Data-Tronix DT-UPS-1000-SMOL Owner's Manual

Datatronix on-line smart ups system

Advertisement

Quick Links

DT-UPS-1000-SMOL
On-Line Smart UPS System
1

Advertisement

Table of Contents
loading

Summary of Contents for Data-Tronix DT-UPS-1000-SMOL

  • Page 1 DT-UPS-1000-SMOL On-Line Smart UPS System...
  • Page 2 Therefore, all users should read the form carefully and thoroughly. Symbol & Description Symbol Description Caution, danger Danger electric shock Alternating current (AC) Direct current (DC) Protective ground Recycle Do not dispose with ordinary trash For assistance, contact our DataTronix Technicians at: (610) 429-1511...
  • Page 3 1 Introduction 1. 2 Safety Instructions 1. Read this manual carefully and thoroughly before operation the UPS and save this manual properly for future reference. 2. Do not tear up or shatter the alarm table on the UPS and pay attention to it. 3.
  • Page 4: System Type And Configuration

    1 Introduction The UPS is an on-line uninterruptible power supply device incorporating double-converter technology with single-phase input and single-phase output. It offers the high quality power supply with the greatest degree of availability and reliability. The 1-3kVA of UPS is compact and convenient for users, especially for the basic equipments in some areas such as: finance, communication, government, traffic, manufacture, education and so on.
  • Page 5: Product Description

    2 Product Description 2. 2 The Appearance of the UPS Figure 2-1 The rear panel of 1K(S/L)、2K(S/L)、3K(S/L) * The picture for back panel is just for reference, it subjects to change on customer’s requirement, please refer to the real subject. Note: The appearances above are examples with the long backup time, the corresponding standard type is without the “External Battery slot”.
  • Page 6: Operating Principle

    2. 3 Operating Principle Figure 2-2 The UPS operating principle 2 Product Description 1. Input filter: it filters the input and provides clean AC power to the UPS. 2. AC/DC converter: In Normal mode, it converts the AC input power to regulated DC power, and raises the regulated DC voltage for DC/AC converter.
  • Page 7: Installation

    6. Charger: The charger of standard UPS provides 1A charging current; and long backup time provided 5.5A charging current. 7. Battery: Sealed maintenance-free lead –acid battery can be used as the DC source of the UPS. 8. Output filter: It filters the output and provides clean AC power to the load. 3 Installation 3.
  • Page 8 2. The UPS should not be placed on a side. The air inlet port at the front panel and the outlet port on the rear panel and two side panels should not be blocked so as to ensure good ventilation. 3.
  • Page 9 Figure 3-1 Connection Method of Input 2. Output cable connection The output of of the UPS is available to use on all sockets. The total output power shall not exceed 1kVA/0.9kW. Simply plug the load power cable to the output sockets of UPS to complete connection as shown in the following diagram.
  • Page 10 strictly complied with. 1. First connect in series the batteries of the pack to ensure proper battery voltage that 1KS/1KL for 36VDC. 2. Take out the battery cable delivered with the UPS, one end of the external battery cable is a plug for connecting the UPS, the other end has 3 open wires for connecting the battery pack.
  • Page 11 1. Computer interface Computer interface: The type of signals is provided by the UPS to communicate with host computer through communication cable included in the standard accessory, User can use special monitor software UPSilon in the standard accessory to monitor the UPS through the port. 3 Installation 2.
  • Page 12 4 Operation (LED model) 4. 1 Introduction of Display Panel 1. ON button: Pressing the ON button more than 1 second, the UPS system is turned on. 2. OFF button: By pressing this button more than 1 second turns off the UPS system whenever the UPS run under the normal mode/battery mode.
  • Page 13: Operation Mode

    4 Operation (LED model) Table 4-1 Description of indicators Color Indicator Description When the indicator on, it shows that the Fault indicator UPS in abnormal condition. Orange Load/battery capacity indicator Show the capacity of load/battery: 1.Indicate the percentage of the load Green Load/battery capacity indicator capacity in normal mode and bypass...
  • Page 14 4 Operation (LED model) of the utility power is out of the normal input range of the UPS. The UPS works in battery mode. Figure 4-2 Normal Mode 2. If output overloaded, the load level indicators will be turned on and alarm will beep every second.
  • Page 15 4 Operation (LED model) It recommended that the capacity of the AC generator chosen should double that of the UPS. 4.2.2 Battery mode In battery mode the display on the front panel is shown in the following diagram. The battery indicator and the inverter indicator are turned on. If the utility power indicator blinks at the same time, it shows that the utility power is abnormal.
  • Page 16 4 Operation (LED model) 4.2.3 Bypass mode When operating in bypass mode set up through UPSilon software, the display on the front panel is show in the following diagram. The utility power indicator and the bypass indicator are turn on. The load/battery capacity indicator will be turned on in accordance with the load capacity connected.
  • Page 17: Operating Instructions

