Electric Fan Coil Thermostats
RAB10.1U Thermostat with
manual changeover.
Description
Designed to control 2- or 4-pipe fan coil or unit ventilators,
the RAB... Electric Fan Coil Thermostats are an attractive
and economical solution that utilize two-wire, gas
membrane technology.
Providing On/Off control, the RAB... Electric Fan Coil
Thermostats are available with dual scale Fahrenheit/
Celsius models with manual or external changeover.
The RAB20.1U requires an aqua sensor to initiate
changeover.
Features
• Fan Speed Switch (RAB90.1U) for remote switching
location (24...277 Vac)
• Two-point control algorithm for on/off control
• Line voltage
• 2-pipe or 4-pipe fan coil applications
• 3-speed fan control
• Fan on only models for ventilation
• Manual or external changeover
• Two mounting styles: electrical wall box or drywall
• Adjustable upper/lower limit stops
• Dual Fahrenheit/Celsius scale
RAB20.1U Thermostat with
exposed setpoint knob and
external changeover.
Applications
The RAB... Electric Fan Coil Thermostats are
recommended for applications in commercial or light
industrial buildings in conjunction with zone valves,
thermal valves, fans or thermostats.
Note:
ARG70, wall plate, is required for UL compliance in
switching line voltage.
RAB...
RAB30.1U Thermostat with
exposed setpoint knob and
3-speed fan control.
www.usa.siemens.com/hvaccomponents
RAB90.1U 3-speed
fan switch.
A-37

Advertisement

loading

Summary of Contents for Siemens RAB10.1U

  • Page 1 RAB… Electric Fan Coil Thermostats RAB10.1U Thermostat with RAB20.1U Thermostat with RAB30.1U Thermostat with RAB90.1U 3-speed manual changeover. exposed setpoint knob and exposed setpoint knob and fan switch. external changeover. 3-speed fan control. Description Applications A-37 Designed to control 2- or 4-pipe fan coil or unit ventilators, The RAB…...
  • Page 2 Part Nos. Description 3-speed Change- Vent- Electric Wall Application over ilation Control Switch Dry Wall 2-pipe Heating/Cooling/Ventilation Manual Heat/Cool/Vent RAB10.1UW RAB10.1U 2-pipe Heating/Cooling/Ventilation Auto Heat/Cool/Vent RAB20.1UW RAB20.1U A-38 4-pipe Heating/Cooling/Ventilation Manual Heat/Cool/Vent RAB30.1UW RAB30.1U — 3-speed Fan Switch — —...
  • Page 3 Dimensions RAB... Room Thermostat and Wall Plate for Mounting (RAB10.1U, RAB20.1U and RAB30.1U) A-39 RAB90.1U and Wall Plate for Mounting 3.39 (86) 1.18 1.18 (30) (30) 3.80 1.53 (96.4) (38.9) Wall Plate (ARG70) for Mounting 0.14 (3.6) 1.10 1.10 (28) (28) Dimensions shown in inches (mm).
  • Page 4: Engineering Drawings

    Engineering Drawings Wiring Diagrams RAB10.1U... RAB20.1U... RAB30.1U... G1 Control Output Fan Speed I Operating Voltage ZV Zone or Thermal Valve G2 Control Output Fan Speed II M1 3-speed Fan W/Y Control Output Actuator G3 Control Output Fan Speed III Neutral...
  • Page 5 • Dual setpoint temperature scale. • Control depending on the room or return air temperature (remote sensing). • Automatic Heating/Cooling changeover. • Operating modes: Normal, Energy Saving, Frost Protection and Off. • Operating mode changeover input for remote control. • Selectable control parameters. www.usa.siemens.com/hvaccomponents...
  • Page 6: Base Plate

    RCC20U Dimensions RCC10U/20U Controller Baseplate 0.16 (4) 1.10 1.10 (28) (28) 0.16 1.38 1.10 (35) (28) 4.09 (104) 1.18 1.10 (30) (28) 0.16 (4) 0.46 (11.8) 1.02 1.18 (26) (30) 3.54 (90) Dimensions are shown in inches (mm). www.usa.siemens.com/hvaccomponents...
  • Page 7 (remote sensing) • Automatic Heating/Cooling changeover • Operating modes: Normal, Energy Saving, Freeze Protection and Off • Operating mode changeover input for remote control • Selectable control parameters • Free Energy Band between Heating and Cooling for energy conservation www.usa.siemens.com/hvaccomponents...
  • Page 8 Degree of Housing Protection ............ NEMA 1 Dead Zone in Normal Operation ......3.5 or 9°F (2 or 5°C) Shipping Weight ............... 0.5 lb (0.23 kg) A-44 Description Part No. Free Energy Band™ Four-pipe Fan Coil Controller RCC30U Accessories A-77 & Service Kits www.usa.siemens.com/hvaccomponents...
  • Page 9 (114.15) 3.80 1.88 (48) (96.6) A-45 Baseplate 0.16 (4) 1.10 1.10 (28) (28) 0.16 1.38 1.10 (35) (28) 4.09 (104) 1.18 1.10 (30) (28) 0.16 (4) 0.46 (11.8) 1.02 1.18 (26) (30) 3.54 (90) Dimensions shown in inches (mm). www.usa.siemens.com/hvaccomponents...
  • Page 10 A-46 TECH TIPS Check your order status quickly and easily via our secure Order Tracker feature. To take advantage of time-saving benefits, go online to www.usa.siemens.com/hvaccomponents, click on site360, and register today. www.usa.siemens.com/hvaccomponents...
  • Page 11 • Operating modes: Normal and OFF (RCU50.2U) • Active 0 to 10 Vdc input for setpoint shifting (RCU50U) • Operating mode changeover input for remote control (RCU50U) • Adjustable minimum limitation for cooling output (RCU50U) • Operating voltage 24 Vac www.usa.siemens.com/hvaccomponents...
  • Page 12: Device Combinations

