[ VII Troubleshooting ]
VII Troubleshooting
[1] Troubleshooting
1. Check methods
1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Water inlet thermistor (TH22)
Water outlet thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C)
Normal
4.3k
- 9.6k
(Refer to the thermistor characteristic graph below.)
1) Thermistor characteristic graph
Low-temperature thermistor
Room temperature thermistor (TH21)
Water inlet thermistor (TH22)
Water outlet thermistor (TH23)
Thermistor R
= 15 k
0
Multiplier of B = 3480 k
Rt = 15 exp { 3480(
0°C 15k
10°C 9.6k
20°C 6.3k
25°C 5.2k
30°C 4.3k
40°C 3.0k
(A) Temperature
(B) Resistance