Aurora ZS Pro-F Installation Manual

Universal protocol converter (upc) zs zone sensors
Hide thumbs Also See for ZS Pro-F:

Advertisement

Quick Links

Aurora Universal Protocol Converter (UPC)
ZS Zone Sensors
Installation Guide
IG1582EW 04/14

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZS Pro-F and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Aurora ZS Pro-F

  • Page 1 Aurora Universal Protocol Converter (UPC) ZS Zone Sensors Installation Guide IG1582EW 04/14...
  • Page 3: Table Of Contents

    To communicate through the local access port ..............10   To set up a Local Access connection in the WebCTRL® for OEMs interface ........... 10   Troubleshooting ........................12   ZS Pro or ZS Pro-F ............................. 12   To format a ZS Sensor ............................13...
  • Page 5: What Are Zs Sensors

    ZS Sensors are thermistor-based temperature sensors that may optionally sense humidity, CO , or VOC. ZS Sensors are wired to the Rnet of the Aurora UPC Controller. The following table shows the 4 ZS Sensor models and their features. Sensor...
  • Page 6: Rnet Configuration

    Aurora UPC ZS Zone Sensors Installation Guide Sensor Features LCD display ZS Pro • button to override the schedule and put the zone in an • occupied state, or force the zone to an unoccupied state buttons to change any editable property, such as •...
  • Page 7: Specifications

    Aurora UPC ZS Zone Sensors Installation Guide   Specifications Sensing element Temperature only range and accuracy Range: 32 to 122°F (0 to 50°C) Accuracy: ±0.35°F (0.2°C) Temperature if humidity is included Range: 50 to 104°F (10 to 40°C) Accuracy: 0.5°F (0.3°C)
  • Page 8 Aurora UPC ZS Zone Sensors Installation Guide Overall dimensions Temperature sensor Width: 3 in. (7.62 cm) or temperature with Height: 4-13/16 in. (12.22 cm) humidity sensor Depth: 13/16 in. (2.01 cm) Width: 2-7/8 in. (7.3 cm) Sensor with CO or VOC Height: 4-13/16 in.
  • Page 9: To Address A Zs Sensor

    Aurora UPC ZS Zone Sensors Installation Guide To address a ZS Sensor Each ZS Sensor on an Rnet must have a unique address, but addresses do not have to be sequential. Use the DIP switches on the back of the ZS Sensor to set an address from 0 to 14. (0 is factory default.) Each DIP switch has the value shown in the figure below.
  • Page 10: Wiring And Mounting A Zs Sensor

    Aurora UPC ZS Zone Sensors Installation Guide Wiring and mounting a ZS Sensor The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain, star, or hybrid configuration.   Power requirements Power requirements Temperature only...
  • Page 11: Rnet Wiring Specifications

    Aurora UPC ZS Zone Sensors Installation Guide CAUTION Do not share power between controller's power and external 12 Vdc unless both devices are half wave.   Rnet wiring specifications NOTE Use the specified type of wire and cable for maximum signal integrity.
  • Page 12: To Wire And Mount A Zs Sensor

    Aurora UPC ZS Zone Sensors Installation Guide Listing UL: NEC CL2P, or better   To wire and mount a ZS Sensor PREREQUISITE The Rnet cable is wired to the controller. The shield wire and the ground wire should be inserted into the controller's GND terminal.
  • Page 13 Aurora UPC ZS Zone Sensors Installation Guide Insert the other 4 wires into the ZS Sensor's screw terminal connector. If wiring 2 cables, insert like-colored wires into each terminal. Recommended wiring scheme: Connect To this this wire... terminal... +12V Black...
  • Page 14: To Communicate Through The Local Access Port

    Aurora UPC ZS Zone Sensors Installation Guide To communicate through the local access port You can connect to the Local Access port of the ZS Sensor to perform test and balance or to make changes to any device on the network.
  • Page 15 Aurora UPC ZS Zone Sensors Installation Guide Set the Baud rate to 115200. Click Accept. On the View tab, click the button next to the BACnet/IP network, then select BACnet Local Access. Click Accept. 10 On the Configure tab, select BACnet Local Access, then click Start.
  • Page 16: Troubleshooting

    Aurora UPC ZS Zone Sensors Installation Guide Troubleshooting ZS Pro or ZS Pro-F If display Then... shows... Incorrect or missing Check for errors in WebCTRL® for OEMs. values On the control program's Properties page, select the Rnet Points tab. Verify that values coming in from the sensors and those going out to the sensors are expected values.
  • Page 17: To Format A Zs Sensor

    Aurora UPC ZS Zone Sensors Installation Guide Characters that The sensor may have a memory problem. Try formatting the sensor (page seem out 13). of place   To format a ZS Sensor Formatting a sensor clears its flash memory. Do either of the following to format a sensor: Download the controller that the sensor is connected to.
  • Page 19 Revision Guide: Pages: Description: Date: First Published 15 Apr 2014...
  • Page 20 Product: Aurora UPC ZS Zone Sensors Document Type: Installation Guide Part Number: IG1582EW Release Date: 04/14 ©2014 The manufacturer has a policy of continual product research and development and reserves the right to change design and specifi cations without notice.