    Device Combinations Description Part No. Remote Cable Temperature/Changeover Sensor QAH11.1 44 lb-in NSR Air Damper Actuator GDE16... 88 lb-in NSR Air Damper Actuator GLB16... Valve Actuator SSB61U Valve Actuator SSC61U SSC61.5U Valve Actuator SQS65U SQS65.5U www.usa.siemens.com/hvaccomponents...
  • Page 13 XpK Proportional band cooling Output percentage 0 to 100% minimum limitation of Room temperature setpoint cooling output XpH Proportional band heating Changeover RCU50.2U – Heating-Cooling Room temperature XpH Proportional band heating Output percentage XpK Proportional band cooling Room temperature setpoint Changeover www.usa.siemens.com/hvaccomponents...
  • Page 14 Dimensions RCU15/50… Controller A-50 RCU15/50… Baseplate Dimensions shown in inches. www.usa.siemens.com/hvaccomponents...
  • Page 15 • Adjustable minimum limitation for cooling output • Operating voltage 24 Vac • Ergonomic design • Dual Fahrenheit/Celsius scale Room Temperature Proportional Band Cooling Y2, Y10 Output Percentage 0 to 100% Minimum Limitation Room Temperature Setpoint of Cooling Output Proportional Band Heating www.usa.siemens.com/hvaccomponents...
  • Page 16 Insulation Against Live Voltage ............4 kV Maximum Number of Contacts per Panel .......... 50 Description Part No. A-52 Room Temperature Controller RCU61U Accessories A-77 & Service Kits Device Combinations Description Type Reference Valve Actuator SSA81 SSB61U SSB81 SSC81 Damper Actuator GLB16x GCA16x GBB16x GDE16x www.usa.siemens.com/hvaccomponents...
  • Page 17 Dimensions RCU61U Controller A-53 Baseplate Dimensions shown in inches. www.usa.siemens.com/hvaccomponents...
  • Page 18 A-54 TECH TIPS Check your order status quickly and easily via our secure Order Tracker feature. To take advantage of time-saving benefits, go online to www.usa.siemens.com/hvaccomponents, click on site360, and register today. www.usa.siemens.com/hvaccomponents...
  • Page 19 • Relay input for fan pump or other controls. • Minimum limitation of the supply air temperature. • Outputs are independently selectable direct acting (DA) or reverse acting (RA). • Adjustable proportional band. www.usa.siemens.com/hvaccomponents...
  • Page 20 Relay Input (Fan) 13, 20 ..............24 Vac Sensor Control Outputs 18, 19, Modulating, P or P + I Control Algorithm Sensing Element ....... Siemens-Ni 1000 Ω at 32°F (0°C) Voltage ............0 Vdc to 10 Vdc, Continuous Shipping Weight ............. 1.40 lb (0.64 kg) Current ................Maximum 1 mA...
  • Page 21 Engineering Drawings Function Diagrams RLA162.5U Room Temperature Controller A-57 RLA162.5U and RLM162U Room Temperature Controllers Room Temperature Controller (RLA162.5U) Air Duct Temperature Controller (RLM162U) — controls minimum or maximum limitation of discharge air Heating valve Cooling valve www.usa.siemens.com/hvaccomponents...
  • Page 22 Dimensions RLA162.5U Controller A-58 RLA162.5U Baseplate Dimensions shown in inches (mm). www.usa.siemens.com/hvaccomponents...
  • Page 23 • Adjustable minimum limitation for cooling output (RDU50U) • Optional selectable Direct Acting or Reverse Acting output (RDU50U and RDU50.2U) • Selectable display of room temperature or setpoint • Fahrenheit or Celsius selectable display • Minimum and maximum setpoint limitation • Operating voltage, 24 Vac www.usa.siemens.com/hvaccomponents...
  • Page 24 88 lb-in NSR Air Damper Actuators GLB131… Two-way Globe Zone Valves Powermite MZ Series Three-way Globe Zone Valves Powermite MZ Series Two-way Globe Zone Valves Powermite MT Series Three-way Globe Zone Valves Powermite MT Series Two-way Ball Valves Powermite 599 Series www.usa.siemens.com/hvaccomponents...
  • Page 25 Dimensions RDU...Controller 4.61 (117) 3.78 1.38 A-61 (96) (35) Baseplate 1.10 1.10 0.46 (28) (28) (11,8) 1.77 (45) 1.10 (28) 4.21 (107) 1.10 (28) 0.28 0.16 (4) 1.18 0.98 (30) (25) 3.54 (90) Dimensions shown in inches (mm). www.usa.siemens.com/hvaccomponents...
  • Page 26 A-62 TECH TIPS Visit us on the web at: www.usa.siemens.com/hvaccomponents, for printable product specification sheets on all products in this catalog. www.usa.siemens.com/hvaccomponents...
  • Page 27 • Room or return air temperature control • Switching a one-speed fan. • Manual heating/cooling changeover • Operating modes: Normal (heating, cooling), Energy Saving, Off • Operating mode changeover input for remote control • Selectable installation and control parameters • Operating voltage 24 Vac www.usa.siemens.com/hvaccomponents...
  • Page 28 Cooling output NO contact for compressor Heating output NC contact Heating output NC contact for reversing valve Heating output NO contact Heating output NO contact for compressor Note: Outputs 5 and 10 must be wired together for compressor control www.usa.siemens.com/hvaccomponents...
  • Page 29 Dimensions RDX... Controller 3.78 (96) 1.38 (35) A-65 Baseplate 1.10 1.10 0.46 (28) (28) (11,8) 1.77 (45) 1.10 (28) 4.21 (107) 1.10 (28) 0.28 0.16 (4) 1.18 0.98 (30) (25) 3.54 (90) Dimensions shown in inches (mm). www.usa.siemens.com/hvaccomponents...
  • Page 30 A-66 TECH TIPS Visit us on the web at: www.usa.siemens.com/hvaccomponents You can: • search for products by part number or description. • print out product information for submittals. • link to technical documentation. • locate a distributor near you. www.usa.siemens.com/hvaccomponents...
  • Page 31: All Models

