Troubleshooting; Before Troubleshooting; Check Control Module Fuses - Crest Audio FBN0751 Service Manual

Crest models 751-2001 condensing boilers service manual
Table of Contents

Advertisement

3

Troubleshooting

Label all wires prior to disconnection
WARNING
when servicing controls.
errors can cause improper and
dangerous operation.
disconnect power to the boiler
before servicing. Failure to comply
could result in severe personal
injury,
property damage.
Never jumper (bypass) any device
WARNING
except for momentary testing as
outlined in the Troubleshooting
chart. Severe personal injury, death,
or substantial property damage can
result.

Before troubleshooting:

1. Have the following items:
a.
Voltmeter that can check 120 vac, 24 vac, and
12 vdc.
b. Continuity checker.
c.
Contact thermometer.
2. Check for 120 vac (minimum 102 vac to maximum
132 vac) to boiler.
3. Make sure thermostat is calling for heat and contacts
are closed. Check for 24 vac between enable input
and ground.
4. Make sure all external limit controls are installed
and operating.
Check the following:
1. Wire connectors to control module are securely
plugged in at the module and originating control.
2. Gas pressures:
• Maximum: 14 inches w.c. (3.5 kPa) (natural and
LP) with no flow (lockup) or with boiler on
• Minimum: 4 inches w.c. (1.0 kPa) (natural and
LP), with gas flowing (verify during boiler
startup)
Wiring
Always
death,
or
substantial

Check control module fuses

ALWAYS check control module fuses before
NOTICE
replacing control module or any major
components (blower, etc.). If one of these fuses
is blown, it can prevent the control module or
other components from operating.
1.
Turn OFF the power to the boiler at the external line
switch.
2.
Remove the upper and lower doors.
3.
Remove the four (4) screws securing the control panel cover to
the unit to gain access to the control module.
4.
Inspect fuses F2, F4, and F5, see FIG 3-1 below.
Figure 3-1 Control Module Fuses
F2 - 3.15 AMP
BLOWER RELAYS
F4 - 5 AMP
PUMP RELAYS
F5 - 5 AMP
IGNITOR OUTPUT
F6 - 5 AMP
NOT USED
(SPARE)
5. The boiler is shipped with four (4) spare fuses in a plastic bag
located inside the control panel.
6. If necessary, replace open fuse (F2 is 3.15 amps, F4, F5 and F6
are 5 amps each).
Note: Fuses F2, F4, F5 and F6 are all slow blow fuses.
Do not jumper fuse or replace with any fuse
WARNING
except as specified. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
7. Re-install the control panel cover using the four (4) screws
removed in Step 3. Re-install the upper and lower doors after
fuse inspection.
8. Restore power to the boiler at the external line switch and verify
boiler operation (Section 9 - Start-up in the Crest Installation
and Operation Manual) after completing boiler service.
Service Manual
37