Hewalex PCWU 200K-2.3kW Instruction Manual

Hewalex PCWU 200K-2.3kW Instruction Manual

Heat pump water heater

Advertisement

Instruction manual

Heat pump
water heater
PCWU 200K-2.3kW
PCWU 300SK-2.3kW
Contents
1. Safety rules for installation.......................................................................................
2. Warranty terms........................................................................................................
3. Recycling and utilization...........................................................................................
4. Environmental requirements ...................................................................................
1. General ....................................................................................................................
2. Cost saving...............................................................................................................
3. Heat pump structure ...............................................................................................
4. Controller instruction ..............................................................................................
4.1 Driver map .........................................................................................................
4.2 To start the heat pump ......................................................................................
4.3 Parameter settings .............................................................................................
4.4 Controller settings ...........................................................................................
4.5 Measured parameters .....................................................................................
4.6 Info ...................................................................................................................
5. Antilegionella..........................................................................................................
6. Equipment maintenance.........................................................................................
3
3
4
4
4
5
6
7
7
8
9
14
15
15
15
15

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PCWU 200K-2.3kW and is the answer not in the manual?

Questions and answers

Summary of Contents for Hewalex PCWU 200K-2.3kW

  • Page 1: Table Of Contents

    Instruction manual Heat pump water heater PCWU 200K-2.3kW PCWU 300SK-2.3kW Contents General 1. Safety rules for installation..................2. Warranty terms......................3. Recycling and utilization................... 4. Environmental requirements ................... Operation instruction (for user) 1. General ........................2. Cost saving....................... 3. Heat pump structure ....................
  • Page 2 3. Installlation ......................... 3.1 Connection heat pump with other devices ............Air supply ......................3.3 Power supply ......................PCWU 200K-2.3kW 3.4 Condense discharge ....................4. Maintenance ....................... PCWU 300SK-2.3kW 5.1 Air filter and air supply pipe................... 5.2 How to remove the top cover in order to clean the evaporator......
  • Page 3: General

    At the end of this manual, a warranty card with the following terms is attached. It is required all customers to complete this warranty card in order to use it for potential warranty claims in the future. A) It is forbidden to repair the unit without contacting HEWALEX service team. In case of any malfunction or failures, please inform us via telephone ((32) 214 17 10) or E-mail (serwis@hewalex.pl).
  • Page 4: Recycling And Utilization

    F) The tank installation shall avoid direct metallic connections with water pipelines. In case that you have to use metal connection ( ie, copper or steel), please apply isolation devices ( ie, PA66 Gf30 - included as free accesories for heat pump, but also availabe from HEWALEX offer lists) G) Please select correct mounting position of the heat pump unit (See installation and service point 2: Select the installation location).
  • Page 5: Cost Saving

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW The COP is calculated by this fomula: Heating capacity COP = Input power The COP value generally depends on the air inlet temperature which serves as the heating source, and the rated water temperature. The higher COP value, the better performance of the heat pump.
  • Page 6: Heat Pump Structure

    Danfoss expansion valve Heat pumps from PCWU 200K-2.3kW and PCWU 300SK-2.3kW series are equipped with thermal expansion valve from Danfoss. The expansion valve in heat pump system is with respect to its function the counterpart of the compressor. It controls the amount of liquefied refrigerant streaming under high pressure towards the evaporator.
  • Page 7: Controller Instruction

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 4. Controller instruction 4.1 Driver map MENU Login [default 0000] Parameter settings Heat pump par. Switch on heat pump [YES/NO, default YES] Tap water temperature heated by heat pump [10-55°C, default 50°C] Min.
  • Page 8 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 4.2 To start the heat pump After power supplied, it takes few seconds to initiate the controller. The following messages will be displayed on the screen. Please do not touch any key at this time.
  • Page 9 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Press On/off button to switch on or switch off the device. Before switching off the device, a confirmation screen will be displayed. Press OK button and the device will be switched off.
  • Page 10 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Heat pump par. You can set the required minimum inlet air temeprature for Min. temp. heat pump operation (in case of that you are using outdoor switching air as heating source).
  • Page 11 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Parameters of electrical heater E The first parameter is to enable or disable electrical heater (as shown below left). By pressing OK.,YES will start flashing. Use arrow buttons to change YES to NO. Accept your change by pressing OK again. If you don’t want to save your change, cancel it by ESC button (parameter value will go back to previous setting).
  • Page 12 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Parameters for solid fuel boiler B If a solid fuel boiler is combined in system, you can set the Max. temp. switching off boiler pump (as shown below left). Possible range lays in 10-85°C (factory setting 65°C)
  • Page 13 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Time program Setting operation of time program for all devices are the same. When you enter time program setting screen, you can see 3 lines that symbolizing 3 situations: Mo-Fr (Monday to Friday), Sa (Saturday) and Su (Sunday). You can define the working time at hourly interval in different days of week.
  • Page 14 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 4.4 Controller settings The users have possibility to change settings of controller, like date and time, display and sounds. Controller settings Controller settings Sounds Date and time Port RS485 Display Language...
  • Page 15: Equipment Maintenance

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 4.4 Measured parameters The value of all measurable parameters can be read from Measured parameters: Measured parameters in main menu. Here you can check out 11.3 C real values of all temperatures sensors in system and states of 14.5 C...
  • Page 16: Operating Faq

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 7. Operating FAQ Basing on our service experience, a number of most frequently asked questions relating to heat pump operation are listed below: 1) Which is better? To operate heat pump at night when the tariff is lower or operate in the day with warmer air inlet? Normally there is no significant difference in the case of cost.
  • Page 17: Installation Service Instruction (For Installers)

