (1-1/2") clearance to the wall directly behind the Fire-Lite assembly. Raised Platform: Nominal four (4") metal base. (Figure 91).Set the Fire-Lite base plate in a mortar bed on to the non-combus- tible raised platform.
  • Page 51 Fire-Lite Application - Raised Metal Platform (cont.) FIGURE 93...
  • Page 52: Fire-Lite Application - Flush Wall Finish Detail

    FIGURE 95 Fire-Lite Fire-Lite Series fireplaces are designed to be installed so that the rough front face of the firebox and smoke dome sit flush to the room face of the rough framing members that create the room wall finish. (Figure 94) CAUTION: Do not frame a wall in front of the Fire-Lite Fire-LiteSeries fire box/smoke dome assembly, as shown in figure 95.
  • Page 53: Ftf-13 Or Equivalent Chimney System

    FTF-13 or Equivalent Chimney System The Fire-Lite is designed, tested and listed for use with FTF-13 Class A metal chimney system, or equivalent. Do not modify or alter metal flue or metal flue components as this could result in an unsafe and potentially dangerous installation that may cause a serious hazard and void the listings, approvals and the limited warranty of the system.
  • Page 54 FTF-13 or Equivalent Chimney System (cont.) Installation of the FTF-13 Metal Chimney System for the Fire- Lite: Transition from the Fire-Lite to the FTF-13 Metal Chimney System: The FTF-13 metal flue attaches to the smoke dome’s top plate by use of the AP-ISO masonry anchor plate. The Anchor Plate is fitted with an octagonal base plate to affix it to the smoke dome’s top plate.
  • Page 55: Ftf-13 Or Equivalent Installation Components

    FTF-13 Installation Components Round Termination FireStop Spacer (30°) FireStop Spacer Offset/Return Package (30°) Chimney Section Combination Offset Return Elbow Stabilizer Anchor Plate Locking Band...
  • Page 56: Summary

    3. Log grates are required for burning solid fuel in the Instructions: Isokern fireplace. Grates allow for easy air flow up through It is critical that the Isokern masonry elements in the the burning logs thus creating a more complete and efficient Fire-Lite firebox and smoke dome assembly be dry before fir- burning of the fuel.
  • Page 57 Isokern does not limit the use of In either case, cover the fireplace opening with a fireplace screens.
  • Page 58: Notes

    Notes...
  • Page 59 ISOKERN is not responsible for misuse or mishandling of components. Nothing in this warranty makes ISOKERN, or any division thereof, liable in any respect for any injury or damage to the building or struc- ture in which the fireplace or chimney system has been installed or to persons or property therein arising out of the use, misuse, or installation of properly manufactured ISOKERN product.