HELVAR SCENESET HES91010 Installation Instructions page 2

Lighting controller

Advertisement

MAINS SUPPLY INPUT
Voltage Range
The S
S
Lighting Controller is factory-set for use with one of the
CENE
ET
following voltage ranges which cannot be changed by the user:
·
230V a.c. (nominal); 180V – 260V a.c. (absolute).
·
115V a.c. (nominal); 90V – 130V a.c. (absolute).
Check that the controller is set for the correct range for the intended power
supply by referring to the serial no./rating plate which is mounted inside
the control connection compartment (behind the right-hand access plate).
WARNING: THE MAINS INPUT MUST BE CONNECTED TO A
SINGLE-PHASE SUPPLY ONLY AND MUST BE EARTHED.
CAUTION: Connecting a supply which exceeds the maximum voltage for the
appropriate input range may cause irreparable damage to the S
Frequency Range
The input supply frequency should be within the range 45 – 65Hz.
Supply Protection
The supply input is protected by the internal 3A MCB. No further
external supply protection is required.
Connecting the Mains Supply
Access to the mains input terminals is gained by removing the access
plate (four-screw fixing).
Cable Function
Connection Point
Live Input
Bottom screw terminal of the MCB
Neutral
Cream coloured screw-terminal block.
Earth
Green/Yellow coloured screw-terminal block.
Suitable cable type:
Cable size:
Stripping length:
Fig.1-3: Mains connection terminals
Document Ref. EPD05113
page 2
Solid, stranded or flexible.
2
2
1.5mm
– 4.0mm
.
12mm (for MCB)
10mm (for other terminals).
EARTH
NEUTRAL
LIVE
(22/07/03)
BREAKOUT MODULE
The B
REAKOUT
right-hand side) and provides connection points to the various FELV
(Functional Extra-Low Voltage) data and control circuits (see Fig.1-4.).
·
S-COM (external) power & data highway.
·
S-COM (star) data highway.
·
S-COM (internal) data highway.
·
S-DIM data highways.
·
S
S
CENE
·
B
REAKOUT
·
D
IMMER
These allow the connection of various external control input or output
devices and enable separate S
connector and its function are given in the User Guide.
S
.
CENE
ET
LEVEL
CN10
Fig.1-4: Location of B
Suitable Cable
All of the S-COM and S-DIM data highways require a screened twisted
pair, whilst all other connections should use equipment wire. For full
details, refer to the Electrosonic Control Cable Specifications data sheet
(part no. I237GB).
Special S-COM cable is available from Helvar Electrosonic which
comprises the following conductors in an overall sleeve:
·
Twisted pair with screen (for data lines).
·
Two power wires (for S-COM supply).
This is ideally suited for use with the S-COM (external) line, but may also
be used on the other S-COM and S-DIM lines if the two power wires are
cut back.
Configuration Switches
A bank of eight DIL slide switches is provided on the module which are
used for the following purposes (from left to right):
·
Switches 1 – 3
S
S
CENE
ET
·
Switches 4 – 8
All of the configuration switches are factory-set to the 'ON' (up) position,
but these can be changed if required.
ENGLISH
module is located behind the access plate (on the
watchdog relay contacts.
ET
module relay coil and contacts.
level override input.
S
s to be linked. Full details of each
CENE
ET
RELAY
SCENESET
DIMMERS 1
STAR
TEMP
WATCHDOG
RELAY
SCENESET
DIMMERS 2
CONFIGURATION
LK1
SWITCHES
1
2
3
4
5
6
7
8
OFF
Module.
REAKOUT
To select different interconnections of the
watchdog and D
IMMER override circuits.
To select line termination on the various
data highways .
PANEL
PANEL
CN1
Part No. I259GB issue 6