    • Operating mode changeover input for remote control (Day/Night) • Air movement control function for avoiding damage resulting from moisture • Selectable installation and control parameters • Display of room temperature or setpoint (selectable) • Electronic minimum and maximum setpoint limits • Operating voltage 24 Vac www.usa.siemens.com/hvaccomponents...
  • Page 32 Temperature Sensor RDF10U, RDF20U, RDF50.1U, RDF60.1U QAH11.1 Two-way and Three-way Zone Valves RDF10U, RDF20U, RDF50.1U, RDF60.1U 599 Series Zone Valve Actuator RDF10U, RDF20U SF Series Zone Valve Actuator RDF50.1U, RDF60.1U SSA61 Series Zone Valve Actuator RDF50.1U, RDF60.1U SSB61U Series www.usa.siemens.com/hvaccomponents...
  • Page 33 Dimensions RDF... Controller 3.78 (96) 1.38 (35) A-69 Baseplate 1.10 1.10 0.46 (28) (28) (11,8) 1.77 (45) 1.10 (28) 4.21 (107) 1.10 (28) 0.28 0.16 (4) 1.18 0.98 (30) (25) 3.54 (90) Dimensions shown in inches (mm). www.usa.siemens.com/hvaccomponents...
  • Page 34 A-70 TECH TIPS Check your order status quickly and easily via our secure Order Tracker feature. To take advantage of time-saving benefits, go online to www.usa.siemens.com/hvaccomponents, click on site360, and register today. www.usa.siemens.com/hvaccomponents...
  • Page 35 This thermostat can also be used as a high limit control for • Adjustable high temperature limit stop a warm air system when a “lockout” type control is desired or required by code. • Manual reset to close contacts Typical Connections Typical High Limit Wiring. Typical Changeover Wiring. www.usa.siemens.com/hvaccomponents...
  • Page 36 Specifi cations/Product Ordering Part No. 141-0522 Part No. 141-0530 Setpoint Range ..........50 to 150°F (10 to 65°C) Setpoint Range ..........25 to 215°F (-4 to +102°C) Maximum Bulb Temperature ..........240°F (116°C) Switch Action ............SPST, open-on-rise Switch Action .................. SPDT Factory Temperature Setting ..........
  • Page 37 Red to Blue Red to Yellow closes on temp. opens on temp. decrease below decrease below set point. set point. OPEN ON RISE CLOSE ON RISE www.usa.siemens.com/hvaccomponents...
  • Page 38 Specifi cations/Product Ordering Part No. 134-1504 Part No. 134-1511 Dimensions ............4" W x 3.25" H x 2.5" D Dimensions ..........2.31" W x 3.19" H x 2.31" D (102 mm W x 83 mm H x 65 mm D) (59 mm W x 81 mm H x 59 mm D) Shipping Weight ...............