    4 Operation (LED model) 4. 3 Operating Instructions 4.3.1 Turning On and Completely Powering Down the UPS Note: The battery is fully charged before delivery. However, storage and transportation will inevitably cause some charge loss. Therefore, it is advisable to charge the battery for 10 hours before using it, so as to ensure adequate battery capacity.
  • Page 18 4 Operation (LED model) bypass indicator will be turn on to indicate that the UPS is working in bypass mode. In order to cut off the output from the UPS, simply cut off the utility power supply. Finally, not any display is shown on the front panel and no output is available from the UPS outlets, system completely power down.
  • Page 19 4 Operation (LED model) 2) Press the 'F' and 'OFF' button more than one second, then release, the buzzer will beep once, and the bypass indicator with battery indicators will flash once every second, which means all of bottom are used for UPS setting. At this point, if the voltage setting is enabled(the Inverter indicator is lit), the No of lighted load led indicator represents current setting value of output voltage, and if the frequency setting is enabled (inverter lights flash), the...
  • Page 20 4 Operation (LED model) The relation of the No of lighted load led and voltage/ frequency as follows Note: L1 ~ L4 are the green lights, L5 is the yellow light, L6 is the red light 4.3.3 Audible alarm and LED indication of UPS operating status and faults LED indicators Operating status...
  • Page 21 4 Operation (LED model) LED indicators Operating status Audible alarm ↑ ↑ ↑ ↑ ● ↑ ★ ↑ ↑ ↑ Utility power abnormal Overload in Battery mode, Beep once ● ● ● ● pre-alarm every sec Overloaded Normal Beep once ●...
  • Page 22 5 Operation (LCD model) 5.1 Operation Display Panel 1. ON button: Pressing the ON button more than 1 second (buzzer beeps once), the UPS system is turned on. 2. OFF button: By pressing this button more than 1 second (buzzer beeps once) turns off the UPS system whenever the UPS run under the normal mode/battery mode.
  • Page 23: Operation (Lcd Model)

    5 Operation (LCD model) c) LCD display screen switch Pressing the function button for more than 1 seconds and less than 2 seconds (buzzer beeps once) to switch LCD display screen 4. LED indicators The LED indicators contains, Bypass indicator, utility power indicator, Inverter indicator, Battery indicator.
  • Page 24 5 Operation (LCD model) time, it shows that the voltage or frequency of the utility power is out of the normal input range of the UPS. The UPS works in battery mode. Figure 5-2 Normal Mode 2) If load is more than 100 percent, the buzzer beeps every second, meanwhile, the warning icon blinks every second too, reminding that UPS is overloaded.
  • Page 25 5 Operation (LCD model) UPS is in idle mode). Then, turn on the UPS according to the startup procedure. After the UPS is turned on, the loads are connected one by one. It recommended that the capacity of the AC generator chosen should double that of the UPS.
  • Page 26 5 Operation (LCD model) 3) The other four display pages are load percent page, actual load page, battery information page and the maximum temperature page. 5.2.3 Bypass Mode When operating in bypass mode set up through UPSilon software, the display on the front panel is shown as the figure 5-4, the utility power indicator and the bypass indicator are turned on.
  • Page 27 5 Operation (LCD model) Figure 5-4 Bypass Mode 5.2.4 LCD indication of UPS alarm status and faults In the event of an UPS fault, UPS enters fault operation mode, at this point, the fault icon turns on consistently, the buzzer beeps continuously and the data information area shows current fault code (refer to table 7-2), the display on the front panel is shown as the figure 5-5, users can switch to output page by pressing function button.
  • Page 28 5 Operation (LCD model) Figure 5-6 Alarm display 5.3 Operating Instructions 5.3.1 UPS ON/OFF Operation Note: The battery is fully charged before delivery. However, storage and transportation will inevitably cause some charge loss. Therefore, it is advisable to charge the battery for 10 hours before using it, so as to ensure adequate battery capacity.
  • Page 29 5 Operation (LCD model) self-diagnosis (all the LCD indicators are turn on about 4 seconds). A few seconds later, the battery indicator, inverter indicators will be turn on to indicate that the UPS is working in battery mode. 2. Powering down the UPS The operation of powering down the UPS contains: turning off ups in normal mode, turning off ups in battery mode 1) Completely power down the UPS from Normal mode...
  • Page 30 5 Operation (LCD model) default. In the event of a battery fault during battery self-diagnosis, the UPS will transfer to normal mode automatically. 2. Through the monitor software Users can also initiate battery self-diagnosis through the background monitoring software. 5.3.3 Setting the output voltage and frequency 1) Connect the mains input to the UPS, and make the UPS works in standby mode or bypass mode.
  • Page 31: Battery Maintenance

