Installation Instructions Thermal-pac & Thermal-duct hot water air handler ECOLOGIX HEATING TECHNOLOGIES INC. 221 Holiday Inn Dr. Cambridge, Ontario N3C 3T2 Phone: 519-658-4330 Fax: 519-658-9384 info@ecologix.ca www.ecologix.ca TP-M11...
Table of Contents IMPORTANT NOTES FOR THE INSTALLER ......................3 TYPICAL PLUMBING CONNECTIONS .........................4 ELECTRICAL WIRING DIAGRAM..........................5 INTRODUCTION...................................9 HOW IT WORKS ...................................9 ....................................9 OOLING ....................................9 EATING ..................................9 ONTINUOUS PRODUCT DESCRIPTION .............................. 10 ....................................10 ABINET ..................................10 EATING OILS ..................................10 AN AND OTOR ................................
IMPORTANT NOTES FOR THE INSTALLER A Quick Check List Are the water connections to the water heater oriented in a way to avoid trapping air in the heating circuit? (see diagram on next page) Is the purge valve installed on the return line from the air handler upstream from the isolation valve? Is the air handler hung and isolated to avoid transmitting vibration through framing and duct work?
ELECTRICAL WIRING DIAGRAM air handler electrical wiring schematic air handler electrical wiring layout -- XELK103 air handler electrical wiring schematic air handler electrical wiring layout -- XELK124 with Cycle Timer TP-M11...
Page 6
For TP75, TDHV-48 and TDHV-60 air handler electrical wiring schematic air handler electrical wiring layout -- XELK113 air handler electrical wiring schematic air handler electrical wiring layout -- XELK134 TP-M11...
Page 7
Physical Properties Cabinet dimensions Supply air Return air water Shipping inlet Model Type d x e f x g Weight outlet TP30, TDHV-12, 20” 14” 24” 12”x16” 12”x16” 1/2” 80 lb. TDHV-18 TP45 to TP75, 22” 22” 31.5” 20”x20” 20”x20”...
Page 8
Blower Motor Full Load (Amps) Circulator Full Load (Amps) 1. Minimum Required. Refer to Design and Installation Instructions for options. 2. All air flows at high speed. 3. Using Ecologix cased slab cooling coils. Above 3.5 tons, use an A-coil. TP-M11...
4330 for answers to questions related to and domestic hot water, eliminating the sizing, installation or trouble-shooting for need for a furnace. any of Ecologix air handlers or water heaters. Combo heating systems are ideally suited for single-family homes, Ecologix provides you with the quietest townhouses and apartments where the operating air handler available.
Once the thermostat is satisfied, speed will over-ride the continuous fan continuous fan speed will resume. PRODUCT DESCRIPTION Ecologix air handlers are certified by: High-density aluminum fins provide Entela Inc. maximum heat transfer for small coil 81 Kelfield St., Unit 7 surface.
Connecting to a Water Heater Any properly sized gas, propane or oil All Ecologix air systems come supplied fired water heater will work in a combo with spring loaded, vertical lift check heating system. Make sure the water valves. These check-valves have been...
2) Select a water heater with an output seasonal adjustment in airflow is that is at least 120% of the heat loss anticipated, parallel main supply ducts must be used. Volume dampers in each of the main supply ducts must be Duct Layout installed and must be accessible for seasonal adjustments.
Air Handler Mounting cabinet remains square. Provide at least 2 feet (0.75 metres) of The Ecologix air handler can be service clearance in front of the access installed in any direction. Its compact panel of the air handler. Zero clearance dimensions even allows for installation is acceptable on all other faces.
Fresh air and HRV connections to Locate outlets at least 6 inches from ductwork can pose a risk of dumping cold outside walls or window coverings. air into ductwork during periods of stand- by or continuous run. Calculate mixed Return Ductwork air stream temperatures and provide interlock controls to prevent freezing Return air plenum should be the same...
thermostats will need 250 ohm, 10 watt resistors on each of the W and Y If the optional fourth relay is installed, the terminals. yellow wires labeled TT on the relay are dry contacts for connection to a boiler or Heat Anticipator Setting external pump.
SERVICE AND MAINTENANCE Filter Air conditioning coil The Ecologix air handler is provided with At the start of each cooling season, a disposable pleated filter. This filter check the drain connection to the cooling should be inspected monthly and coil to ensure it is free of debris.
• Water heater supply tube (dip Pump does not run tube) is restricted or damaged; In areas where hard water is present the check and/or replace. pump may “stick” and fail to run. Often, • Supply water temperature set too closing the isolation valve on the return low or not calibrated properly;...
Fax: 519-658-9384 info@ecologix.ca This product is warranted by Ecologix Heating Technologies Inc to be free from defects in materials and workmanship that affect product performance under normal use and maintenance within the applicable periods specified below. Replacements furnished will carry only the un-expired portion of the original warranty.