Hitachi RAK-25QXA Installation Manual page 2

Indoor unit split unit air conditioner
Hide thumbs Also See for RAK-25QXA:

Advertisement

1
Preparation of Pipe
Use a pipe cutter to cut
Trimming tool
the copper pipe.
Copper pipe
CAUTION
!
Jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming
to prevent copper chips from entering the pipe.
Before fl aring, please put on the fl are nut.
Die
Die
Copper pipe
Recommend to use
R410A fl aring tool.
A (mm)
Outer
Thickness
Flare tool for R410A
Diameter (mm)
(mm)
Clutch type
Clutch type
~
6.35 (1/4)
0.0
0.5
0.8
~
9.52 (3/8)
0.0
0.5
0.8
~
12.70 (1/2)
0.0
0.5
0.8
~
15.88 (5/8)
1.0
0.0
0.5
THIS APPLIANCE MUST BE
!
WARNING
EARTHED.
Power supply shall be connected at the rated voltage, otherwise the
unit will be broken or could not reach the specifi ed capacity.
Procedures of Wiring
In case that power is supplied from Indoor Unit
Indoor Unit
30mm
10mm
10mm
GRN + YEL
70mm
Strip wires
WARNING
!
The naked part of the wire core should be 10 mm and fi x it
to the terminal tightly. Then try to pull the individual wire to
check if the contact is tight. Improper insertion may burn the
terminal.
Be sure to use only power cables approved from the authorities
in your country. For example in Germany: Cable type: NYM
3x1.5mm2.
Please refer to the installation manual for wire connection to
the terminals of the units. The cabling must meet the standards
of electrical installation.
There is a AC voltage of 230V between the L and N terminals.
Therefore, before servicing, be sure to remove the plug from
the AC outlet or switch off the main switch.
1
Insulation And Maintenance Of Pipe Connection
The connected terminals should be completely sealed with heat insulator and then tied up with rubber
strap.
Please tie the pipe and power line together with vinyl tape as shown in the fi gure showing the installation
of Indoor and Outdoor units. Then fi x their position with holders.
To enchance the heat insulation and to prevent water condensation, please cover the outdoor part of
the drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
Insulation material for pipe connection
2
Installation Of Remote Controller
The remote controller can be placed in its holder
which is fi xed on wall or beam.
To operate the remote controller at its holder, please
ensure that the unit can receive signal transmitted
from the controller at the place where the holder
is to be fi xed. The unit will beep when signal is
received from the remote controller. The signal
transmission is weaken by the fl uorescent light.
Therefore, during the installation of the remote
control holder, please switch on the light, even
during day time, to determine the mounting location
of the holder.
Operation Test
Please ensure that the air conditioner is in normal operating condition during the operation test.
Explain to your customer the proper operation procedures as described in the user's manual.
3
Power Source And Operation Test
Power Source
CAUTION
!
Please use a new socket. Accident may occur due to the use of old socket because of poor contact.
Please plug in and then remove the plug for 2 – 3 times. This is to ensure that the plug is completely
plugged into the socket.
Keep additional length for the power cord and do not render the plug under external force as this
may cause poor contact.
Do not fi x the power cord with U-shape nail.
<
>
IA1008: A
2
Pipe Connection
In case of removing fl are nut of an Indoor
unit, fi rst remove a nut of small diameter
!
side, or a seal cap of big diameter side will
fl y out. Prevent water from entering into the
CAUTION
piping when working.
Flare nut
Torque
Wrench
wrench
Outer
dia.of pipe
Small dia. side
6.35 (1/4")
Large dia. side
9.52 (3/8")
12.70 (1/2")
15.88 (5/8")
Small dia. side
6.35 (1/4")
Valve
head cap
Large dia. side
9.52 (3/8")
12.7 (1/2")
Valve core cap
Conventional fl are tool
Wing nut type
1.0~1.5
1.5~2.0
1.0~1.5
1.5~2.0
1.0~1.5
1.5~2.5
1.0~1.5
1.5~2.5
Wiring Of The Indoor Unit
For wire connection of the Indoor unit, you need to
remove front panel and electrical cover.
Method to remove front panel
Refer to "FINAL STAGE OF INSTALLATION – How to
Remove The Front Cover".
Method to remove the low cover
Pull the cover at
and
in the directions as
shown by arrows to remove the cover.
Checking for the electric
source and the voltage range
Before installation, the power source must be checked
and necessary wiring work must be completed. To make
the wiring capacity proper, use the wire gauges list below
for the lead-in from a pole transformer and for the wiring
from a switch board of fuse box to the main switch and
outdoor unit in consideration of the locked rotor current.
IMPORTANT
Cable length
up to 16m
up to 15m
up to 25m
Sleeve of
protection pipe
Putty
Putty
The remote
controller must be
Remote
slide in
Controller
the remote
