AIR DISTRIBUTION SYSTEMS

For proper air distribution, the supply duct system shall be
designed so that the static pressure does not exceed the
listed static pressure rating on the furnace rating plate.
Three typical distribution systems are illustrated in
Figure 6.
Single trunk duct
Dual trunk duct with crossover connector
Dual trunk duct
*
B
1
Crossover Duct must be centered directly under furnace.
S
2
Use 12" Diameter Round or equivalent insulated Flex---duct only.
S
3
Terminate Flex---duct (opposite furnace) in the center of the trunk duct.
S
4
Flex---duct material must be pulled tight — No Loops or unnecessary dips
S
— Air Flow may be impeded.
A
B *
1
4
Crossover
3
Figure 6 — Air Distribution Systems
Location, size and number of registers should be selected
on the basis of best air distribution and floor plan of the
home.
The Air Temperature Rise is to be adjusted to obtain a tem-
perature rise within the range(s) specified on the furnace
rating plate.
Transition Duct with Branches
Transition duct
Branches