    6 Maintenance 6.1 Battery Maintenance The battery is key component of the UPS. The battery life depends on the ambient temperature, charging and discharging times. High ambient temperature and deep discharging will shorten the battery life. 1. Sealed maintenance-free lead –acid battery be used in the standard. When being connected to the utility power whether the UPS has been turned on or not, the UPS keeps charging the battery and also offers the protective function of charging and discharging.
  • Page 32: Maintenance

    6 Maintenance 6. 2 Checking UPS function Every time when conducting field maintenance, please check the regular function of the UPS, including: 1. Check the operation status of the UPS If the main voltage is within the specifications, the UPS should operate in normal mode;...
  • Page 33: Troubleshooting

    7 Troubleshooting In the event of an UPS fault, shoot the trouble according to Table 7-1 or Table 7-2. If the fault still persists, please contact our customer service center. Problem Possible Solution cause LED display Alarm Ensure that the UPS is not overloaded and the ventilation opening is not blocked and ambient The 1# Fault...
  • Page 34 7 Troubleshooting Problem Possible cause Solution LED display Alarm The 1# fault LED is on. Beep once The charger of Please contact the distributor or every Service center battery LED second defective is blinks Maybe reversed polarity (L,N) of Please check the polarity of the site wiring neutral wiring and the line wiring,...
  • Page 35 7 Troubleshooting Faults Possible Solution Fault/Warning cause Fault icon Alarm code Beep Internal Please contact constantly continuously fault. distributor or Service center Beep Internal Please contact constantly continuously fault. distributor or Service center Beep Internal Please contact constantly continuously fault. distributor or Service center Turn off the UPS.
  • Page 36 7 Troubleshooting Faults Possible cause Solution Fault/Warning Fault icon Alarm code The UPS output will Blink once Beep once Battery voltage be cut off, please every every second switch to the backup second power. Blink once Check the battery of Beep once UPS power on every...
  • Page 37: Specifications

    8 Specifications 8. 1 Electrical Model 1KS/1KL 2KS/2KL 3KS/3KL Rating 1KVA/900W 2KVA/1800W 3KVA/2700W Input system Single phase & earth ground Voltage range (60±5)VAC~(138±5)VAC Input ≥0.99 Power factor Voltage range of bypass (40±5)VAC~(133±5)VAC Output system Single phase & earth ground ① Rated voltage 110VAC Power factor...
  • Page 38 8 Specifications 8. 2 Mechanical Model L*W*H (mm) Weight (kg) 450x482.6x88 450x482.6x88 450x482.6x88 1KS/1KL 450x482.6x88 2KS/2KL 450x482.6x88 3KS/3KL 450x482.6x88 10.5 8. 3 Environmental Item Normal range Ambient temperature 0℃~40℃ Environment humidity 20%~90%(No condensation) Lower than 1000m: no derating Altitude Over 1000m :1% derating for every 100m rise Storage temperature -15℃~45℃...
  • Page 39 Serial communication cable DATATRONIX 1-Year Limited Warranty DATATRONIX. (the "Company") warrants to the Original Purchaser that the item purchased is free from defects in workmanship or material under normal use. This warranty starts on the date of shipment of the hardware to the Original Purchaser.
  • Page 40 for the hardware shall remain with the Original Purchaser until such time as Company takes receipt of the hardware. Upon receipt, the Company will promptly repair or replace the defective unit, and then return said unit to Original Purchaser, shipping prepaid. The Company may use reconditioned or like-new parts or units, at its sole option, when repairing any hardware.
  • Page 41 Company or its agent has been advised of the possibility of such damages, or for any claim brought against your by another party. Jurisdictions vary with regard to the enforceability of provisions excluding or limiting liability for incidental or consequential damages. You should check the laws of your local jurisdiction to find out whether the above exclusion applies to you.