Boiler Setup; Combustion Data - TCNet Boiler Controller User And Service Manual

Table of Contents

Advertisement

TCNet Boiler Controller

Boiler Setup

Max. Power kW
Min. Power kW
Feed rate gr/min
Efficiency %
Max auger Curr. A
Curr. Detect latency sec
Grate Open T s

Combustion Data

Fuel Energy kW/kg
Modulator
Mod. Delta :C
Hysteresis :C
Feed Period :C
25
5
380
91
0.5
2
190
4.88
PID
10
2
15
User and Service Manual
The maximum power of the
boiler
The minimum power of the
boiler
The pellet feed amount for a
minute of the auger or other
fuel feeding system.
The total efficiency of the
boiler
The maximum allowable
current drawn by the auger
excitation motor.
The time delay for the auger
current limit alarm
The run time of the grate
open/close actuator.
The energy of a kilogram of
used pellet. (Please refer to the
information on your pellet
package)
The power regulation metod of
the boiler. There are three
modes for power regulation.
(PID [Graph1], 5STEP [Graph2]
or fixed power [Graph3])
The power regulation to reduce
the power of the boiler.
Eg. : The boiler temp. 50 C
Mod.Delta : 10 C
Boiler begins to slow down
when it is reached to 40 C.
The temperature overlimit.
E.g :
The temp.of the boiler is : 50 C
If the hysteresis is set 2 C.
the boiler operates between
50-51 C. If it exceeds the 51 C
,it deflates the flame.
The fuel consumption to reach
the capacity :
E.g : If the feed period is set 15
it feeds 5 gr in every 15 sec.
If the feed period is set 20 it
feeds 7 gr.
If the feed period is set 25.
It feeds 9 gr.fuel in every 25 sec
20