Network Adapter Installation Guide Introduction The Radionics D6680 Network Adapter is a two-channel network adapter. The D6680 includes a cable for connecting to DB25 Channel 1 Port. For most NetCom installations, only one channel needs to be used and configured.
AC maximum operating range 100 to 240 VAC ~ 50/60 Hz 0.2 Amp maximum Standby Power An Uninterrupted Power Supply is required for use with the D6680, when used for UL FIRE Protective Signaling Systems. A 60-hour minimum UPS standby power supply is required for UL Certification.
Page 3
Signaling, the D6680 must be mounted in a separate enclosure like the AE1 (grey) or the AE2 (red). Before installing the D6680 in the AE1 or AE2 enclosure, the correct mounting holes must be found on the back wall of the enclosure. Only these holes line up correctly to allow the D6680 to be secured with two screws.
Page 4
10. Attach the cover to the cover plate with the four #6 self-tapping screws provided. Programming Refer to the D6600 NetCom System Guide (P/N: 46542) for information on how to program the D6680. Additional UL Requirements The D6680 must be installed in the same room as the D6600 Central Station Receiver and within 50 ft.