FOR HEALTHY CLIMATE
General
The Healthy Climate
®
germicidal light emits ultraviolet
(UVC) energy, which has been proven effective in
reducing microbes such as viruses, bacteria, yeasts,
and molds.
UVC germicidal lights greatly reduce the growth and
proliferation of mold and other bioaerosols (bacteria
and viruses) on illuminated surfaces.
Germicidal lights are NOT intended to be used for
removal of active mold growth. Existing mold growth
must be appropriately removed PRIOR to installation of
the germicidal light.
Shipping and Packing List
Package 1 of 1 contains:
1 - Healthy Climate
®
germicidal unit
1 - UVC lamp (UV-2000 contains 2 lamps.)
1 - Power cord
1 - Remote door interlock switch with 5 ft(1.5m) power
cord (UV-2000 Only)
1 - Self-adhesive gasket/template
5 - Sheet metal screws with lockwashers
1 - Installation instructions
1 - Homeowners IAQ Guide
1 - ATTENTION! warning sheet
1 - Warranty sheet
2 - UVC Danger labels
Required Tools and Unique Supplies
• Electric drill
• Phillips screw bit or screwdriver
• 1" - 1.5" (25mm-38mm) holecutter
• 1/4" (6mm) drill bit
• Cotton cloth and gloves
• Galvanized flexible elbows will be needed for any
take-offs closer than 6 ft(1.8m) when flex duct is used.
DANGER
Ultraviolet (UVC) Radiation Hazard.
Any exposure will cause significant eye damage
and may cause skin damage.
Do not look into UV light source. Wear UV eye
and skin protection. Access panels must be in
place during appliance operation.
AIR CLEANERS/
FILTERS
505,031M
2005
®
MODELS UV-500, UV-1000, UV-2000
Potential Mold Spore Release.
Application of UVC lights to existing mold growth can
cause respiratory irritation and allergic symptoms.
Do not use UVC lights where active mold growth
exists. Remove active mold growth from surfaces
prior to operation of UV lights.
Risk of property damage, injury, or death.
Installation, adjustments, alterations, service and
maintenance must be performed by a qualified
service technician.
This UVC light appliance emits a light that may be
attractive to children. If you have children in your
household, make certain that they are not exposed
to or allowed to look at the UVC light. Consider hav-
ing a qualified service technician install a Remote
Door Interlock Switch (64X53) as an accessory to
your Air Handling System. UVC light should not be
"seen" after the UV Light appliance is installed.
HEALTHY CLIMATE
GERMICIDAL LIGHT
WARNING
WARNING
WARNING
Electric shock hazard.
Can cause injury or death.
Disconnect all remote electrical
power supplies before servicing.
Access panels must be in place dur-
ing the appliance operation.
212167-04 Rev. 1C 12/05
®

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UV-500 and is the answer not in the manual?

Questions and answers

Summary of Contents for Healthy Climate UV-500

  • Page 1 ® 505,031M 2005 GERMICIDAL LIGHT HOMEOWNERS MANUAL & DEALER INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE ® MODELS UV-500, UV-1000, UV-2000 General WARNING The Healthy Climate ® germicidal light emits ultraviolet Potential Mold Spore Release. (UVC) energy, which has been proven effective in...
  • Page 2: Power Consumption

    Dimensions/Specifications DIMENSIONS: MODEL UV-500/1000 2.5" Model UV-500 - 11" L x 7" W x 2.5" H (279mm x 178mm x 63mm) 7" Model UV-1000 - 11" L x 7" W x 2.5" H 15.25" (279mm x 178mm x 63mm) Model UV-2000 - 17" L x 7" W x 2.5" H (432mm x 178mm x 63mm) 11"...
  • Page 3: Clearances And Requirements

    Duct depth must be at least 16" ance properties. (406mm) to allow for the lamp length. Ensure no plastic parts or wire insulation are exposed The Healthy Climate ® germicidal light must be to UVC light. Do not install in a location that installed a minimum of 6 ft(1.8m) away from...
  • Page 4: Installation

    Lamp and viewport hole Self-adhesive drilling locations for gasket/template. Models UV-500 and UV- 1000. Fig. 3 Insert lamp and fasten with retaining bracket. CAUTION Lamp and viewport hole Sharp Edges Hazard. drilling locations for Equipment sharp edges can cause injuries.
  • Page 5: Harness Connection

    Remove cap. INSTALL REMOTE DOOR INTERLOCK SWITCH interlock to air handler access panel. (Standard with UV-2000. Optional for UV-500, UV-1000. Part No. 64X53.) Fig. 5 Remote door interlock switch installation. Mount the remote door interlock switch so that power to...
  • Page 6 UVC germicidal lamp allows maximum exposure of airborne bioaerosols to the UVC light. This also promotes maximum filtration of the air and preven- tion of thermal stratification (hot at the ceiling, cool on the floor). Model UV-2000 Internal Wiring Model UV-500 Internal Wiring...
  • Page 7: Maintenance

    Potential Risk of Fire. 1. Obtain the correct replacement lamp for your Dust, lint and other debris may cause fire if allowed Healthy Climate ® model. to come in contact with illuminated UVC lamp. 2. Disconnect power to the device.
  • Page 8: Replacement Parts

    Replacement Parts Description UV-500 UV-1000 UV-2000 Base Gasket/Template 64X42 64X42 64X64 Lighted On/Off Switch 64X50 64X50 64X50 Ballast 64X38 64X62 64X62 Cover Interlock Switch 64X45 64X45 64X45 Fuseholder 64X48 64X48 64X48 Fuse 64X49 64X49 64X49 Replacement Parts Not Illustrated Complete Unit w/Lamp(s)
  • Page 9 Installation CHECKLIST FOR COMPLETE INSTALLATION AND SAFETY ITEMS: All items were included in the shipping box and have been installed (see Shipping and Packing List). Danger label installed on door to air handling unit. (See Fig. 6) Additional Danger label installed, if necessary. (See Fig. 6) Note: If exposure to the UVC light is possible in any other situation (e.g.
  • Page 11 Installation CHECKLIST FOR COMPLETE INSTALLATION AND SAFETY ITEMS: All items were included in the shipping box and have been installed (see Shipping and Packing List). Danger label installed on door to air handling unit. (See Fig. 6) Additional Danger label installed, if necessary. (See Fig. 6) Note: If exposure to the UVC light is possible in any other situation (e.g.

This manual is also suitable for:

Uv-1000Uv-2000

Table of Contents