EF18/22/25/35/42/50VE2W - , MSZ- EF18/22/25/35/42/50VE2B - SPLIT-TYPE AIR CONDITIONERS MSZ-EF18/22/25/35/42/50VE2S - have been modified. Please void OBH589 REVISED EDITION-C. INDOOR UNIT No. OBH589 SERVICE MANUAL REVISED EDITION-D Models MSZ-EF18VEW MSZ-EF22VEW MSZ-EF25VEW MSZ-EF35VEW MSZ-EF42VEW MSZ-EF50VEW MSZ-EF18VEB MSZ-EF22VEB MSZ-EF25VEB MSZ-EF35VEB MSZ-EF42VEB MSZ-EF50VEB...
Page 2
Revision A: • Airflow in the Silent mode in the cooling operation has been changed. • "TROUBLESHOOTING" has been corrected (10-2, 10-4). Revision B: • MSZ-EF18VEW - , MSZ-EF18VEB - and MSZ-EF18VES - have been added. Revision C: •...
The following models may be connected to the MUZ-EF·VE(H) series after once connected to the MXZ series and operated, for example because of relocation. In that case, the MUZ-EF·VE(H) series outdoor units will not operate without taking a step. Follow the procedure "Deleting the memorized abnormal condition" described in 10-2.1. MSZ-EF18VEW - MSZ-EF22VEW - MSZ-EF25VEW -...
NOISE CRITERIA CURVES MSZ-EF18VEW MSZ-EF22VEW MSZ-EF25VEW MSZ-EF35VEW MSZ-EF18VEB MSZ-EF22VEB MSZ-EF25VEB MSZ-EF35VEB MSZ-EF18VES MSZ-EF22VES MSZ-EF25VES MSZ-EF35VES MSZ-EF18VE2W MSZ-EF22VE2W MSZ-EF25VE2W MSZ-EF35VE2W MSZ-EF18VE2B MSZ-EF22VE2B MSZ-EF25VE2B MSZ-EF35VE2B MSZ-EF18VE2S MSZ-EF22VE2S MSZ-EF25VE2S MSZ-EF35VE2S FAN SPEED FUNCTION SPL(dB(A)) LINE FAN SPEED FUNCTION SPL(dB(A)) LINE COOLING COOLING Super High...
Page 9
MSZ-EF42VEW MSZ-EF50VEW MSZ-EF42VEB MSZ-EF50VEB MSZ-EF42VES MSZ-EF50VES MSZ-EF42VE2W MSZ-EF50VE2W MSZ-EF42VE2B MSZ-EF50VE2B MSZ-EF42VE2S MSZ-EF50VE2S FAN SPEED FUNCTION SPL(dB(A)) LINE FAN SPEED FUNCTION SPL(dB(A)) LINE COOLING COOLING Super High Super High HEATING HEATING NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 NC-20 NC-20 NC-10...
SERVICE FUNCTIONS MSZ-EF18VEW MSZ-EF22VEW MSZ-EF25VEW MSZ-EF35VEW MSZ-EF42VEW MSZ-EF50VEW MSZ-EF18VEB MSZ-EF22VEB MSZ-EF25VEB MSZ-EF35VEB MSZ-EF42VEB MSZ-EF50VEB MSZ-EF18VES MSZ-EF22VES MSZ-EF25VES MSZ-EF35VES MSZ-EF42VES MSZ-EF50VES MSZ-EF18VE2W MSZ-EF22VE2W MSZ-EF25VE2W MSZ-EF35VE2W MSZ-EF42VE2W MSZ-EF50VE2W MSZ-EF18VE2B MSZ-EF22VE2B MSZ-EF25VE2B MSZ-EF35VE2B MSZ-EF42VE2B MSZ-EF50VE2B MSZ-EF18VE2S MSZ-EF22VE2S MSZ-EF25VE2S MSZ-EF35VE2S MSZ-EF42VE2S MSZ-EF50VE2S 8-1. TIMER SHORT MODE For service, the following set time can be shortened by bridging JPG and JPS on the electronic control P.C.
8-3. HOW TO SET REMOTE CONTROLLER EXCLUSIVELY FOR A PARTICULAR INDOOR UNIT (MSZ-EF•VE2W/B/S) A maximum of 4 indoor units with wireless remote controllers can be used in a room. To operate the indoor units individually with each remote controller, assign a number to each remote controller according to the number of the indoor unit.
9-1. COOL ( ) OPERATION (1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons TEMP button to select the desired temperature. The setting range is 16 - 31°C. 1.
NOTE 2 FOR MULTI SYSTEM AIR CONDITIONER OUTDOOR UNIT: MXZ series Multi system air conditioner can connect two or more indoor units with one outdoor unit. • When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the others for heating, the operation mode of the indoor unit that operates first is selected.
(9) ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher by micro- processor. However, the temperature on the LCD screen on the remote controller is not changed. Also the horizontal vane swings in various cycle.
9-8. WEEKLY TIMER OPERATION • A maximum of 4 ON or OFF timers can be set for individual days of the week. • A maximum of 28 ON or OFF timers can be set for a week. NOTE: The simple ON/OFF timer setting is available while the weekly timer is on. In this case, the ON/OFF timer has priority over the •...