controller holder,
in the direction
as shown in the
fi gure, until it
Remote
hooks at the lower
Controller
end of the remote
Holder
controller holder.
Screw (2 pieces)
3
Removal Of Air From The Pipe And Gas Leakage Inspection
Procedures of using Vacuum Pump for Air Removal
As shown in right fi gure, remove the cap of valve core. Then, connect the charge hose.
1
Remove the cap of valve head. Connect the vacuum pump adapter to the vacuum pump
and connect the charge hose to the adapter.
Fully tighten the "Hi" knob of the manifold valve and completely unscrew the "Lo" knob.
Run the vacuum pump for about 10~15 minutes, then completely tighten the "Lo" knob
2
and switch off the vacuum pump.
Torque N·m
Remove the charge hose and tighten the cap of valve core. Check the cap's periphery
3
(kgf
·
cm)
if there is any gas leakage.
14.0 – 18.0 (140 – 180)
33.0 – 42.0 (330 – 420)
Completely unscrew the spindle of the service valve (at 2 places) in anti-clockwise
50.0 – 62.0 (500 – 620)
4
direction to allow the fl ow of refrigerant (using Hexagonal Wrench key).
63.0 – 77.0 (630 – 770)
19.6 – 24.5 (200 ~ 250)
Re-cap the service valve and tighten using wrench. Check the cap's periphery if there
19.6 – 24.5 (200 ~ 250)
5
is any gas leakage. The task is then completed.
29.4 – 34.3 (300 – 350)
12.3 – 15.7 (125 ~ 160)
Gas Leakage Inspection
Please use gas leakage detector to check if leakage occurs
at the connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop
leakage. (Use the detector provided for R410A).
Connect the
earth cord
After remove the screw
Wire cross-section
and cover, and put the
connecting cords and fi x
1.5mm
2
the cover with screw.
2
2.5mm
2
4.0mm
How to Remove The Front Cover
1 Remove the front panel.
Please remove and attach the front panel by both hands.
Locking mechanism
Front Panel
To remove the front panel,
slide the front panel locking
mechanisms (left and right)
toward the directions as
indicated by arrows in the
illustration, until you hear a
clicking sound.
After opening the front panel by both hands.
Undo the right arm while pushing it inside.
Slide the front panel to right as shown in fi gure. Then remove while
pulling it to front.
Open the electrical cover. Disconnect the wire connector.
2 Remove the fi lters.
3 After removing two screws, pull the center of the front cover towards
you and release the claws.
4 Pull the side faces (lower sections) of the front cover towards you
as shown in the fi gure and remove the cover.
Disconnect the wire connector
Terminal cover
How To Connect The Optional Parts
(RAC Adapter, Wired Remote Control)
Wired remote controller
Fix the wired remote controller cord and RAC
adapter cord by band.
[For all optional part, please refer catalog for part number]
As for connecting to H-Link, a separately purchased
RAC Adapter is required.
To install the wiring the electrical box cover must be opened.
Connect the connector of RAC adapter to CN7.
Assemble back the cover of electrical box.
Please refer to the respective user manual of RAC Adapter
for further details.
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
WIRED REMOTE CONTROLLER
[For all optional part, please refer catalog for part number]
Connection to the electrical box:
Remove the cover of electrical box.
Connect the connector of wired remote controller to CN9.
Assemble back the cover of electrical box.
Please refer to the respective user manual of wired remote
controller for further details.
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
How to Attach the Front Cover
1
Check that the drain pan is securely attached.
2
After installing the front cover onto the unit, hook three
claws at upper side of the cover securely. Then, push
the center of the front cover to lock the claws.
3
Tighten the two screws.
Push to lock the claws
4
Connect the wire connector. Close the electrical cover.
Remove the front
5
Install the fi lter.
panel by pulling it
towards you.
6
Slide the shafts of the right and left arms on the washable
panel along the steps to insert the shafts into the holes
till they stop. After checking that the shafts are securely
inserted, close the panel.
Arm
Step
Firmly insert the front
panel arms by sliding
along the steps located
at the main body
When the meter reaches -101KPa
(-76cmHg) during pumping, fully tighten
the shuttle.
Meter showing pressure
Closed
R410A Manifold
valve
Charge hose
Vacuum pump
Stop
Stop
valve
valve
Vacuum pump adapter
When pumping starts,
slightly loosen the fl are
nut to check of air
sucked in. Then tighten
the fl are nut.
The body of
service valve
Cap of valve
core
Hexagonal
Wrench Key
Cap of valve head
Cap of valve head
RAC Adapter
RAC Adapter cord
Wired remote
controller cord
H-LINK
Slot
Slot
Slide the front panel
locking mechanisms
(left and right) into the
slots located at the
main body, until you
hear a clicking sound.