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Installation service instruction (for installers) 1. Storage and transportation During storage, heat pump shall be protected with foil and carton box as the factory package and prevent from water or flood.
  • Page 18 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 290/ The foundation of heat pump must be able to support the whole device even when the tank is 402 kg filled with water. For 200L version, it will be 290 kg, and for 300L version, 402kg.
  • Page 19: Installlation

    Symbols: electrical heater 1.5kW factory configuration mixing valve ie.ESBE VTA322 (3/4") [NO. in katalog. HEWALEX 70.70.00] safety valve max. 7 bar included in factory configuration AKE WYA-20 3/4" cold water input expansive vessel min. 12L ie. ELBI D18 [NO. on katalog. A202L24] connector 3/4"...
  • Page 20 (difference to scheme 1 is circulation pump application) connector 3/4" in case of using metallic pipes, isulation adapter shall be applied apply to model PCWU 200K-2.3kW and PCWU 300SK-2.3kW (ie. adapter PA66 GF30) Boiler pump can be connected to terminal 3 and 4. Then...
  • Page 21 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Reference resistance values to simulate temperature for boilers from different brands: Resistor R1 [kΩ] Resistor R2 [kΩ] Resistor R1 [kΩ] Resistor R2 [kΩ] Boiler manufacturer Boiler manufacturer Temp. 20 ¸ 30°C Temp.
  • Page 22 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW solar collector ambient temperature sensor condensate discharge flexible hose inner ɸ21mm connector 3/4" in case of using metallic pipes isulation adapter shall be applied (ie. adapter PA66 GF30) hot water output...
  • Page 23: Air Supply

    RL07. For model PCWU 300SK-2.3kW, air filter is included, which shall be regularly cleaned. But for model PCWU 200K-2.3kW, due to space limitation, there is no air filter in heat pump. The total resistance of air supply pipe including additional ventilation pipeline(if any) shall not exceed 40 Pa.
  • Page 24: Power Supply

    In model PCWU 200K-2.3kW, due to space limitation, filter cannot be integrated into heat pump. It is suggested for the users to install external filter at air inlet side in accordance with the guidance in section 3.2 Air...
  • Page 25: How To Remove The Top Cover In Order To Clean The Evaporator

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 5.2 How to remove the top cover in order to clean the evaporator? Unscrew these 2 screws as shown on Remove those 4 screws connecting the top Remove the aluminum panel forward and put...
  • Page 26: Emptying And Cleaning Of The Water Tank

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 5.5 Emptying and cleaning of the water tank 1. Turn off the code water inlet and disconnect the main power supply. 2. Empty the water in the tank via drainage connection in the bottom.
  • Page 27: Function Of Switching Off Heat Pump Automatically When Cop Is Low

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 6.4 Function of switching off heat pump automatically when COP is low When air inlet temperature is lower than the setting value, heat pump will be blocked to avoid low efficiency work. This function is designed to have an intelligent system, which can automatically choose the most economical source for heating.
  • Page 28: Manual Control

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Solid fuel boiler B [visible in the diagram No. 3,8,9 ] Max. temp. switching off boiler pomp [10-85°C, default 65°C] Min. temp. switching on boiler pump [30-60°C, default 45°C] Difference in temp. switch boiler pump on [5-15°C, default 8°C]...
  • Page 29 Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Parameters of heat pump There is one more parameter in installer level than user level: Hysteresis temp. switch heat pump on. It is to define the Heat pump par.: temperature difference to target, which will restart heat pump to Histeresis maintain water temperature.
  • Page 30: Alarms

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Maximum defrosting duration The second parameter is defrosting duration. It will limit the longest Heat pump par.: defrosting time in one defrosting cycle. If it is expired, heat pump will resume to normal operating no matter whether defrosting Max.
  • Page 31: Alarm List

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 8.3 Alarm list Alarm Alarm Potential reasons Solution Consequences name 1) Bad connection of sensor ( teminals to the 1) Check whether the connection Absent value of control board is loosen, cable skin isolated...
  • Page 32: Technical Data

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW Technical data 1. Dimensions ø560 ø150 Overheating protection switch and titanium anode Safety valve connection Magnesium anode Hot water out Prepared for temp. sensor Electrial heater Water circulation Boiler coil inlet...
  • Page 33: Parameter Table

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 2. Parameter table Model PCWU 200K-2.3kW 300SK-2.3kW Heating capacity Tank volume Input work Running current 2.78 2.78 Working efficiency COP 3.84 3.84 (A15/W15-45) Power supply V~/Hz 230/50 230/50 Compressor quantity Compressor type...
  • Page 34: Performance Charts

    15 - 35 C 15 - 45 C 15 - 55 C Air inlet temperature 15 - 35 C 15 - 45 C 15 - 55 C Air inlet temperature Data based on model PCWU 200K-2.3kW and PCWU 300SK-2.3kW tests...
  • Page 35: Electrical Diagram

    Instruction manual Heat pump water heater PCWU 200K-2.3kW/PCWU 300SK-2.3kW 5. Electrical diagram PCWU 200K-2.3kW OUT C OUT F IN external controller OUT D RL09L RL09N RL10L RS485 RS485 COMP RL10N RL11L S13+ S13- RL11N S14+ S14- S15+ Sterownik S15- S16+...
  • Page 36: Warranty Card

    9. Detailed warranty conditions can be find in the manual (point 2 instruction: Warranty terms): It is forbidden to repair the unit without contacting HEWALEX service team. In case of any malfunction or failures, please inform us via telephone ((32) 214 17 10) or E-mail (serwis@hewalex.pl).