(4) Press button to complete and transmit the weekly timer setting. which was blink- ing goes out, and the current time will be displayed. NOTE: • Press button to transmit the setting information of weekly timer to the indoor unit. Point the remote controller toward the indoor unit for 3 seconds.
9-10. EMERGENCY/TEST OPERATION In the case of test run operation or emergency operation, use Operation mode COOL/HEAT EMERGENCY OPERATION switch on the right side of the indoor unit. Set temperature 24°C Emergency operation is available when the remote controller is missing Fan speed Med.
Page 25
10-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-4.) disappears, the memorized failure details can be recalled. 1.
Page 26
2. Indoor unit failure mode table The left lamp of Abnormal point OPERATION INDI- Condition Remedy (Failure mode) CATOR lamp Not lighted Normal — — The room temperature thermistor short or 1-time fl ash every Room temperature Refer to the characteristics of the room temperature open circuit is detected every 8 seconds dur- 0.5-second thermistor...
Page 27
10-3. INSTRUCTION OF TROUBLESHOOTING Start Indoor unit operates. Indoor unit oper- Indoor unit does OPERATION INDICATOR Outdoor unit does not receive the ates. lamp on the indoor unit is not operate normally. signal from re- Outdoor unit fl ashing ON and OFF. does not operate.
Page 28
10-4. TROUBLESHOOTING CHECK TABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes. OPERATION INDICATOR Lighted Blinking...
10-6. TROUBLESHOOTING FLOW A Check of indoor fan motor The indoor fan motor error has occurred, and the indoor fan does not operate. Turn OFF the power supply. Pay enough attention to the high voltage on the fan motor connector CN211. Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch.
Page 31
B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner. Press OPERATE/STOP (ON/OFF) button on the remote controller. 1 Look at the image of the signal transmitting section of the remote controller through the monitor of a digital camera or a camera phone.
Page 32
C Check of indoor P.C. board and indoor fan motor Turn OFF the power supply. Remove indoor fan motor connector CN211 from indoor power P.C. board and vane Measure the resistance of indoor fan Short circuit: motor connector CN151 from the indoor motor.
Page 33
D How to check miswiring and serial signal error MUZ-EF Type Turn the main power supply OFF. Is there rated voltage in the power supply? Check the power supply. Check for incorrect indoor-outdoor connecting wiring. Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)? The connection information to the Multi series is stored...
Page 34
MXZ Type Turn OFF the power supply. Is there rated voltage in the power supply? Check the power supply. Turn ON the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Check the wiring. Press EMERGENCY OPERATION switch once. Does the left lamp of OPERATION INDICATOR lamp light up? <Confi...
Page 35
E Electromagnetic noise enters into TV sets or radios Is the unit earthed? Earth the unit. Is the distance between the antennas Extend the distance between the antennas and and the indoor unit within 3 m, or is the the indoor unit, and/or the antennas and the distance between the antennas and the outdoor unit.
Page 36
10-7. TEST POINT DIAGRAM AND VOLTAGE Indoor power P.C. board, Indoor electronic control P.C. board, Receiver board, Display board, Switch board MSZ-EF18VEW MSZ-EF22VEW MSZ-EF25VEW MSZ-EF35VEW MSZ-EF42VEW MSZ-EF50VEW MSZ-EF18VEB MSZ-EF22VEB MSZ-EF25VEB MSZ-EF35VEB MSZ-EF42VEB MSZ-EF50VEB MSZ-EF18VES MSZ-EF22VES MSZ-EF25VES MSZ-EF35VES MSZ-EF42VES MSZ-EF50VES Fuse (F11)
Page 37
MSZ-EF18VE2W MSZ-EF22VE2W MSZ-EF25VE2W MSZ-EF35VE2W MSZ-EF42VE2W MSZ-EF50VE2W MSZ-EF18VE2B MSZ-EF22VE2B MSZ-EF25VE2B MSZ-EF35VE2B MSZ-EF42VE2B MSZ-EF50VE2B MSZ-EF18VE2S MSZ-EF22VE2S MSZ-EF25VE2S MSZ-EF35VE2S MSZ-EF42VE2S MSZ-EF50VE2S Fuse (F11) Varistor (NR11) Indoor fan motor Indoor power P.C. board (CN211) Connector to terminal 325 VDC block (CN201) (–) GND (high- voltage DC) 15 VDC (+)3-6 VDC...
Page 39
OPERATING PROCEDURE PHOTOS 2. Remove the indoor electrical box Photo 2 Electrical box Earth wire (1) Remove the panel (Refer to 1.) and the corner box right. (2) Remove the screw of the V.A. clamp. Remove the V.A. clamp and the indoor/outdoor connecting wire.
Page 40
OPERATING PROCEDURE PHOTOS 4. Removing the nozzle assembly Photo 4 (1) Remove the panel (Refer to 1.) and the corner box right. (2) Remove the indoor/outdoor connecting wire (Refer to 2.). (3) Remove the electrical cover (Refer to 2.). (4) Disconnect the following connector: <Indoor electronic control P.C.
Page 41
OPERATING PROCEDURE PHOTOS 6. Removing the indoor fan motor, the indoor coil Photo 5 Lead wire of thermistor and the line flow fan the indoor coil thermistor (1) Remove the panel (Refer to 1.) and the corner box right. (2) Remove the indoor electronic control P.C. board holder, the electrical box and the nozzle assembly.