CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 1 Functions Remote Control Transmitter AUTO SPEED HEAT COOL ON OFF TEMP OFF/ON MODE SLEEP FAN SPEED AUTO TIMER AIR SWING OFF/ON SET/C MANUAL RESET Remote Control SLEEP Operation START/STOP Sleep Mode Auto-Control...
Page 3
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 Indoor Unit Sensing The Room Temperature Hot-start Control (Heating) Room Temperature Sensor (thermistor) The indoor fan stops until the Evaporator piping temperature will be reached. Starting Current Control Automatic Restarting Control Indoor Fan is delayed for 1.6 seconds at the...
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 Outdoor Unit Anti-freezing Control For The Overload Protector Evaporator Compressor will be stopped when the Evaporator’s piping temperature is 0°C or 30 sec. Forced Operation Control less for three minutes Restarting at 12°C or higher (Time Delay...
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 7 Operation Details 7.1. Cooling Mode Operation When selecting the Cooling (COOL) Mode Operation, the unit will operate according to the setting by the Remote Control and the operation is as the following.
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 7.3. Detail of Sleep Mode Sleep Mode operates to match your sleeping condition. 1. At Cooling or Soft Dry operation When you set the Sleep Mode (SLEEP), the following movement will start to avoid overcooling.
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 7.5. Deice control • Deicing operation is controlled by sensing the indoor piping temperature and timer. • Deicing starts when 60 minutes after start of heating or deice ends and if the indoor piping temperature is 46° (°C) or lower.
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 8 Operating Instructions SAFETY PRECAUTIONS Operation Precautions Installation Precautions Before operating, please read the following “Safety Precautions” carefully. Warning Warning To prevent personal injury, injury to others and This sign warns of death or serious injury.
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 How to Insert the Batteries NAME OF EACH PART 1 Signal Transmitter Remote Control 2 Operation Display Cooling Model AUTO AUTO SPEED SPEED COOL COOL Gently press the place marked OPEN and slide...
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 Setting the Fan Speed Setting the Horizontal Airflow Direction Operation Details • Press 4 to select:- – Low Fan Speed COOL – Cooling Operation – Medium Fan Speed • To set the room temperature at your preference –...
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 HELPFUL INFORMATION ENERGY SAVING AND OPERATION Pre-season Inspection HINTS Clean the air filters, re-insert and operate the air Auto Operation conditioners. Setting the Temperature • Approximately 10% of electricity can be saved.
Page 26
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect. 2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.
Page 27
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 Installation Parts Provided Installation parts you should purchase* 1. Suspension bolts (M10 × 600...4 pcs.) 1. *Bushing-sleeve 2. Nut, washer (M10...16 pcs.) 2. *Sleeve 3. Spring washer (M10...8 pcs) 3. *Putty (Gum type sealer) 4.
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 9.2. INDOOR UNIT 9.2.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section) 9.2.2. HOW TO FIX INSTALLATION PLATE Installation on the ceiling Installation on the wall • Measure and mark the position for the Suspension bolts •...
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 Installation on the floor 9.2.4. INDOOR UNIT INSTALLATION • Measure and mark the position for the floor brackets and the Piping hole. • Drill the hole for the anchor nut. Indoor unit installation •...
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 (ii) Secure the Indoor unit onto the Installation bracket with 9.2.5. CONNECT THE CABLE TO THE four M8 bolts with washer. INDOOR UNIT • Engage the lower flange of the hanging bracket on the 1.
Page 31
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 2. For the Left Side Piping. 5. For the Left Bottom or Right Bottom Piping. <For the Left Rear or Right Rear Piping of Ceiling or Attach the Edge Protector onto the edge of the Knock- Wall Mounting>...
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 9.3. OUTDOOR UNIT 9.3.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section) 9.3.2. INSTALL THE OUTDOOR UNIT At the best location, start installation according to Connecting The Piping To Outdoor Unit Indoor/Outdoor Unit Installation Diagram.
Page 33
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 9.3.4. (a) EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION) WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.
Page 34
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 2) Air Purging The air which contains a moisture is remaining in the Refrigeration cycle may cause a malfunction on the Compressor. 1. To purge the air, push the pin on the Gas side 3-way valve for three seconds using with a Hexagonal wrench and set it free for one minute.
Page 35
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 In case of the Outdoor unit is installed upper position of the indoor unit. 1. Tape the Pipings, and Connecting cable from down to up. 2. From the pipings gathered by taping along the exterior wall and the trap is required to prevent water from entering the room.
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 10 Servicing Information Pump-Down Terminal • The thermostat will be switched ON (even if the room temperature is low) when the pump-down terminal is short-circuited (by using) alligator-type clips or a similar method), thus permitting easy pump-down when the unit is to be moved to another place.
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 11 Troubleshooting Guide 11.1. Refrigeration cycle system In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.
Page 38
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 11.1.1. Relationship between the condition of the air conditioner and pressure and electric current Cooling Mode Heating Mode Condition of the air conditoner Low Pressure High Pressure Electric current Low Pressure High Pressure...
Page 52
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 SCHEMATIC DIAGRAM 3/3 DISPLAY (XH-4) (XH-4) BLUE BLUE CN-DISP CN-DISP OPERATION ORANGE TIMER Heat Exchanger Temp. AUTO Intake Air Sensor DISCHARGE AIR TEMP SENSOR 510.0K CST4.0OMGT STEPPING MOTOR M54588P MA165 TA-5 STEPPING MOTOR...
Page 53
CS-A12ATP5 CU-A12ATP5 / CS-A18ATP5 CU-A18ATPT5 / CS-A24ATP5 CU-A24ATPT5 How to use electronic circuit diagram TIMER TABLE Test Mode Name Time (When test point Remarks Short-circuited) Time Delay Safety Control 2 min. 58 sec. 0 sec. Circuit Protection Control 30 sec.